Upper Front and Front Entry Roofs
9) Some slate roof tiles were cracked, broken and/or loose. Leaks may occur as a result. Recommend that a qualified roofer replace tiles or make repairs as necessary.
Electric
11) One or more modern, 3-prong electric receptacles were found with an open ground. Three-prong receptacles should have a hot, a neutral and a ground wire connected. Homeowners often install new 3-prong receptacles on older, 2-wire circuits that only have hot and neutral wires. This is a shock hazard when appliances that require a ground are used with these receptacles. Examples of such appliances include computers and related hardware, refrigerators, freezers, portable air conditioners, clothes washers, aquarium pumps, and electrically operated gardening tools. Where the electric system was installed prior to when grounded circuits were required (1960s), it is permissible to replace 3-prong receptacles with 2-prong receptacles to prevent appliances that require a ground from being plugged in to an ungrounded circuit. However, the client should be aware of this limitation when planning use for various rooms, such as an office. For newer electric systems, circuits should be repaired so grounded, 3-wire cables provide power to 3-prong receptacles. Recommend that a qualified electrician repair per standard building practices.
Location(s) affected: 3-prong outlets on 2nd floor - front and middle bedrooms
12) One or more electric receptacles had reverse-polarity wiring, where the hot and neutral wires were reversed. This is a shock hazard. Recommend that a qualified electrician repair as necessary.
Location(s) affected: 1st floor, living room, Left wall
13) Carbon monoxide alarms were not observed in the home. This is a potential safety hazard. Recommend installing approved carbon monoxide alarms on each level and in accordance with the manufacturer's recommendations.
14) For home buyers, batteries in all the smoke alarms should be replaced after taking occupancy. Batteries should be replaced annually in the future. Some batteries were missing from smoke detectors at the time of inspection.
15) One or more electric receptacles appeared to have no power. Recommend asking the property owner about this. Switches may need to be operated or GFCI/AFCI protection may need to be reset to make some receptacles energized. If necessary, recommend that a qualified electrician evaluate and repair.
Location(s) Affected: Living Room wall outlet adjacent to dining room