Summary

Client(s):  Mr. & Mrs. Home Buyer
Property address:  789 New Lane
Nice City, California
Inspection date:  Thursday, February 20, 2014

This report published on Tuesday, April 29, 2014 9:41:04 AM PDT

This report is the exclusive property of Coastal Inspections and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a risk of injury or death
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeFuture improvementsRecommended correction for future improvements
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeServiceableItem or component is in serviceable condition
Concern typeCommentFor your information


General information
1 - This structure is in an overall good condition with no deferred maintenance issues or concerns, and is in a good overall structural condition, with no signs of settlement or stress cracks visible, except as noted in this report.
Exterior
2 - One or more flights of stairs with more than two risers have no handrail installed. This is a safety hazard. Install graspable handrails that a hand can completely encircle for support per standard building practices.
3 - Cracks, deterioration and/or damage were found in areas of the stucco siding. Evaluate and make repairs as necessary.
4 - One or more ground fault circuit interrupter (GFCI) electric receptacles did not trip when tested. This is a safety hazard due to the risk of shock. Evaluate and repair as necessary.
5 - Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.
9 - This structure displays excellent conditions throughout its exterior portion with no differed maintenance items and no major concerns, except as noted in this report.
Roof
11 - Roof seems to be in serviceable condition viewed from the ground, and /or the windows. Attic space showed dry conditions with no signs of previous water damage visible.
Garage
12 - There are hairline cracks in garage's concrete slab. These cracks are not structural and are of a cosmetic nature. Recommend sealing all cracks to prevent entry of moisture and to prevent further damage.
15 - The door separating the garage and the living spaces is in a good working condition. This is a fire rated partition that is meant to stop and slow the spread of fire from the garage to the living areas. This door has all the needed elements such as a self closing device, fully gasketed construction and a solid core material.
16 - This garage is in a good overall condition with all components functioning correctly, except as noted in this report.
Attic
17 - Recessed "can" lights are installed in the ceiling below the attic. The inspector was unable to find a label or markings that indicated if these lights are designed to be in contact with insulation, and one or more lights are in contact with insulation. This is a possible fire hazard. Further evaluation should be performed to determine if these lights are rated for contact with insulation. If they aren't, or if their rating can't be determined, insulation should be moved, and wells or barriers should be installed or repaired as necessary to keep the insulation away from these lights.
18 - Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.
19 - No insulation is installed over the attic access hatches. Recommend installing insulation above hatch for better energy efficiency.
20 - Attic is in a good overall condition that displays adequate ventilation, proper insulation and adequate protection of all components routed through. It also displays a structural condition that is proper, secure and safe. There are no signs of excessive movement, lack of support or improper modifications to the structural components of this building.
Electric service
23 - Labels for the breakers in the sub-service panel is missing, unreadable or incomplete. Recommend installing, updating or correcting the labels as necessary so it's accurate. Evaluation by a qualified electrician may be necessary.
24 - The electrical service panel is in serviceable condition having all needed components, and is adequate for the size of the structure.
Water heater
25 - There are non compatible metal connection used in this water heaters plumbing connections. Replace with similar metal connections to avoid corrosion and damage to the piping system.
27 - Water heaters are in serviceable condition, providing adequate hot water and displaying all essential components such as appropriate seismic straps, and drain lines for their pressure relief valves.
Heating and cooling
29 - The outside condensing unit is not securely connected to a base or to the concrete decking beneath. Damage may occur if the unit shifts due to vibration. Evaluate and repair as necessary so the unit is secure to its base.
30 - Air handler filter(s) are dirty and should be replaced now. They should be checked monthly in the future and replaced as necessary.
32 - Condenser units are equipped with adequate electrical shut off switches.
33 - Temperatures
34 - Furnaces are all in serviceable condition, providing adequate heat to the living areas when their controls were operated.
35 - Condensing units are in serviceable condition, providing needed thermal exchange to supply the living areas with cool air, when their controls were operated.
Plumbing and laundry
36 - The washing machine is installed over finished flooring inside living space and has no catch pan or drain installed. These are not commonly installed, but they are recommended to prevent water damage to finished interior spaces below if or when the washing machine leaks, overflows or is drained. Recommend having a qualified contractor install both a catch pan and drain.
37 - Adequate water pressure is supplied to this structure @ 45 Psi
38 - This laundry area is in an overall good condition with no signs of deferred maintenance, and its components in a functioning state, except as noted in this report.
39 - There is an adequate water pressure regulator installed on the main water line entering this structure.
Fireplaces and chimneys
44 - Add a damper stop to prevent full closure of the fireplace damper. This will prevent build-up and allow ventilation of natural gases in case of any leaks in the gas supply system inside the fireplace.
46 - Fireplace(s) in this structure are in serviceable condition with all parts functioning properly, except as noted in this report. There are no signs of deferred maintenance present.
Kitchen
48 - Water leaked from the dishwasher's air gap device when it was operated. Debris may be clogging the drain line or the garbage disposal drain plug has not been punched yet (on new units). A qualified plumber or appliance repair technician should evaluate and repair as necessary.
49 - The microwave oven appears to be inoperable. The client(s) should ask the property owner(s) about this, and if necessary, the microwave oven should be replaced, or a qualified appliance technician should evaluate and repair.
50 - The kitchen sink drain has an active leak. For example, at pipe fittings and/or junctions between pipe and sink. A qualified plumber should evaluate and repair as necessary.
52 - This kitchen is in an overall good condition, with no signs of deferred maintenance issues or major concerns, except as noted in this report.
Bathrooms
53 - There was no hot water connection in one bathroom faucet when inspected. Valves might be shut off preventing water flow to this faucet. Turning on water valves is not a part of this inspection since leaks might get started as a result. Turn on valves as needed for a full evaluation of the faucet.
54 - One or more sink stopper mechanisms are missing, or need adjustment or repair. Stopper mechanisms should be installed where missing and/or repairs should be made so sink stoppers open and close easily.
55 - One or more bathtub drains are clogged or drain slowly. Drain(s) should be cleared as necessary.
57 - Bathrooms in this buildings are all in a good overall condition displaying proper plumbing connections, adequate ventilation, and necessary electrical components such as GFCI outlets close to the sink. There are no signs of deferred maintenance, excessive moisture, or other related issues of concern, except as noted in this report.
Interior rooms
58 - One or more smoke alarms are damaged, deteriorated and/or missing from their mounting brackets. Damaged and/or missing smoke alarms should be replaced as necessary so a functioning one exists in each hallway leading to bedrooms, and in each bedroom. For more information, visit:
http://www.cpsc.gov/cpscpub/pubs/5077.html
59 - A carbon monoxide detector is required on every floor of your home, including the basement. A detector should be located within 10 feet of each bedroom door and there should be one near or over any attached garage. Each detector should be replaced every five to six years.

Proper placement of a carbon monoxide (CO) detector is important. If you are installing only one carbon monoxide detector, the Consumer Product Safety Commission (CPSC) recommends it be located near the sleeping area, where it can wake you if you are asleep. Additional detectors on every level and in every bedroom of a home provides extra protection against carbon monoxide poisoning.

Homeowners should remember not to install carbon monoxide detectors directly above or beside fuel-burning appliances, as appliances may emit a small amount of carbon monoxide upon start-up. A detector should not be placed within fifteen feet of heating or cooking appliances or in or near very humid areas such as bathrooms.
60 - Batteries in all the smoke alarms should be replaced after taking occupancy, and annually in the future. "Chirping" noises emitted from smoke alarms typically indicate that batteries need replacing. For more information, visit:
http://www.cpsc.gov/cpscpub/pubs/5077.html
61 - Lock mechanisms on one or more windows does not pull the window panel close enough for the lock to engage. Repairs should be made so that windows lock and unlock easily.
62 - One or more doors will not latch when closed. Repairs should be made such as aligning strike plates with latch bolts and/or replacing locksets to have doors latch properly when closed.
63 - Carpeting in one or more rooms is damaged and/or significantly deteriorated. Recommend replacing carpeting where necessary.
64 - Carpeting in one or more rooms is soiled and/or stained. Recommend having carpeting professionally cleaned as necessary.