Exterior / Foundation
5) 

Cracks or deterioration were found in one or more sections of brick veneer. This may relate to water/pest damage at sub floor. A qualified contractor should evaluate and make repairs as necessary, such as repointing mortar to prevent water intrusion and further deterioration in the future.
6) 

Rot or water damage was found at one or more sections of floor sheathing, joists and/or beams. A qualified contractor should evaluate and repair as necessary. All rotten wood should be replaced.
Pest damage present at these areas.
Left and left front areas of sub structure
10-16-2018 New pictures with notes in comments below pictures.
7) 
No vapor barrier was installed in the crawl space. This is a conducive condition for wood destroying organisms due to the likelihood of water evaporating into the building from the soil. A qualified person should install a vapor barrier as per standard building practices.
10-16-2018 A vapor barrier was installed.
8) 
The crawl space access hatch was missing. A qualified person should repair, replace or install as necessary to prevent water and vermin intrusion.
9) 
Some crawl space vent screens were missing. Animals such as vermin or pets may enter the crawl space and nest, die and/or leave feces and urine. A qualified person should replace damaged or deteriorated screens where necessary using screen material such as "hardware cloth" with 1/4 inch minimum gaps.
10) 


Additional piers/footings should be installed at this beam for proper support and bearing.
10-16-2018 See item 6 for update.
Electric
11) 


Relatively few electric receptacles were installed in one or more areas. This can result in "octopus" wiring with extension cords, which is a fire hazard. A qualified electrician should evaluate and install additional receptacles as necessary and as per standard building practices.
No outlets at bathrooms.
10-16-2018 New GFCI outlets have been installed.
12) 


Two-pronged electric receptacles rather than three-pronged, grounded receptacles were installed in one or more areas. They are considered to be unsafe by today's standards and limit the ability to use appliances that require a ground in these rooms. Examples of appliances that require grounded receptacles include:
- Computer hardware
- Refrigerators
- Freezers
- Air conditioners
- Clothes washers
- Clothes dryers
- Dishwashers
- Kitchen food waste disposers
- Information technology equipment
- Sump pumps
- Electrical aquarium equipment
- Hand-held motor-operated tools
- Stationary and fixed motor-operated tools
- Light industrial motor-operated tools
- Hedge clippers
- Lawn mowers
This list is not exhaustive. A qualified electrician should evaluate and install grounded receptacles as per the client's needs and standard building practices.
10-16-2018 A grounded outlet has been installed at laundry location.
15) 

Batteries in all the smoke alarms should be replaced after taking occupancy, and annually in the future. "Chirping" noises emitted from smoke alarms typically indicate that batteries need replacing. For more information, visit:
http://www.cpsc.gov/cpscpub/pubs/5077.html
16) 

The legend for overcurrent protection devices (breakers or fuses) in panel #A and B was missing. Recommend installing, updating or correcting the legend as necessary so it's accurate. Evaluation by a qualified electrician may be necessary.
10-16-2018 A legend was installed at the sub panel.
Water Heater
20) 

No drain line was installed for the temperature-pressure relief valve. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. A qualified plumber should install a drain line as per standard building practices.
10-16-2018 A drain extension was installed at this valve.
21) 

The outer flame shield for the water heater combustion chamber was missing. This is a potential fire hazard. A qualified person should repair or replace as necessary.
22) 
A water heater was installed over finished living spaces and had no catch drain installed. Recommend having a qualified contractor install a drain to prevent water damage to finished interior spaces below if/when the water heater develops a leak or is drained.
10-16-2018 A drain was installed at this pan.
23) 

The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be at this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future.