This report published on Saturday, April 13, 2019 7:48:35 AM EDT
Welcome and thank you for choosing CRM Home Inspections, LLC. This report is designed to be as thorough as possible, but also clear and concise.
This report identifies the defects that the inspector observed that were deemed material to the home inspection, also this report may offer comments as a courtesy to the client regarding some of the maintenance needs of the home and of some average life expectancies of certain components. Please pay attention to important information and warnings in this report. They can help prevent failure of equipment or damage to the home, and may contain safety concerns regarding this home and property.
How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
Safety
Poses a safety hazard
Repair/Replace
Recommend repairing or replacing
Repair/Maintain
Recommend repair and/or maintenance
Maintain
Recommend ongoing maintenance
Evaluate
Recommend evaluation by a specialist
Monitor
Recommend monitoring in the future
Comment
For your information
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Sunny
Temperature during inspection: Warm
Inspection fee: $280
Payment method: Check
Type of building: Single family, Detached garage
Buildings inspected: One house, One detached garage
Age of main building: 99 yrs
Source for main building age: Municipal records or property listing
Front of building faces: Southwest
Main entrance faces: Southwest
Occupied: No
1) Recommendation: After moving into the house, I strongly recommend having the locks changed. Over the years, previous owners may have distributed the keys to family and friends. A new set of locks would insure privacy and security. If the house has remote garage door openers, I would recommend changing the code access also.
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Minor slope
Condition of driveway: Appeared satisfactory
Driveway material: Asphalt
Condition of sidewalks and/or patios: Appeared satisfactory
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared satisfactory
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
Condition of decks, porches and/or balconies: Appeared satisfactory, Required repairs, replacement and/or evaluation (see comments below)
Condition of stairs, handrails and guardrails: Appeared satisfactory
Exterior stair material: Wood, Masonry
2) Fungal rot was found in decking boards and joists at the back deck. Recommend that a qualified contractor evaluate and repair as necessary. All rotten wood should be replaced.
Photo 2-1 Photo 2-2
Photo 2-3 Photo 2-4
Photo 2-5
3) There was a lot of debris mounded up behind the shed. This should be removed as it can attract animals.
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared satisfactory
Apparent wall structure: Wood frame, Brick
Wall covering: Cement fiber, Cement
Condition of foundation and footings: Appeared satisfactory
Apparent foundation type: Unfinished basement
Foundation/stem wall material: Concrete block, Stone
4) Some sections of vinyl soffit were missing. Recommend that a qualified person install soffit panels where missing.
Photo 4-1
5) One or more holes or gaps were found at the fascia board (north east corner). Vermin, insects or water may enter the structure. Recommend that a qualified person repair as necessary.
Photo 5-1
6) Shrubs were in contact with the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo 6-1
7) A tree was close to the building at the north east corner of the house. Damage to the building can occur, especially during high winds. Recommend trimming or removing the tree.
Photo 7-1
8) The stain/paint finish in some areas was failing (e.g. peeling, faded, worn, thinning). Wood trim with a failing finish can be damaged by moisture. Recommend that a qualified person prep (e.g. clean, scrape, sand, prime, caulk) and restain/paint the the wood trim as needed.
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.
Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Exterior door material: Wood
Condition of floor substructure above: Appeared satisfactory
Pier or support post material: Wood, Steel
Beam material: Solid wood
Floor structure above: Solid wood joists
Condition of insulation underneath floor above: Not applicable, none installed
9) The basement stairs (bottom section) were missing a handrail. This is a potential fall hazard. Handrails should be installed at stairs with four or more risers or where stairs are greater than 30 inches high. Recommend that a qualified person install a handrail where missing.
Photo 9-1
10) A guardrail was missing at the basement stairs landing. This poses a fall hazard. Guardrails should be installed where walking surfaces are more than 30 inches above the surrounding grade or surfaces below. Recommend that a qualified person install guardrails where missing and per standard building practices.
Photo 10-1
11) The rim joist was not insulated (wood joist on top of foundation wall). This is a major area of heat loss. Recommend a qualified person install insulation around the entire rim joist for better heat retention. Fiberglass insulation or spray foam insulation should be used for best results.
Photo 11-1 Photo 11-2
12) Evidence of prior water intrusion was found in one or more sections of the basement. For example, water stains at walls. This is common with a stone foundation. The basement should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, then recommend that a qualified contractor who specializes in drainage issues evaluate and repair as necessary. Typical repairs for preventing water from accumulating in basements include:
Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
Improving perimeter grading
Repairing, installing or improving underground footing and/or curtain drains
Photo 12-1 Photo 12-2
Photo 12-3 Photo 12-4
Photo 12-5 Photo 12-6 Paneling should be removed.
Photo 12-7 Paneling should be removed. Photo 12-8 Paneling should be removed.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Traversed
Condition of roof surface material: Appeared satisfactory
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Hipped
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared satisfactory
Condition of gutters, downspouts and extensions: Appeared satisfactory
13) Gutters were missing at the dormers (front and back). Rainwater can come in contact with the building exterior as a result. Recommend that a qualified person install gutters as necessary.
Photo 13-1 Photo 13-2
14) One downspout was missing an extension. Water can accumulate around the building foundation and inside the basement as a result. Recommend that a qualified person install a downspout extension so rainwater drains away from the structure. Ideally the extensions should be a minimum of 5ft in length and point away from the foundation in such a way that water cannot accumulate at the foundation.
Photo 14-1 Photo 14-2
15) Moss was growing on the roof in some areas. As a result, shingles can lift or be damaged. Leaks can result and/or the roof surface can fail prematurely. Efforts should be made to kill the moss during its growing season (wet months). Typically, zinc or phosphate-based chemicals are used for this and must be applied periodically. For information on various moss treatment products and their pros and cons, visit: https://www.reporthost.com/?MOSS
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Traversed
Condition of roof structure: Appeared satisfactory
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared satisfactory
Ceiling insulation material: Fiberglass roll or batt
Condition of roof ventilation: Appeared satisfactory
Roof ventilation type: Gable end vents, Enclosed soffit vents
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared satisfactory
Primary service type: Overhead
Number of service conductors: 2
Service voltage (volts): 120-240
Estimated service amperage: 150
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 150
System ground: Ground rod(s) in soil
Condition of main service panel: Appeared satisfactory
Location of main service panel #A: Basement
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Appeared satisfactory
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: Yes
Carbon monoxide alarms installed: Yes
16) One or more electric receptacles and/or the boxes in which they were installed were loose and/or not securely anchored. Wire conductors can be damaged due to repeated movement and/or tension on wires, or insulation can be damaged. This is a shock and fire hazard. Recommend that a qualified electrician repair as necessary.
17) One or more electric receptacles at the kitchen and full bath had no visible ground fault circuit interrupter (GFCI) protection. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices.
Photo 17-1 Photo 17-2
Photo 17-3 Photo 17-4
18) Smoke and carbon monoxide alarms were missing on one or more levels and in each bedroom. This is a potential safety hazard. Some states and/or municipalities require smoke and CO alarms to be installed in the vicinity of each sleeping area, in each bedroom (smoke), on each level and in accordance with the manufacturer's recommendations. Recommend installing additional smoke and carbon monoxide alarms per these standards. For more information, visit: http://www.reporthost.com/?COALRM and http://www.reporthost.com/?SMKALRM
19) The electrical outlet at the front porch had no power. Recommend asking the property owner about this. Switches may need to be operated or GFCI/AFCI protection may need to be reset to make some receptacles energized. If necessary, recommend that a qualified electrician repair as needed.
Photo 19-1
20) The covering on the main electrical service line was slightly deteriorated. Water can penetrate the line and enter the electric meter and/or electrical panel. This can cause electrical components to rust and corrode. Recommend wrapping the line with a water proof tape for better protection.
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared satisfactory
Water service: Public
Location of main water shut-off: Basement
Condition of supply lines: Appeared satisfactory
Supply pipe material: Copper
Condition of drain pipes: Appeared satisfactory
Drain pipe material: Plastic
Condition of waste lines: Appeared satisfactory
Waste pipe material: Cast iron
Vent pipe condition: Appeared satisfactory
Vent pipe material: Galvanized steel, Cast iron
Sump pump installed: No
Condition of fuel system: Appeared satisfactory
Location of main fuel shut-off valve: At gas meter
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared satisfactory
Type: Tank
Energy source: Natural gas
Estimated age: 8 yrs
Capacity (in gallons): 40
Location of water heater: Basement
Condition of burners: Appeared satisfactory
Condition of venting system: Appeared satisfactory
21) The water heater drain valve was leaking. This may indicate that the water heater will need to be replaced soon. Recommend that a qualified person repair or replace the water heater as needed.
Photo 21-1
22) The estimated useful life for most water heaters is 10-15 years. This water heater appeared to be near this age and may need replacing at any time. Recommend budgeting for a replacement in the near future.
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating/cooling components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Furnace
Last service date of primary heat source: New 2019
Condition of forced air heating/(cooling) system: Appeared satisfactory
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: New 2019
Location of forced air furnace: Basement
Forced air system capacity in BTUs or kilowatts: 80,000
Condition of furnace filters: Appeared satisfactory
Location for forced air filter(s): At base of air handler
Condition of forced air ducts and registers: Appeared satisfactory
Condition of burners: Appeared satisfactory
Type of combustion air supply: Vented door
Condition of venting system: Appeared satisfactory
Condition of controls: Appeared satisfactory
23) One or more heating ducts gaps present. This can result in reduced energy efficiency and increased moisture in surrounding spaces. Recommend that a qualified HVAC contractor make permanent repairs as necessary. For example, by securely supporting ducts and installing approved tape or mastic at seams. There is also a hole in the cold air return at the air handler. This may have been done for better air flow. Recommend a qualified HVAC contractor evaluate and make repairs as needed.
Photo 23-1 Photo 23-2
24) The gas fired forced air furnace is new so routine servicing is not needed at this point. However a qualified HVAC contractor should inspect, clean, and service this system, and make repairs if necessary annually in the future. For more information visit: https://www.reporthost.com/?ANFURINSP
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Appeared satisfactory
Wood-burning fireplace type: Masonry
Condition of chimneys and flues: Appeared satisfactory, Required repair, replacement and/or evaluation (see comments below)
Wood-burning chimney type: Masonry
25) No spark screen or rain cap was installed at one or more chimney flue terminations. Spark screens reduce the chance of embers exiting the flue and causing fires. They also prevent wildlife (e.g. birds, rodents, raccoons) from entering flues. Rain caps prevent water from entering flues, mixing with combustion deposits and creating caustic chemicals which can corrode flues. They also prevent damage to masonry from freeze-thaw cycles and prevent metal components (e.g. dampers, metal firebox liners) from rusting. Recommend that a qualified person install rain caps with spark screens per standard building practices where missing.
Photo 25-1 Photo 25-2
26) One or more solid fuel-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all solid fuel-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at: https://www.reporthost.com/?CSIA
27) The brick chimney was severely deteriorated. For example, loose or missing mortar, cracked, broken, loose or spalled bricks. Loose bricks can pose a safety hazard, and deteriorated masonry can allow water to infiltrate the chimney structure and cause further damage. Recommend that a qualified contractor repair as necessary.
Photo 27-1 Photo 27-2
28) One or more masonry chimney crowns were missing. Crowns are meant to keep water off of the chimney structure and prevent damage from freeze-thaw cycles. Recommend that a qualified contractor repair or replace crowns as necessary, and per standard building practices.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared satisfactory
Condition of cabinets: Appeared satisfactory
Condition of sinks and related plumbing: Appeared satisfactory
Condition of under-sink food disposal: N/A (none installed)
Condition of dishwasher: N/A (none installed)
Condition of range, cooktop or oven: N/A (none installed)
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath, second floor
Location #B: Half bath, first floor
Condition of counters: Appeared satisfactory
Condition of cabinets: Appeared satisfactory
Condition of flooring: Appeared satisfactory
Condition of sinks and related plumbing: Appeared satisfactory
Condition of toilets: Appeared satisfactory
Condition of bathtubs and related plumbing: Appeared satisfactory
Condition of shower(s) and related plumbing: Appeared satisfactory
Bathroom and laundry ventilation type: Windows, None visible
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: No
29) The hot water supply at the 2nd floor bathroom tub did not get hot when tested. This could be due to the fact that the water heater was turned to the vacation setting. Also the mixing valve handle turned less that a 1/4 turn which may be restricting the hot water flow. Recommend that a qualified person evaluate and repair as needed.
Photo 29-1
30) The 2nd floor bathroom didn't have an exhaust fan installed. Moisture can accumulate and result in mildew and peeling paint. Even if the bathroom has a window that opens, it may not provide adequate ventilation, especially during cold weather when windows are closed or when wind blows air into the bathroom. Recommend that a qualified person install an exhaust fan in the bathroom and have it vent to the exterior.
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared satisfactory
Exterior door material: Wood
Condition of interior doors: Appeared satisfactory
Condition of windows and skylights: Appeared satisfactory
Type(s) of windows: Wood
Condition of walls and ceilings: Appeared satisfactory
Wall type or covering: Drywall or plaster
Ceiling type or covering: Drywall or plaster
Condition of flooring: Appeared satisfactory
Condition of concrete slab floor(s): Appeared satisfactory
Flooring type or covering: Vinyl, linoleum or marmoleum, Laminate
Condition of stairs, handrails and guardrails: Appeared satisfactory
31) Handrails at the 2nd floor stairs were missing. This is a potential fall hazard. Handrails should be installed at stairs with four or more risers or where stairs are greater than 30 inches high. Recommend that a qualified contractor install handrails where missing and per standard building practices.
Photo 31-1
32) Condensation or staining was visible between multi-pane glass in one or more windows (2nd floor). This usually indicates that the seal between the panes of glass has failed or that the desiccant material that absorbs moisture is saturated. As a result, the view through the window may be obscured, the window's R-value will be reduced, and accumulated condensation may leak into the wall structure below. Recommend that a qualified contractor evaluate and repair windows as necessary. Usually, this means replacing the glass in window frames.
Photo 32-1 Photo 32-2
33) The window at the 2nd floor bathroom was stuck shut. Recommend that a qualified person repair windows as necessary so they open and close easily.
Photo 33-1
34) Glass in one or more windows (front living room windows) was cracked. Recommend that a qualified contractor replace glass where necessary.
Photo 34-1 Photo 34-2
Photo 34-3
35) One or more window/door screens were damaged or deteriorated. These windows/doors may not provide ventilation during months when insects are active. Recommend replacing window screens as necessary.