
 
 
| Client(s): | Home Buyer | 
| Property address: | 1234 Perfect Street Ocean, California | 
| Inspection date: | Saturday, September 22, 2012 | 
This report published on Tuesday, April 29, 2014 9:39:56 AM PDT
|  | Safety | Poses a risk of injury or death | 
|  | Major Defect | Correction likely involves a significant expense | 
|  | Repair/Replace | Recommend repairing or replacing | 
|  | Repair/Maintain | Recommend repair and/or maintenance | 
|  | Future improvements | Recommended correction for future improvements | 
|  | Maintain | Recommend ongoing maintenance | 
|  | Evaluate | Recommend evaluation by a specialist | 
|  | Monitor | Recommend monitoring in the future | 
|  | Serviceable | Item or component is in serviceable condition | 
|  | Comment | For your information | 
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp
 This structure is in an overall good condition with no deferred maintenance issues or concerns, and is in a good overall structural condition, with no signs of settlement or stress cracks visible, except as noted in this report.
This structure is in an overall good condition with no deferred maintenance issues or concerns, and is in a good overall structural condition, with no signs of settlement or stress cracks visible, except as noted in this report.
|  Photo 1-1 | 
 Structures built prior to 1979 may contain lead-based paint and/or asbestos in various building materials such as insulation, air ducts, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client(s) should consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit these websites:
Structures built prior to 1979 may contain lead-based paint and/or asbestos in various building materials such as insulation, air ducts, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client(s) should consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit these websites:

 One or more trip hazards were found in the driveway due to cracks, settlement and/or heaving. Recommend having a qualified contractor evaluate and repair or replace driveway sections as necessary to eliminate trip hazards.
One or more trip hazards were found in the driveway due to cracks, settlement and/or heaving. Recommend having a qualified contractor evaluate and repair or replace driveway sections as necessary to eliminate trip hazards.
|  Photo 3-1 |  Photo 3-2 | 
|  Photo 3-3 | 

 One or more hornet, bee and/or wasp nests were found. These can pose a safety hazard. Nest(s) should be removed as necessary.
One or more hornet, bee and/or wasp nests were found. These can pose a safety hazard. Nest(s) should be removed as necessary.
|  Photo 4-1 | 

 The driveway has significant cracks and/or deterioration in one or more areas. A qualified contractor should evaluate and repair or replace driveway sections as necessary.
The driveway has significant cracks and/or deterioration in one or more areas. A qualified contractor should evaluate and repair or replace driveway sections as necessary.
|  Photo 5-1 |  Photo 5-2 | 
 One or more gutters are missing. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Install gutters and downspouts where missing. Also, extensions such as splashblocks or tie-ins to underground drain lines should be installed as necessary to carry rain water away from the house.
One or more gutters are missing. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Install gutters and downspouts where missing. Also, extensions such as splashblocks or tie-ins to underground drain lines should be installed as necessary to carry rain water away from the house.
|  Photo 6-1 |  Photo 6-2 | 
 Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.
Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.
|  Photo 7-1 | 
 Other concerns.
Other concerns.
|  Photo 8-1 |  Photo 8-2 | 
|  Photo 8-3 Buried clean out pipe |  Photo 8-4 | 
|  Photo 8-5 Missing metal brackets at post beam connection on the shade structure |  Photo 8-6 One side gate drags on the concrete driveway | 
 This structure's exterior components is in a good overall condition with no major maintenance concerns, except as noted in this report.
This structure's exterior components is in a good overall condition with no major maintenance concerns, except as noted in this report.
|  Photo 9-1 |  Photo 9-2 | 
|  Photo 9-3 | 
 Minor cracks were found in sidewalk or patio sections. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
Minor cracks were found in sidewalk or patio sections. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
|  Photo 10-1 |  Photo 10-2 | 
 Trees are overhanging roof and are within 10 feet of roof vertically. This is a conducive condition for wood destroying insects and organisms since organic debris such as leaves or needles are more likely to accumulate on the roof surface. Accumulated debris may cause water to enter gaps in the roof surface and leak into attic and/or interior spaces. Trees should be pruned so they are at least 10 feet above roof, or don't overhang the roof.
Trees are overhanging roof and are within 10 feet of roof vertically. This is a conducive condition for wood destroying insects and organisms since organic debris such as leaves or needles are more likely to accumulate on the roof surface. Accumulated debris may cause water to enter gaps in the roof surface and leak into attic and/or interior spaces. Trees should be pruned so they are at least 10 feet above roof, or don't overhang the roof.
|  Photo 11-1 | 
 Composition tabbed shingles are installed on roof sections with a slope less than 3/12 (three inches rise for every 12 inches run). Most shingle manufacturers won't warranty composition shingles if used on a roof with a slope less than 3/12. Monitor the roof and interior spaces below for leaks in the future. Ideally, or if leaks occur, a qualified roofing contractor should replace the roof surface with materials intended for low slopes such as a "torch down" roof.
Composition tabbed shingles are installed on roof sections with a slope less than 3/12 (three inches rise for every 12 inches run). Most shingle manufacturers won't warranty composition shingles if used on a roof with a slope less than 3/12. Monitor the roof and interior spaces below for leaks in the future. Ideally, or if leaks occur, a qualified roofing contractor should replace the roof surface with materials intended for low slopes such as a "torch down" roof.
|  Photo 12-1 | 
 Roof is in serviceable condition showing no signs of extensive wear or deferred maintenance, except as noted in this report.
Roof is in serviceable condition showing no signs of extensive wear or deferred maintenance, except as noted in this report.
|  Photo 13-1 |  Photo 13-2 | 
|  Photo 13-3 |  Photo 13-4 | 
|  Photo 13-5 |  Photo 13-6 | 

 There are large slab cracks in the garage floor slab. Garage slab is not a part of the structural slab in this structure, and the cracks does not indicate a major structural concern. Replace the garage's concrete slab with a new slab, metal reinforcement, and moisture barrier.
There are large slab cracks in the garage floor slab. Garage slab is not a part of the structural slab in this structure, and the cracks does not indicate a major structural concern. Replace the garage's concrete slab with a new slab, metal reinforcement, and moisture barrier.
|  Photo 14-1 |  Photo 14-2 | 
 Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.
Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.
|  Photo 15-1 |  Photo 15-2 | 
 Other concerns.
Other concerns.
|  Photo 16-1 Missing roof sheathing board |  Photo 16-2 Moisture stains on sill plate | 
 Garage vehicle door is in a good condition displaying no signs of stress and or excessive wear. This garage door has all needed components such as sides and bottom weather stripping, and functioned correctly at the time of inspection.
Garage vehicle door is in a good condition displaying no signs of stress and or excessive wear. This garage door has all needed components such as sides and bottom weather stripping, and functioned correctly at the time of inspection.
|  Photo 17-1 |  Photo 17-2 | 
 This garage is in a good overall condition with all components functioning correctly, except as noted in this report.
This garage is in a good overall condition with all components functioning correctly, except as noted in this report.
|  Photo 18-1 |  Photo 18-2 | 
 There is no automatic garage door opener installed in this garage.
There is no automatic garage door opener installed in this garage.
|  Photo 19-1 | 


 Evidence of "light to moderate" rodent infestation was found in one or more areas. The Center for Disease Control (CDC) defines this as less than 20 feces per square foot. Rodent infestation may be a safety hazard due to the risk of contracting  Hantavirus Pulmonary Syndrome (HPS). HPS is a rare (only 20-50 cases per year in the United states) but deadly (40% mortality rate) disease transmitted by infected rodents through urine, droppings, or saliva. Humans can contract the disease when they breathe in aerosolized virus. For example, from sweeping up rodent droppings.
Evidence of "light to moderate" rodent infestation was found in one or more areas. The Center for Disease Control (CDC) defines this as less than 20 feces per square foot. Rodent infestation may be a safety hazard due to the risk of contracting  Hantavirus Pulmonary Syndrome (HPS). HPS is a rare (only 20-50 cases per year in the United states) but deadly (40% mortality rate) disease transmitted by infected rodents through urine, droppings, or saliva. Humans can contract the disease when they breathe in aerosolized virus. For example, from sweeping up rodent droppings.|  Photo 20-1 |  Photo 20-2 | 

 Ventilation is substandard in the attic. Inadequate attic ventilation may result in high attic and roof surface temperatures, reduce the life of the roof covering materials and increase cooling costs. High levels of moisture are also likely, and can be a conducive condition for wood destroying insects and organisms. Standard building practices require one square foot of vent area for 150 to 200 square feet of attic space. Vents should be evenly distributed between soffits, ridges and at corners to promote air circulation. A qualified contractor should evaluate and install vents as per standard building practices.
Ventilation is substandard in the attic. Inadequate attic ventilation may result in high attic and roof surface temperatures, reduce the life of the roof covering materials and increase cooling costs. High levels of moisture are also likely, and can be a conducive condition for wood destroying insects and organisms. Standard building practices require one square foot of vent area for 150 to 200 square feet of attic space. Vents should be evenly distributed between soffits, ridges and at corners to promote air circulation. A qualified contractor should evaluate and install vents as per standard building practices.
|  Photo 21-1 |  Photo 21-2 | 
 The ceiling insulation's R rating is significantly less than what's recommended for this area. Recommend having a qualified contractor install additional insulation as per standard building practices for better energy efficiency.
The ceiling insulation's R rating is significantly less than what's recommended for this area. Recommend having a qualified contractor install additional insulation as per standard building practices for better energy efficiency.
|  Photo 22-1 |  Photo 22-2 | 
|  Photo 22-3 Hot spots indicate low attic insulation |  Photo 22-4 | 
 No insulation is installed over the attic access hatch. Recommend installing insulation above hatch for better energy efficiency.
No insulation is installed over the attic access hatch. Recommend installing insulation above hatch for better energy efficiency.
|  Photo 23-1 | 
 Attic is in a good overall condition that displays adequate ventilation, proper insulation and adequate protection of all components routed through. It also displays a structural condition that is proper, secure and safe. There are no signs of excessive movement, lack of support or improper modifications to the structural components of this building.
Attic is in a good overall condition that displays adequate ventilation, proper insulation and adequate protection of all components routed through. It also displays a structural condition that is proper, secure and safe. There are no signs of excessive movement, lack of support or improper modifications to the structural components of this building.
|  Photo 24-1 |  Photo 24-2 | 
|  Photo 24-3 |  Photo 24-4 | 
 The attic area was viewed from the access hatch. Areas beyond the inspectors visual range in the attic space are not covered in this report. Intent of this inspection is to get a sense of the house's structural make-up and stability. This inspection is not a complete attic inspection and in the case that a complete visual inspection is necessary, your inspector will inform you.
The attic area was viewed from the access hatch. Areas beyond the inspectors visual range in the attic space are not covered in this report. Intent of this inspection is to get a sense of the house's structural make-up and stability. This inspection is not a complete attic inspection and in the case that a complete visual inspection is necessary, your inspector will inform you.


 There are no arc fault circuit interrupter (AFCI) breakers in the main service panel serving the bedrooms. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs and/or replace circuit breakers as necessary.
There are no arc fault circuit interrupter (AFCI) breakers in the main service panel serving the bedrooms. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs and/or replace circuit breakers as necessary.
|  Photo 26-1 | 

 The electrical panel box in this structure is in serviceable condition, but the panel is rated substantially less than 200 amps, and may be inadequate for the client(s) needs. Evaluate as needed and  upgrade to a 200 amp service if possible.
The electrical panel box in this structure is in serviceable condition, but the panel is rated substantially less than 200 amps, and may be inadequate for the client(s) needs. Evaluate as needed and  upgrade to a 200 amp service if possible.
|  Photo 27-1 |  Photo 27-2 | 
|  Photo 27-3 |  Photo 27-4 | 
|  Photo 27-5 |  Photo 27-6 | 
 Other concerns.
Other concerns.
|  Photo 28-1 This box's cover could not be opened to visually inspect this unit | 

 No drain line is installed for the temperature-pressure relief valve. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. A qualified plumber should install a drain line as per standard building practices. For example, extending to 6 inches from the floor, or routed so as to drain outside.
No drain line is installed for the temperature-pressure relief valve. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. A qualified plumber should install a drain line as per standard building practices. For example, extending to 6 inches from the floor, or routed so as to drain outside.
|  Photo 29-1 | 
 Dissimilar metal connector should be replaced with similar connections to avoid corrosion.
Dissimilar metal connector should be replaced with similar connections to avoid corrosion.
|  Photo 30-1 | 
 Water heater is in a good physical condition, displaying all needed elements such as appropriate sceismic straps, and drain lines for it's pressure relieve valve, but it did not produce hot water when inspected.
Water heater is in a good physical condition, displaying all needed elements such as appropriate sceismic straps, and drain lines for it's pressure relieve valve, but it did not produce hot water when inspected.
|  Photo 31-1 |  Photo 31-2 | 
|  Photo 31-3 |  Photo 31-4 Gas was shut off to the unit when inspected | 
|  Photo 31-5 | 
 Other concerns.
Other concerns.
|  Photo 32-1 |  Photo 32-2 | 
|  Photo 32-3 Loose insulation could be a fire hazard | 
 No filter is visible for the heating/cooling system. As a result, unfiltered air will flow through the system, and the heating/cooling equipment life and the indoor air quality may be reduced. Correctly sized filter(s) should be installed. If necessary, guides or retaining devices should be installed or repaired so filter(s) are securely anchored and gaps around edges are minimized.
No filter is visible for the heating/cooling system. As a result, unfiltered air will flow through the system, and the heating/cooling equipment life and the indoor air quality may be reduced. Correctly sized filter(s) should be installed. If necessary, guides or retaining devices should be installed or repaired so filter(s) are securely anchored and gaps around edges are minimized.
|  Photo 33-1 | 
 The outside condensing unit is not securely connected to a base or to the concrete decking beneath. Damage may occur if the unit shifts due to vibration. Evaluate and repair as necessary so the unit is secure to its base.
The outside condensing unit is not securely connected to a base or to the concrete decking beneath. Damage may occur if the unit shifts due to vibration. Evaluate and repair as necessary so the unit is secure to its base.
|  Photo 34-1 | 

 Furnace is in serviceable condition, providing heat to the living areas when it's controls were operated, but the unit did not reach 100 f in heating mode. Service as needed.
Furnace is in serviceable condition, providing heat to the living areas when it's controls were operated, but the unit did not reach 100 f in heating mode. Service as needed.
|  Photo 35-1 | 
 Condenser unit is equipped with an adequate electrical shut off switch.
Condenser unit is equipped with an adequate electrical shut off switch.
|  Photo 36-1 | 
 Condensing unit is in serviceable condition, providing needed thermal exchange to supply the living areas with cool air, when it's controls were operated.
Condensing unit is in serviceable condition, providing needed thermal exchange to supply the living areas with cool air, when it's controls were operated.
|  Photo 37-1 | 
|  Photo 38-1 Heater did not reach 100 f in heating mode. Evaluate and service as required |  Photo 38-2 A/C reached a minimum of 15 f below ambient temperature in cooling mode | 
|  Photo 38-3 90 f ambient temperature | 

 The water supply pressure is greater than 80 psi. Pressures above 80 psi may void warranties for some appliances such as water heaters or washing machines. Flexible supply lines to washing machines are more likely to burst with higher pressures. Typically the pressure cannot be regulated at the water meter. Recommend having a qualified plumber evaluate and make modifications to reduce the pressure below 80 psi. Installing a pressure reducing valve on the main service pipe is a common solution to this problem. If one exists, then it should be adjusted for lower pressures.
The water supply pressure is greater than 80 psi. Pressures above 80 psi may void warranties for some appliances such as water heaters or washing machines. Flexible supply lines to washing machines are more likely to burst with higher pressures. Typically the pressure cannot be regulated at the water meter. Recommend having a qualified plumber evaluate and make modifications to reduce the pressure below 80 psi. Installing a pressure reducing valve on the main service pipe is a common solution to this problem. If one exists, then it should be adjusted for lower pressures.
|  Photo 39-1 | 

 There is no water pressure regulator installed on the main water line entering this structure. City water pressure fluctuation can cause damage to the structure's plumbing lines. It is recommended to install a pressure regulator to maintain a constant safe pressure inside the structure's plumbing lines.
There is no water pressure regulator installed on the main water line entering this structure. City water pressure fluctuation can cause damage to the structure's plumbing lines. It is recommended to install a pressure regulator to maintain a constant safe pressure inside the structure's plumbing lines.
|  Photo 40-1 | 

 Water hammering was noticed when the faucet by the garage was operated. Evaluate and repair as necessary such as installing a water hammer arrestor.
Water hammering was noticed when the faucet by the garage was operated. Evaluate and repair as necessary such as installing a water hammer arrestor.
|  Photo 41-1 | 
 Other concerns.
Other concerns.
|  Photo 42-1 Laundry area is using a GFI outlet. Remove and exchange with a regular outlet as needed to avoid accidental tripping | 
 The main shut off valve is buried in the front planter. Remove dirt from around this valve for accessibility and ease of operation.
The main shut off valve is buried in the front planter. Remove dirt from around this valve for accessibility and ease of operation.
|  Photo 43-1 | 
 This laundry area is in an overall good condition with no signs of deferred maintenance, and its components in a functioning state, except as noted in this report.
This laundry area is in an overall good condition with no signs of deferred maintenance, and its components in a functioning state, except as noted in this report.
|  Photo 44-1 | 
 This Laundry room supports a gas only dryer. The client should be advised that an electric dryer unit will not work in this laundry room layout without an electrical modification.
This Laundry room supports a gas only dryer. The client should be advised that an electric dryer unit will not work in this laundry room layout without an electrical modification.
|  Photo 45-1 | 

 No insulation is installed under the floor in the crawl space. Recommend that a qualified contractor install R19 or better (6" thick fiberglass batt) insulation under the floor for better energy efficiency.
No insulation is installed under the floor in the crawl space. Recommend that a qualified contractor install R19 or better (6" thick fiberglass batt) insulation under the floor for better energy efficiency.
|  Photo 46-1 | 

 Wooden support posts are not securely fastened to beams above. This is a safety hazard since they can separate during a seismic event. A qualified contractor should evaluate and make repairs as necessary, such as installing metal ties, bracing with lumber and/or plywood gussets as per standard building practices.
Wooden support posts are not securely fastened to beams above. This is a safety hazard since they can separate during a seismic event. A qualified contractor should evaluate and make repairs as necessary, such as installing metal ties, bracing with lumber and/or plywood gussets as per standard building practices.
|  Photo 47-1 | 
 No vapor barrier is installed. This is a conducive condition for wood destroying insects and organisms due to the likelihood of water evaporating into the structure from the soil. A qualified contractor should install a vapor barrier. Standard building practices require the following:
No vapor barrier is installed. This is a conducive condition for wood destroying insects and organisms due to the likelihood of water evaporating into the structure from the soil. A qualified contractor should install a vapor barrier. Standard building practices require the following:|  Photo 48-1 | 
 Clean and remove abandoned wiring from the crawlspace.
Clean and remove abandoned wiring from the crawlspace.
|  Photo 49-1 |  Photo 49-2 | 
 Crawlspace is in a good overal condition with all needed components in place. All ventilation ports are covered with metal mesh, with an intact access door, and a clean condition with no evidence of infestation. Crawl space conditions is good with exception of items noted in this report.
Crawlspace is in a good overal condition with all needed components in place. All ventilation ports are covered with metal mesh, with an intact access door, and a clean condition with no evidence of infestation. Crawl space conditions is good with exception of items noted in this report.
|  Photo 50-1 |  Photo 50-2 | 
|  Photo 51-1 | 


 One or more open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.
One or more open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary. |  Photo 52-1 |  Photo 52-2 | 


 One or more electric receptacles and/or the boxes they are installed in are loose and/or not securely anchored. Wire conductors may be damaged due to repeated movement and/or tension on wires, or insulation may be damaged. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair as necessary.
One or more electric receptacles and/or the boxes they are installed in are loose and/or not securely anchored. Wire conductors may be damaged due to repeated movement and/or tension on wires, or insulation may be damaged. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair as necessary.
|  Photo 53-1 | 


 One or more ground fault circuit interrupter (GFCI) electric receptacles did not trip when tested with the inspector's test instrument. These devices should trip when tested with a test instrument in addition to tripping via the test buttons on the receptacles. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary.
One or more ground fault circuit interrupter (GFCI) electric receptacles did not trip when tested with the inspector's test instrument. These devices should trip when tested with a test instrument in addition to tripping via the test buttons on the receptacles. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary.
|  Photo 54-1 | 

 The range can tip forward, and no anti-tip bracket appears to be installed. This is a safety hazard since the range may tip forward when weight is applied to the open door, such as when a small child climbs on it, or if heavy objects are dropped on it. Anti-tip brackets have been sold with all free standing ranges since 1985. An anti-tip bracket should be installed to eliminate this safety hazard. For more information, visit:
The range can tip forward, and no anti-tip bracket appears to be installed. This is a safety hazard since the range may tip forward when weight is applied to the open door, such as when a small child climbs on it, or if heavy objects are dropped on it. Anti-tip brackets have been sold with all free standing ranges since 1985. An anti-tip bracket should be installed to eliminate this safety hazard. For more information, visit:|  Photo 55-1 | 
 Hood exhaust ducts are connected without use of a mechanical fasteners such as metal screws. Screw exhaust duct pieces together with metal screws or other mechanical fasteners and seal with duct tape to prevent movement and disconnection.
Hood exhaust ducts are connected without use of a mechanical fasteners such as metal screws. Screw exhaust duct pieces together with metal screws or other mechanical fasteners and seal with duct tape to prevent movement and disconnection.
|  Photo 56-1 | 
 Handles and/or drawer pulls are not installed on one or more cabinets, where the drawers and/or doors are difficult to open without them. Recommend installing handles and/or pulls as necessary.
Handles and/or drawer pulls are not installed on one or more cabinets, where the drawers and/or doors are difficult to open without them. Recommend installing handles and/or pulls as necessary.
|  Photo 57-1 | 

 Hot water was shut off to the kitchen faucet. Evaluate and repair as necessary.
Hot water was shut off to the kitchen faucet. Evaluate and repair as necessary.
|  Photo 58-1 | 
 Gas connection to the oven is shut off. The oven did not get evaluated in this inspection.
Gas connection to the oven is shut off. The oven did not get evaluated in this inspection.
|  Photo 59-1 |  Photo 59-2 | 
 Other concerns.
Other concerns.
|  Photo 60-1 Ice / water dispenser did not get evaluated | 
 This kitchen is in an excellent condition, displaying all equipments and components at their best state. There are no differed maintenance issues or other concerns in this kitchen, except as noted in this report.
This kitchen is in an excellent condition, displaying all equipments and components at their best state. There are no differed maintenance issues or other concerns in this kitchen, except as noted in this report.
|  Photo 61-1 | 


 One or more open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.
One or more open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary. |  Photo 62-1 | 

 One or more toilets are loose or is not firmly attached to the ground. Remove the toilet(s) for further evaluation and repairs if necessary. A new wax ring should be installed and toilet(s) should be securely anchored and fully adhered to the floor to prevent movement and leaking.
One or more toilets are loose or is not firmly attached to the ground. Remove the toilet(s) for further evaluation and repairs if necessary. A new wax ring should be installed and toilet(s) should be securely anchored and fully adhered to the floor to prevent movement and leaking.
|  Photo 63-1 | 
 One or more sink drains use flexible drain pipe. This type of drain pipe is more likely to clog than smooth wall pipe. Recommend having a qualified plumber replace this pipe with standard plumbing components (smooth wall pipe) to prevent clogged drains.
One or more sink drains use flexible drain pipe. This type of drain pipe is more likely to clog than smooth wall pipe. Recommend having a qualified plumber replace this pipe with standard plumbing components (smooth wall pipe) to prevent clogged drains.
|  Photo 64-1 | 
 One or more sink stopper mechanisms are missing, or need adjustment or repair. Stopper mechanisms should be installed where missing and/or repairs should be made so sink stoppers open and close easily.
One or more sink stopper mechanisms are missing, or need adjustment or repair. Stopper mechanisms should be installed where missing and/or repairs should be made so sink stoppers open and close easily.
|  Photo 65-1 | 
 Seal around all penetrations into the wall system.
Seal around all penetrations into the wall system.
|  Photo 66-1 |  Photo 66-2 | 
 Bathrooms in this buildings are all in a good overall condition displaying proper plumbing connections, adequate ventilation, and necessary electrical components such as GFI outlets close to the sink. There are no signs of deferred maintenance, excessive moisture, or other related issues of concern, except as noted in this report.
Bathrooms in this buildings are all in a good overall condition displaying proper plumbing connections, adequate ventilation, and necessary electrical components such as GFI outlets close to the sink. There are no signs of deferred maintenance, excessive moisture, or other related issues of concern, except as noted in this report.
|  Photo 67-1 |  Photo 67-2 | 
|  Photo 68-1 |  Photo 68-2 | 


 One or more open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.
One or more open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary. |  Photo 69-1 |  Photo 69-2 | 
|  Photo 69-3 |  Photo 69-4 | 
|  Photo 69-5 |  Photo 69-6 | 


 Few electric receptacles and two-pronged receptacles rather than three-pronged, grounded receptacles are installed in one or more interior rooms. This can result in "octopus" wiring with extension cords. Two-prong receptacles are considered unsafe by today's standards, and limit the ability to use appliances that require a ground in these rooms. This is a safety hazard for both fire and shock. Examples of appliances that require grounded receptacles include:
Few electric receptacles and two-pronged receptacles rather than three-pronged, grounded receptacles are installed in one or more interior rooms. This can result in "octopus" wiring with extension cords. Two-prong receptacles are considered unsafe by today's standards, and limit the ability to use appliances that require a ground in these rooms. This is a safety hazard for both fire and shock. Examples of appliances that require grounded receptacles include:|  Photo 70-1 |  Photo 70-2 | 

 An insufficient number of smoke alarms are installed. Additional smoke alarms should be installed as necessary so a functioning one exists in each hallway leading to bedrooms, and in each bedroom. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html
An insufficient number of smoke alarms are installed. Additional smoke alarms should be installed as necessary so a functioning one exists in each hallway leading to bedrooms, and in each bedroom. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html
|  Photo 71-1 | 

 Carbon Monoxide detectors is required in all houses (1 – 4 units) if they have any of the following:
Carbon Monoxide detectors is required in all houses (1 – 4 units) if they have any of the following:
 There is one or more older style single Pane window(s) and or doors in this structure. These doors and windows are not as energy efficient or operate as smooth as the newer styles. Evaluate and replace as needed.
There is one or more older style single Pane window(s) and or doors in this structure. These doors and windows are not as energy efficient or operate as smooth as the newer styles. Evaluate and replace as needed.
|  Photo 73-1 |  Photo 73-2 | 

 Screen(s) in one or more windows are missing. The client(s) should ask the property owner(s) about this. Screens are often removed for window cleaning and they may be stored somewhere. If not, then recommend installing screens where missing.
Screen(s) in one or more windows are missing. The client(s) should ask the property owner(s) about this. Screens are often removed for window cleaning and they may be stored somewhere. If not, then recommend installing screens where missing.
|  Photo 74-1 | 
 One or more doors will not latch when closed. Repairs should be made such as aligning strike plates with latch bolts and/or replacing locksets to have doors latch properly when closed.
One or more doors will not latch when closed. Repairs should be made such as aligning strike plates with latch bolts and/or replacing locksets to have doors latch properly when closed.
|  Photo 75-1 | 
 Other concerns.
Other concerns.
|  Photo 76-1 Missing one pocket door pull |  Photo 76-2 | 
 Interior spaces in this building are in an overall good condition with no signs of deferred maintenance or other areas of concern, except as noted in this report.
Interior spaces in this building are in an overall good condition with no signs of deferred maintenance or other areas of concern, except as noted in this report.
|  Photo 77-1 |