3) One or more large trees on the property may be likely to fall on the structure, and are a potential safety hazard. Recommend consulting with a qualified arborist to determine if tree(s) need to be removed and/or pruned.
|
   |
|
4) The rear set of stairs are wobbly. A qualified contractor should evaluate and repair as necessary, such as installing additional supports and/or diagonal bracing.
|
  |
|
5) Bottom step on rear stairs missing one cross brace. This should be replaced immediately as it presents a fall hazard.
|
  |
|
6) One or more wall-mounted exterior light fixtures have wiring that's subject to water intrusion due to caulk not being installed around the light fixture's back plate. Caulk should be applied around the perimeter of back plates where missing. A gap should be left at the bottom for condensation to drain out.
|
  |
|
7) One or more outside faucets are missing backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the house. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.
Recommend installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit: http://edis.ifas.ufl.edu/BODY_AE079
|
   |
|
8) Although the rear deck was covered with snow, the inspector did notice several loose planks. It is recomended that the client look closely at the deck planks after the snow has melted to determine if there is a need for maitenance or repair.
|
  |
|
9) Fences and/or gates are damaged and/or deteriorated in some areas. A qualified contractor should evaluate and make repairs or replace sections as necessary.
|
  |
|
10) Fascia boards are damaged or deteriorated in one or more areas. A qualified contractor should evaluate and make repairs as necessary.
|
 |
 |
11) Soffits at one or more cantilever or overhang sections are unvented. This can result in moisture accumulation in floor cavities and rot. A qualified contractor should install screened vents in soffits where missing and as per standard building practices.
|
 |
|
12) One or more large trees are very close the foundation. Tree roots can cause significant structural damage to foundations. Recommend having a qualified tree service contractor or arborist remove trees as necessary to prevent damage to the structure's foundation.
|
 |
|
13) Gaps exist at one or more openings around the exterior, such as those where outside faucets, refrigerant lines, and/or gas supply pipes penetrate the exterior. Gaps should be sealed as necessary to prevent moisture intrusion and entry by vermin.
|
 |
|
14) One or more outside faucets aren't anchored securely to the structure's exterior. Fasteners should be installed or replaced as necessary so faucets are securely anchored to prevent stress on plumbing supply lines and possible leaks.
|
 |
 |
15) This property is clad with composition wood fiber siding. Many brands of this type of siding by different manufacturers are known to deteriorate and/or fail prematurely due to moisture penetration. Failure is typically visible in the form of swelling, cracking and delamination, especially at the bottom edges. Class action lawsuits have been filed or are being filed against most manufacturers of this material.
Some areas of siding on this structure show the symptoms described above, but it appears that the siding hasn't deteriorated to the point of needing replacement, some repairs have been performed Some manufacturers (Louisiana Pacific) recommend a repair process for this siding where affected areas are sealed with "Permanizer Plus", a flexible primer made by Pittsburgh Paint, followed by two coats of 100% acrylic latex paint. This sealant must be applied to the bottom edges using a brush. The face of the siding can be sprayed. The "Permanizer Plus" sealer isn't required for edges that aren't swollen, cracked or deteriorated, but the acrylic latex should still be brushed on these edges.
At a minimum, recommend having a qualified contractor seal and repaint as described above, or by other methods specified by the siding's manufacturer. The client(s) may wish to have a qualified contractor evaluate further to determine if some or all of the siding should be replaced.
For more information, visit: Pittsburgh Paints, PRIMERS -THE FOUNDATION FOR A TOP QUALITY JOB Failing LP Siding Help Page
|
 |
 |
16) Caulk is missing or deteriorated in some areas and should be replaced and/or applied where necessary. For more information on caulking, visit The Ins and Outs of Caulking.
|
 |
 |
17) The exterior finish in some areas is failing. A qualified contractor should prep (pressure wash, scrape, sand, prime caulk, etc.) and repaint or restain areas as needed and as per standard building practices.
|
 |
|
18) Minor cracks were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
|
 |
|
19) Sidewalks were covered with snow, unable to determine their condition.
|
 |
|
20) Several gutters were full of snow, preventing a thourough inspection. However, the gutters that were not full of snow appear to be in servicable condition with proper slope towards drain pipes.
|
| |
|
21) The header joist on the rear porch has pulled slightly away from the support. This can be easily repaired by reseating the nails, or addeding deck screws to tighten the board before it gets worse.
|
| |
|
22) The front porch has moved slightly from its original postion over the years. Although this doesn't appear to be of a sturctural concearn, it should be patched to prevent insect, water, and rodent intrusion.
|
   |
|
27) The vehicle door isn't balanced. The door won't stay in place when it's partially opened and falls to the ground instead. This is a safety hazard since the door may fall when open. A qualified contractor should evaluate and make repairs as necessary. For more information on garage door safety issues, visit: http://www.cpsc.gov/cpscpub/pubs/523.html or http://www.ohdstl.com/safety.html
|
   |
|
28) The auto-reverse mechanism on the vehicle door opener is inoperable or requires too much force to activate. This is a safety hazard, especially for small children. A qualified contractor should evaluate and repair as necessary. For more information on garage door safety issues, visit: http://www.cpsc.gov/cpscpub/pubs/523.html or http://www.ohdstl.com/safety.html
|
   |
|
29) One or more garage electric receptacles appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all garage receptacles, except for one for use with a refrigerator or freezer, have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
|
  |
|
30) Weatherstrip around or at the bottom of the garage-house door is damaged or deteriorated. It should be replaced as necessary to prevent vehicle fumes from entering living spaces.
|
  |
|
31) No infared "photo eye" devices are installed for the vehicle door's electric door opener. They've been required on all vehicle door openers since 1993 and improve safety by triggering the vehicle door's auto-reverse feature without need for the door to come in contact with the object, person or animal that's preventing it from closing. Recommend considering having a qualified contractor install these devices for improved safety. For more information on garage door safety issues, visit: http://www.cpsc.gov/cpscpub/pubs/523.html or http://www.ohdstl.com/safety.html
|
  |
|
32) The exterior entrance door has window highlight inserts installed rather than a solid core door. This may represent a security hazard since these doors are easily broken. Windowed exterior entrance doors should be replaced with solid core doors by a qualified contractor.
|
 |
|
33) Weatherstrip at the sides of the vehicle door is missing. It should be installed where missing to prevent water and vermin intrusion.
|
 |
|
34) The interior perimeter of the garage is excluded from this inspection due to lack of access from stored items.
|
   |
|
40) The water heater flame is yellow rather than blue. This may be caused by scale on top of the burner, a dirty burner orifice, the flue being clogged, and/or improper gas pressure. A qualified contractor should evaluate and repair as necessary.
|
  |
|
41) The drain line to the water heater's temperature-pressure relief valve terminates less than 6 inches from the floor. This is a potential safety hazard due to the risk of explosion. A drain line that terminates less than 6 inches from the floor can result in the water heater exploding if or when the valve opens due to restricted venting. The drain line should be modified, and by a qualified contractor if necessary, so it terminates 6" from the floor.
|
  |
|
42) The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be approaching this age and may need replacing in the near future. Recommend budgeting for a replacement in the near future.
|
| |
|
43) The doors that close off the water heater and furnace come off of the track. It appears that the Track head is comming loose from the frame. The track footing guide is not installed, keeping the doors from staying in alignment.
|
  |
|
44) Significant amounts of debris, dirt and/or dust are visible in one or more sections of supply and/or return air ducts. This can be a health hazard, especially for those with allergies or respiratory problems. The Environmental Protection Association (EPA) recommends considering having ducts professionally cleaned when "ducts are clogged with excessive amounts of dust and debris and/or particles are actually released into the home from your supply registers". At a minimum, the visible debris should be thoroughly cleaned. Recommend having a qualified contractor clean the ducts. For more information on duct cleaning in relation to indoor air quality, visit: http://www.epa.gov/iaq/pubs/airduct.html
|
  |
|
45) The estimated useful life for most forced air furnaces is 15 to 20 years. This furnace appears to be approaching this age and may need replacing at any time. Recommend budgeting for a replacement in the near future.
|
 |
|
46) One or more rooms' interior doors have no gap below, or have a gap less than 3/4". As a result, return air flow out of the room is restricted with closed door(s) and the heating/cooling system on. This may result in the heating and/or cooling system having a reduced efficiency and higher energy costs. To allow adequate return air flow, recommend either trimming the bases of doors as necessary to maintain a 3/4" gap below, or leaving doors open while the heating or cooling system is in operation.
|
  |
|
47) The last service date of this system appears to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. This servicing should be performed annually in the future.
|
  |
|
48) Copper water supply pipes in homes built prior to 1986 may be joined with solder that contains lead. Lead is a known health hazard, especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained about 50 percent lead. The client(s) should be aware of this, especially if children will be living in this structure. Evaluating for the presence of lead in this structure is not included in this inspection. The client(s) should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions such as these may be advised:
Flush water taps or faucets. Do not drink water that has been sitting in the plumbing lines for more than six hours. Install appropriate filters at points of use. Use only cold water for cooking and drinking. Hot water dissolves lead more quickly than cold water. Use bottled or distilled water. Treat well water to make it less corrosive. Have a qualified plumbing contractor replace supply pipes and/or plumbing components as necessary.
For more information visit: http://www.cpsc.gov/CPSCPUB/PUBS/5056.html http://www.epa.gov/safewater/lead/index.html
|
  |
|
49) The water supply pressure is greater than 80 psi. Pressures above 80 psi may void warranties for some appliances such as water heaters or washing machines. Flexible supply lines to washing machines are more likely to burst with higher pressures. Typically the pressure cannot be regulated at the water meter. Recommend having a qualified plumber evaluate and make modifications to reduce the pressure below 80 psi. Installing a pressure reducing valve on the main service pipe is a common solution to this problem. If one exists, then it should be adjusted for lower pressures.
|
  |
|
50) There is a very large plastic bin filled with water sitting where the washing machine would normally sit. Unaware of its purpose. The drain for the washer also appears to have been cut flush with the wall .
|
 |
|
51) The inspector was not able to find the water meter. Recommend that the client(s) attempt to find the water meter by consulting with the property owner(s), searching for it themselves, or consulting with the local water municipality. It is especially important to find the meter if no main shut-off valve is found because the meter may be the only way to turn off the water supply in the event of an emergency, such as when a supply pipe bursts.
|
| |
|
52) Turning on the rear outside faucet produced a momentary surge of brown water, then ran clear. The water in the house also has a sulfur smell to it. This may be because the house may have been vacant for a while. Recommened operating ALL faucets for about 5-10 minutes to flush out the system, as well as draining and flushing the water heater as well. This will removing any stagnant water that may have been sitting for some time.
|
| |
|
53) Vinyl flooring in the laundry room shows evidence of past water damage. The dryer vent has been stuffed with paper towels that will need to be removed before use.
|
   |
|
58) One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
|
  |
|
59) The dishwasher drain line is not configured with a "high loop" or "air gap". A high loop is created by routing the drain line up to the bottom surface of the counter top above, and securely fastening it to that surface. It is meant to prevent water from siphoning out of the dishwasher, and to prevent water from the sink drain or food disposal from entering the dishwasher. Some dishwashers have a built-in high loop where one is not required to be configured in the drain line. The clients should try to determine if a high loop is required for this brand and model of dishwasher (review installation instructions, etc.). If one is required, or it cannot be determined if one is not required, then a qualified contractor should install a high loop as per standard building practices.
Also, no "air gap" is installed. Air gaps are another device meant to prevent water from the sink drain or food disposal from entering the dishwasher. These are required in some municipalities for new construction and when remodeling. The client(s) should consult with a qualified contractor to determine if an air gap should be installed.
|
  |
|
60) The dishwasher's door seal is damaged, deteriorated, misaligned or otherwise does not seal well. A qualified appliance technician should evaluate and repair as necessary.
|
  |
|
61) Drawers are difficult to open and close in one or more cabinets. A qualified contractor should evaluate and repair as necessary.
|
 |
|
62) Refrigerator and freezer were turned down to thier lowest settings. Unable to check effective operating tempature of either.
|
 |
|
63) The range hood fan vents into the kitchen rather than outdoors. Ventilation may be inadequate and moisture may accumulate indoors. Recommend having a qualified contractor make modifications as necessary as per standard building practices so the range hood fan vents outdoors.
|
 |
 |
64) Caulk is missing and/or deteriorated where countertops meet backsplashes in wet areas, such as around sinks. Caulk should be replaced where deteriorated and/or applied where missing to prevent water damage.
|
 |
|
65) Light fixture above sink appear to be inoperable. Recommend further evaluation by replacing bulb(s) and/or consulting with the property owner(s). Repair or replacement of the light fixture by a qualified electrician may be necessary.
|
 |
|
66) The dishwasher appears to be near, at, or beyond its intended service life of 10 to 15 years. Recommend budgeting for replacements as necessary.
|
 |
|
67) The refrigerator ice maker is in the "off" position. The inspector was unable to evaluate this component.
|
 |
|
68) Water stains and/or evidence of past water damage was found in the shelving or cabinet components below the sink. The client(s) should evaluate and consider having repairs made.
|
| |
|
69) Cover ring around drain pipe under sink is broken and sould be repaired/replaced as necessary.
|
| |
|
70) Side wall in cabinet under counter between the sink and the stove has come loose and should be repaired/replaced as necessary.
|
| |
|
71) Baseboards around the kithen and dining room are missing.
|
| |
|
72) The wood flooring in the kitchen/dining room appears to have been recently replaced. However, there are two substaintial scratches on the new floor from what appears to be from replacing the kitchen appliuances back after the floor was put in.
|
   |
|
73) Receptacle that serves countertop surface is within six feet of a sink appears to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that receptacle that serves countertop surface within six feet of sink has GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
|
 |
 |
74) Caulk is missing and/or deteriorated where countertops meet backsplashes in wet areas, such as around sinks. Caulk should be replaced where deteriorated and/or applied where missing to prevent water damage.
|
 |
|
75) The enamel coating on one or more sinks is damaged and/or deteriorated. For example, chipped or worn, and/or rust on some exposed steel. However, no leaks were found due to the deterioration. The client(s) should evaluate to determine if the sinks should be replaced.
|
 |
|
76) One or more toilets have no water supply and could not be fully evaluated. The shut-off valve(s) may be turned off, or repairs may be necessary. The client(s) should ask the property owner(s) about this, and have a qualified plumber evaluate and repair if necessary.
|
 |
|
77) Water stains and/or evidence of past minor water damage was found in the shelving or cabinet components below the sink. The client(s) should evaluate and consider having repairs made.
|
  |
|
78) Cover plate is missing screws. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plate screws should be installed where missing.
|
  |
 |
79) Tile and/or grout around one or more bathtubs is damaged or deteriorated. For example, deteriorated or missing grout, cracked, missing or loose tiles, etc. A qualified contractor should evaluate and repair tile and/or grout as necessary.
|
  |
|
80) Toilet "runs" after being flushed, where water leaks from the tank into the bowl. Significant amounts of water can be lost through such leaks. A qualified plumber should evaluate and repair or replace components as necessary.
|
 |
 |
81) Caulk is missing on old screw points for shower stall door frame. It should be applied where missing to prevent water intrusion and damage to the wall structure and underlying tile.
|
 |
|
82) One or more light fixtures appear to be inoperable. Recommend further evaluation by replacing bulb(s) and/or consulting with the property owner(s). Repairs or replacement of the light fixture(s) by a qualified electrician may be necessary.
|
  |
|
83) Water stains and/or evidence of past minor water damage was found in the shelving or cabinet components below the sink. It also appears that the plumbing is fairly new, indicating that any past leaks may have been repaired. The client(s) should moitor this area to make sure repairs were effective.
|
 |
|
84) One or more light fixtures have missing bulbs and could not be fully evaluated. Bulbs may simply need to be installed, or repairs or replacement may be necessary.
|
  |
|
94) Carpeting in one or more rooms is loose and poses a trip hazard. A qualified carpeting installation contractor should restretch or replace carpet as necessary.
|
   |
|
95) A screw in the outer sash of the window prevents the screen from sitting flush with the window frame. This should be repaired to prevent insect intrusion.
|
 |
|
96) One window that opens, comes loose on thge track, and is sometimes difficult to open, but will open. Repairs should be made as necessary, and by a qualified contractor if necessary so windows open fully, and open and close easily.
|
 |
|
97) The safety mechanism on one window is missing and/or damaged so that they are inoperable. Repairs should be made by a qualified contractor or service technician so that the windows safety mechanism works correctly.
|
 |
|
98) Carpeting in one or more rooms is soiled and/or stained. Recommend having carpeting professionally cleaned as necessary.
|
  |
|
99) Batteries in all the smoke alarms should be replaced after taking occupancy, and annually in the future. "Chirping" noises emitted from smoke alarms typically indicate that batteries need replacing. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html
|
  |
|
100) Ceiling fan in dining room wobbles slightly during operation. This may be caused by one or more of the following:
Loose screws Loose blade(s) A loose connection between the rod and the fan body A loose connection between the fan body and the electric box above Misaligned blades Bent or warped blades Unbalanced blades
Recommend having a qualified contractor evaluate and repair as necessary. For more information, visit:
http://www.faninfo.com/ceiling_fans_balance.html http://thefanshop.com/fanfaq/maintenance.htm http://www.lampdepot.com/service/wobble_problems.htm
|
 |
|
101) The doorbell button is loose or damaged. It should be repaired or replaced as necessary, and by a qualified contractor if necessary.
|
 |
|
102) Screen(s) in one or more windows are loose due to a raised screw on the outside of the screen at the windows edge.Screens should be repaired where necessary.
|
 |
|
103) The front door has a minor dent on the inside surface. This is strictly cosmmetic and doesn't affect the operation or safety of the door. It also is missingthe striker plate for the dead bolt, which should be repaired.
|
 |
|
104) Carpeting in one or more rooms is soiled and/or stained. Recommend having carpeting professionally cleaned as necessary.
|