Property Inspection Report
WASHINGTON STATE HOME INSPECTORS LICENSE #251

Client(s):  Example
Property address:  18714 Woodburn Ct SE
Yelm Wa
Inspection date:  Thursday, June 10, 2021

This report published on Tuesday, June 29, 2021 1:52:29 PM PDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

PLEASE NOTE THE PICTURES PROVIDED ARE NOT EXCLUSIVE OF ALL FINDINGS AND ARE USED TO HELP VISUALIZE THE DEFECTS NOTED.

[sig]International Association of Certified Home Inspectors




Better Business Bureau

How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a risk of injury or death
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information
Concern typeConducive conditionsConditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Crawl Space
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows

View summary

Attachments

Olive Inspection agreement(1).pdf

General InformationTable of contents
Report number: 11240
Time started: 10:00
Time finished: 11:30
Present during inspection: Client, Realtor, Sellers children
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Rain
Temperature during inspection: Cool
Ground condition: Damp
Recent weather: Dry (no rain)
Overnight temperature: Cool
Inspection fee: $575
Payment method: Cash
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: 1996
Source for main building age: Client, Municipal records or property listing
Front of building faces: Northwest
Main entrance faces: Northwest
Occupied: Yes
1) Evidence of rodent infestation was found in the form of feces and/or damaged insulation in the crawl space. Consult with the property owner about this. A qualified person should make repairs to seal openings in the structure, set traps, and clean rodent waste as necessary. Recommend following guidelines in these Center for Disease Control articles:
http://www.cdc.gov/rodents/prevent_infestations/seal_up.html
http://www.cdc.gov/rodents/prevent_infestations/trap_up.html
http://www.cdc.gov/rodents/prevent_infestations/clean_up.html
2) Based on construction observed, modifications (garage conversion) to this property may have been made without the owner having attained permits or inspections from the municipality. Work may have been performed by someone other than a qualified contractor or person. Consult with the property owner about this, and if necessary research permits.

At worst case, if substantial work was performed without permits, this knowledge must be disclosed when the building is sold in the future. This can adversely affect future sales. Also, the local municipality could require costly alterations to bring the building into legal compliance or even require that the additions or modifications be removed.
Photo
Photo 2-1 
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level, Minor slope
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete, Paving stones
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Wood
Condition of stairs, handrails and guardrails: Required repairs, replacement and/or evaluation (see comments below)
Exterior stair material: Wood, Concrete
3) Fungal rot was found at one or more guardrail top rails. Recommend that a qualified person evaluate and repair as necessary. All rotten wood should be replaced.
Photo
Photo 3-1 
Photo
Photo 3-2 
4) Risers for stairs at one or more locations were higher than 7 3/4 inches and posed a fall or trip hazard. Risers should be 7 3/4 inches or shorter. At a minimum, be aware of this hazard, especially when guests who are not familiar with the stairs are present. Recommend that a qualified contractor repair per standard building practices.
Photo
Photo 4-1 
5) The risers for stairs at one or more locations varied in height and pose a fall or trip hazard. Risers within the same flight of stairs should vary by no more than 3/8 inch. At a minimum, be aware of this hazard, especially when guests who are not familiar with the stairs are present. Recommend that a qualified contractor repair per standard building practices.
Photo
Photo 5-1 
6) One or more sets of stairs were unstable and/or wobbly. A qualified contractor should repair as necessary. For example, by installing additional bracing or supports.
Photo
Photo 6-1 
7) Guardrails at one or more locations with drop-offs higher than 30 inches were loose and/or wobbly, and pose a fall hazard. Recommend that a qualified person repair guardrails as necessary.
Photo
Photo 7-1 
Photo
Photo 7-2 
8) A hot tub was installed. Hot tubs, related equipment and supply hookups are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Regular maintenance is required, and safety issues may exist. Recommend that a qualified specialist evaluate and, if needed, maintain or repair.
Photo
Photo 8-1 
9) Cracks, holes, settlement, heaving and/or deterioration were found in sidewalks and/or patios. Recommend that qualified contractor repair as necessary.
Photo
Photo 9-1 
10) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in the driveway, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.
11) All areas of the deck substructure were inaccessible due to limited space below. These areas couldn't be evaluated and are excluded from the inspection.
Photo
Photo 11-1 
Photo
Photo 11-2 
Exterior and FoundationTable of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Condition of wall exterior covering: Required repairs, replacement and/or evaluation (see comments below)
Apparent wall structure: Wood frame
Wall covering: Wood, Wood fiber
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Crawl space, Concrete garage slab
Foundation/stem wall material: Poured in place concrete
12) Some sections of siding and/or trim were missing. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo
Photo 12-1 
13) Conducive conditionsThis property was clad with composition wood-fiber siding. Various manufacturers (e.g. Louisiana Pacific, Weyerhaeuser and Masonite) have produced this type of siding, which is made from oriented strand board (OSB) or "hardboard." It is prone to deteriorate and/or fail prematurely due to moisture penetration, especially when the paint coating is substandard or has not been maintained. Failure is typically visible in the form of swelling, cracking, buckling, wafer pops, delamination and fungal growth.

Some areas of siding on this structure showed symptoms described above and need replacement and/or maintenance. Some manufacturers (e.g. Louisiana Pacific) recommend a repair process for this siding where affected areas are sealed with Permanizer Plus, a flexible primer made by Pittsburgh Paint, followed by two coats of 100% acrylic latex paint. This sealant must be applied to the bottom edges using a brush. The face of the siding can be sprayed. The Permanizer Plus sealer isn't required for edges that aren't swollen, cracked or deteriorated, but the acrylic latex should still be brushed on these edges.

Recommend that a qualified contractor evaluate and replace siding as necessary, and/or seal and repaint as necessary. Repairs should be made per the siding and/or sealant manufacturer's installation instructions, and per standard building practices.

For more information, visit:
http://www.google.com/search?q=permanizer+plus
http://www.google.com/search?q=failing+composition+wood+siding
Photo
Photo 13-1 
Photo
Photo 13-2 
Photo
Photo 13-3 
Photo
Photo 13-4 
Photo
Photo 13-5 
Photo
Photo 13-6 
Photo
Photo 13-7 
Photo
Photo 13-8 
Photo
Photo 13-9 
14) Conducive conditionsUntreated wood siding and/or trim was in contact with concrete or masonry at the exterior. Moisture collected between the two materials or wicking up into the wood is a conducive condition for wood-destroying organisms. Wood siding or trim should be installed with a minimum clearance of 1-2 inches between it and concrete or masonry below it at building exteriors. Monitor these areas for rot or infestation in the future and repair if needed. Recommend that a qualified person repair per standard building practices. For example, by trimming siding or trim as needed.
Photo
Photo 14-1 
15) Conducive conditionsOne or more windows or doors were installed with no "drip cap" or "Z" flashings installed above them. Better building practices call for such flashings, which greatly reduce the chance of leaks above windows and doors. Without this flashing, caulk and paint must be maintained or water can enter the wall structure and cause rot and possible structural damage. Depending on the exposure (e.g. roof overhang, height of exterior wall, direction of prevailing rain) this may or may not be an issue. The client should monitor these areas in the future and maintain caulk and paint as necessary. Consult with a qualified contractor about installing flashings where needed, and per standard building practices. Note that when trim or siding is removed to install flashing, damaged wood may be found and additional repairs may be needed.
16) Conducive conditionsVegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 16-1 
17) Conducive conditionsThe paint or stain finish in some areas was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture.Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint or restain the building exterior where necessary and per standard building practices. Any repairs needed to the siding or trim should be made prior to this.
18) Conducive conditionsCaulk was deteriorated in some areas. For example, around windows, around doors and/or at siding butt joints. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit:
https://www.reporthost.com/_docs/FPL_Caulking_Ins_Outs.pdf
19) [Some] exterior wall sections were obscured by vegetation and/or stored items and couldn't be fully evaluated. They are excluded from this inspection.
Photo
Photo 19-1 
Photo
Photo 19-2 
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Traversed
Location of crawl space access point #A: Building exterior
Crawl space access points that were opened and viewed, traversed or partially traversed: A
Condition of floor substructure above crawl space: Appeared serviceable
Pier or support post material: Wood
Beam material: Solid wood
Floor structure: Solid wood joists
Condition of insulation underneath floor above: Required repairs, replacement and/or evaluation (see comments below)
Insulation material underneath floor above: Fiberglass roll or batt
Condition of vapor barrier: Appeared serviceable
Vapor barrier present: Yes, Full
Condition of crawl space ventilation: Appeared serviceable, Required repairs, replacement and/or evaluation (see comments below)
Ventilation type: with vents
20) One or more outdoor crawl space access hatches or doors were missing, damaged, deteriorated or substandard. Water and/or vermin can enter the crawl space. Recommend that a qualified person replace, install or repair hatches or doors where necessary.
Photo
Photo 20-1 
21) Many sections of under-floor insulation above the crawl space have fallen down, were missing and/or were damaged or deteriorated. This may result in reduced energy efficiency. Recommend that a qualified person install or replace insulation as necessary.
Photo
Photo 21-1 
Photo
Photo 21-2 
Photo
Photo 21-3 
Photo
Photo 21-4 
Photo
Photo 21-5 
22) Insulation in the crawl space was damaged, apparently by rodents (e.g. burrow holes, feces, urine stains). If this report doesn't already recommend replacement of insulation for energy efficiency, the client may want to have insulation replaced for sanitary reasons or to prevent odors.
23) Conducive conditionsCellulose material such as scrap wood was found in the crawl space. This is a conducive condition for wood-destroying organisms. Recommend removing all cellulose-based debris or stored items.
24) One or more crawl space vents were intentionally blocked (e.g. removable panels, rigid foam). This restricts ventilation in the crawl space and can result in increased levels of moisture inside. This is a conducive condition for wood-destroying organisms. Such vents should be left open at all times except during severe freezing weather. Recommend removing materials or items blocking vents as necessary.
Photo
Photo 24-1 
Photo
Photo 24-2 
Photo
Photo 24-3 
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.
Age of roof surface(s): 10-15 years
Roof inspection method: Traversed
Condition of roof surface material: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Required repair, replacement and/or evaluation (see comments below), Near, at or beyond service life
Condition of gutters, downspouts and extensions: Required repair, replacement and/or evaluation (see comments below)
Gutter and downspout material: Metal
Gutter and downspout installation: Full
25) Conducive conditionsFungal rot or significant water damage was found at one or more roof areas at edges of roof sheathing. Recommend that a qualified contractor repair as necessary. For example, by replacing all rotten wood, priming and painting new wood and installing flashing.
Photo
Photo 25-1 
Photo
Photo 25-2 
Photo
Photo 25-3 
Photo
Photo 25-4 
26) Conducive conditionsThe siding on one or more exterior walls was in contact with or too close to roof surfaces below. This is a conducive condition for wood-destroying organisms. There should be a gap of 1 1/2 to 2 inches between a roof surface and siding above. The gap is meant to prevent water from wicking up into the bottom edge of the siding and causing fugal rot, or damaging the siding. There may also be inadequate space for additional layers of roofing materials in the future. Recommend that a qualified contractor repair per standard building practices. For example, by trimming the siding.
Photo
Photo 26-1 
Photo
Photo 26-2 
27) Conducive conditionsSome composition shingles were damaged. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor repair as necessary. For example, by replacing shingles.
Photo
Photo 27-1 
Photo
Photo 27-2 
28) Extensions such as splash blocks or drain pipes for one or more downspouts were misaligned. Water can accumulate around the building foundation or inside crawl spaces or basements as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure.
Photo
Photo 28-1 
Photo
Photo 28-2 
29) Loose zinc strips were found on the roof. Recommend re securing.
Photo
Photo 29-1 
30) Conducive conditionsBarge boards, which are the trim boards at gable ends of roofs, were exposed at their lower ends and subject to rot from exposure to rain runoff. This is a conducive condition for wood-destroying organisms. Shingles or flashing should be installed over them to prevent rot. Recommend that a qualified person install shingles or flashing over exposed barge boards where missing and per standard building practices.
31) Conducive conditionsOne or more roof flashings were substandard and/or missing. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.
Photo
Photo 31-1 
32) Conducive conditionsOne or more rubber or neoprene pipe flashings were loose or lifting. Leaks can result from windblown rain. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary to prevent leaks. For example, by nailing flashings down and sealing as necessary.
Photo
Photo 32-1 
33) Conducive conditionsOne or more downspouts or elbows were loose or detached. Rainwater can come in contact with the building exterior or accumulate around the foundation as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.
Photo
Photo 33-1 
34) No "drip edge" flashing was visible at roof eaves (lower edges) or rakes (gable end edges). Drip edge helps prevent water from soaking into the edges of the roof sheathing material (typically plywood or oriented strand board). This reduces the chance of fungal rot or deterioration from water damage in the roof sheathing. Recommend that a qualified contractor install drip edge flashings where missing and per standard building practices.
35) Conducive conditionsSignificant amounts of debris have accumulated in one or more gutters or downspouts. Gutters can overflow and cause water to come in contact with the building exterior, or water can accumulate around the foundation. This is a conducive condition for wood-destroying organisms. Recommend cleaning gutters and downspouts now and as necessary in the future.
36) Conducive conditionsSignificant amounts of debris such as leaves, needles, seeds, etc. have accumulated on the roof surface. Water may not flow easily off the roof, and can enter gaps in the roof surface. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend cleaning debris from the roof surface now and as necessary in the future.
37) Conducive conditionsVegetation such as trees, shrubs, and/or vines overhung the roof surface or were in contact with the roof edge. Organic debris such as leaves or needles are likely to accumulate in gutters and on the roof surface. Gutters can overflow and cause water to come in contact with the building exterior or water can accumulate around the foundation. This is a conducive condition for wood-destroying organisms. Vegetation in contact with the roof can damage the roof surface and/or the roof drainage system. Recommend pruning vegetation so as to not be in contact with the roof and to not overhang the roof surface. If vegetation is too tall then it should be pruned at least 10 feet above the roof surface.
Photo
Photo 37-1 
38) Moss was growing on the roof. As a result, shingles can lift or be damaged. Leaks can result and/or the roof surface can fail prematurely. Efforts should be made to kill the moss during its growing season (wet months). Typically, zinc or phosphate-based chemicals are used for this and must be applied periodically. For information on various moss treatment products and their pros and cons, visit:
http://www.google.com/search?q=moss+on+roof
Attic and Roof StructureTable of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch(es)
Location of attic access point #A: second floor
Location of attic access point #B: Garage
Attic access points that were opened and viewed, traversed or partially traversed: A
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Ceiling insulation material: Mineral wool loose fill
Approximate attic insulation R value (may vary in areas): R-30
Condition of roof ventilation: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Roof ventilation type: Box vents (roof jacks), Open soffit vents
39) The ceiling insulation in one or more areas of the attic was compacted or uneven. Heating and cooling costs may be higher due to reduced energy efficiency. Recommend that a qualified person repair, replace or install insulation as necessary and per standard building practices (typically R-38).
Photo
Photo 39-1 
40) Attic access point(s) #B were inaccessible because stored items were blocking. These areas were not evaluated and are excluded from this inspection.
Photo
Photo 40-1 
41) All attic areas and roof structures more than 6 feet from attic access point(s) #A were inaccessible due to limited height. These areas were not evaluated and are excluded from the inspection.
Photo
Photo 41-1 
42) Microbial staining was visible on roof sheathing in the attic. Such staining usually occurs due to elevated humidity in the attic, and subsequent elevated moisture levels in the sheathing. When humid attic conditions have been corrected, it's likely that such staining will stop growing. Humid conditions often occur during construction when large volumes of water evaporate from paint and drywall mud, and can then return to normal, dryer levels. However, ongoing ventilation and/or insulation issues can also result in humid conditions. Please note any other comments in this report related to ventilation, insulation and/or moisture levels in the attic, and make any related recommended corrections. After issues related to the moisture conditions have been corrected, the clients may or may not wish to have mitigation work performed for the biological staining. Typically mold abatement specialists perform such work and may do the following:
  • Remove affected attic insulation
  • Clean microbial staining from wood surfaces
  • Treat wood surfaces with mildewcides
  • Prime wood with special primers
  • Install new attic insulation
Note that the inspector is not a mold specialist or industrial hygienist and provides no professional opinion on health issues related to microbial growth.
Photo
Photo 42-1 
Photo
Photo 42-2 
Photo
Photo 42-3 
Photo
Photo 42-4 
Photo
Photo 42-5 
Garage or CarportTable of contents
Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of garage: Appeared serviceable
Type of door between garage and house: Solid core, Wood
Condition of garage vehicle door(s): Not determined (inaccessible or obscured)
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
43) Weatherstripping around or at the base of the door between the garage and the house was damaged. House to garage doors should prevent fire and fumes from spreading from the garage to the house. Weatherstripping should form a seal around this door. This is a potential safety hazard. Recommend that a qualified person replace or install weatherstripping as necessary.
Photo
Photo 43-1 
44) The attic access hatch cover in the attached garage ceiling was missing. Current standard building practices call for wooden-framed ceilings and walls that divide the house and garage to provide limited fire-resistance rating to prevent the spread of fire from the garage to the house. This includes having an access hatch cover installed that is in good condition, with similar fire-resistance. Recommend that a qualified person replace or repair hatch cover(s) per standard building practices. For more information, visit:
http://www.google.com/search?q=attached+garage+fire+resistance
Photo
Photo 44-1 
45) One or more garage vehicle doors were obscured by stored items. The inspector was unable to operate or fully evaluate the door(s) as a result.
Photo
Photo 45-1 
46) Many floor areas were obscured by stored items and/or debris and couldn't be fully evaluated.
Photo
Photo 46-1 
Photo
Photo 46-2 
47) Minor cracks were found in the concrete slab floor. These are common and appeared to be only a cosmetic issue.
48) Modifications were made, such as installing interior walls and/or shelving, and limit or reduce the parking space originally available in the garage.
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide detectors is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide detectors should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 200
System ground: Ground rod(s) in soil
Condition of main service panel: Required repair, replacement and/or evaluation (see comments below)
Location of main service panel #A: Garage
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: Non-metallic sheathed, Aluminum multi-strand
Solid strand aluminum branch circuit wiring present: None visible
Smoke alarms installed: Yes, but not tested
Carbon monoxide alarms installed: No, recommend install
Smoke alarm power source(s): Hard wired
49) No arc fault circuit interrupter (AFCI) breakers were installed for bedroom circuits. These are relatively new devices, and reduce the risk of fire by protecting against overheated or arcing receptacles (outlets) or light fixtures. Consult with a qualified electrician about upgrading circuits to AFCI protection per standard building practices. For more information, visit:
http://www.google.com/search?q=arc+fault+circuit+interrupter
50) Wire splices were exposed and were not contained in a covered junction box. This is a potential shock or fire hazard. Recommend that a qualified electrician repair per standard building practices. For example, by installing permanently mounted junction boxes with cover plates where needed to contain wiring splices.
Photo
Photo 50-1 
51) One or more receptacles (outlets) were installed directly above electric baseboard heaters. This was a common practice in the past, but insulation on appliance cords in contact with the heater(s) can be damaged by heaters. This is a shock and fire hazard. Recommend that a qualified electrician make repairs or modifications as necessary. For example, by converting receptacles to junction boxes, moving receptacles and/or moving baseboard heaters.
Photo
Photo 51-1 
52) Smoke alarms were missing from bedrooms. Additional smoke alarms should be installed as necessary so a functioning detector exists in each hallway leading to bedrooms, in each bedroom, on each level and in any attached garage. For more information, visit:
http://www.cpsc.gov/cpscpub/pubs/5077.html
53) Based on the age of this structure and the appearance of existing smoke alarms, the alarms may have been installed more than 10 years ago. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
http://www.google.com/search?q=old+smoke+alarms
54) No carbon monoxide alarms were visible. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed for new construction and/or for homes being sold. Recommend installing approved CO alarms outside of each separate sleeping area in the immediate vicinity of the bedrooms on each level and in accordance with the manufacturer's recommendations. For more information, visit:
http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html
55) One or more exterior receptacle (outlet) covers were broken. This is a potential shock hazard. Recommend that a qualified person replace covers where necessary.
Photo
Photo 55-1 
56) Batteries in all the smoke alarms should be replaced after taking occupancy, and annually in the future. "Chirping" noises emitted from smoke alarms typically indicate that batteries need replacing. For more information, visit:
http://www.cpsc.gov/cpscpub/pubs/5077.html
57) The inspector was unable to open and evaluate panel(s) #A because items were blocking access. These panel(s) are excluded from this inspection. Recommend that repairs, modifications and/or cleanup should be made as necessary so panels can be opened and fully evaluated.
Photo
Photo 57-1 
58) One or more light fixtures were inoperable (didn't turn on when nearby switches were operated). Recommend further evaluation by replacing bulbs and/or consulting with the property owner. If replacing bulbs doesn't work and/or no other switch(es) can be found, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
Photo
Photo 58-1 
Photo
Photo 58-2 
Plumbing / Fuel SystemsTable of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Location of main water meter: By street
Location of main water shut-off: Building exterior
Service pipe material: Copper
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Location(s) of plumbing clean-outs: Building exterior
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Water HeaterTable of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below), Near, at or beyond service life
Type: Tank
Energy source: Electricity
Estimated age: 15 years
Capacity (in gallons): 80
Temperature-pressure relief valve installed: Yes
Manufacturer: Whirlpool
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 130
59) The water heater's earthquake straps or struts were substandard. For example, they may allow significant movement or use substandard fasteners. This is a potential safety hazard in the event of an earthquake due to the risk of the water heater tipping over, gas lines breaking if it's gas-fired, or electric wiring being damaged if powered by electricity. Leaks can also occur in water-supply pipes. Recommend that a qualified person repair or replace existing earthquake reinforcement per standard building practices.
Photo
Photo 59-1 
60) One or more sections of the temperature-pressure relief valve drain line were sloped upwards. This is a potential safety hazard due to the risk of explosion. Water and/or minerals can accumulate in the drain line after periodic discharges and impair the operation of the valve. Also, mineral deposits from accumulated water can accumulate on the valve and impair its operation. A qualified plumber should repair per standard building practices, and so the drain line doesn't slope upwards. For more information, visit: https://www.reporthost.com/_docs/TPvalve.pdf
Photo
Photo 60-1 
61) One or more flexible connectors were used for the temperature-pressure relief valve drain line. Flex connectors can be bent or kinked so as to restrict the flow of the drain line and impair the operation of the valve. They typically are not rated for the temperature and pressure of water being discharged (potentially 150 psi and 210 degrees F). Flex connectors used this way pose a potential safety hazard for explosion. Recommend that a qualified plumber repair per standard building practices. For example, by installing a drain line made of rigid copper or CPVC plastic pipe.
Photo
Photo 61-1 
62) The hot water temperature was greater than 120 degrees Fahrenheit. This is a safety hazard due to the risk of scalding. The thermostat should be adjusted so the water temperature doesn't exceed 120 degrees. If the water heater is powered by electricity, a qualified person should perform the adjustment, since covers that expose energized equipment normally need to be removed. For more information on scalding dangers, visit:
http://www.cpsc.gov/CPSCPUB/PUBS/5098.pdf
63) Significant corrosion or rust was found at the supply pipes or fittings. This can indicate past leaks, or that leaks are likely to occur in the future. Recommend that a qualified plumber evaluate and replace components or make repairs as necessary.
Photo
Photo 63-1 
Photo
Photo 63-2 
64) The estimated useful life for most water heaters is 8-12 years. This water heater appeared to be beyond this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.
Photo
Photo 64-1 
65) A water heater was installed over a finished living space or in an area where leaking can cause damage, and there was no catch pan and no drain was installed. Consider having a qualified contractor install a catch pan and drain to prevent water damage if the water heater develops a leak. Note that installing a drain may be difficult or impossible depending on the location of the water heater.
Heating, Ventilation and Air Condition (HVAC)Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Electric heaters
General heating distribution type(s): None, individual heaters
Condition of electric heaters (not forced air): Required repair, replacement and/or evaluation (see comments below)
Electric heater type (not forced air): Baseboard, Wall mounted, with fan
Manufacturer of electric heaters (not forced air): Cadet
Condition of controls: Appeared serviceable
Condition of whole house fan: Required repair, replacement and/or evaluation (see comments below)
24 hour automatic ventilation system present: Yes
66) One or more recalled Cadet brand wall heaters were found. Cadet models FW, FX, LX, TK, ZA, Z, RA, RK, RLX, RX, RW and ZC wall heaters have been recalled. The client should ask the property owner if repairs have been made related to the recalls. If so, documentation for the repairs should be reviewed. If not, then a qualified electrician should evaluate and replace or repair heaters as necessary. For more info visit:
http://www.cadetco.com/
http://www.cpsc.gov/CPSCPUB/PREREL/PRHTML00/00070.html
67) One or more windows in this structure were equipped with air supply ports (window vents). These are intended to improve indoor air quality in relatively air- tight structures by supplying fresh air to living spaces and by reducing moisture accumulation. Air supply ports should be kept open at all times.
68) An exhaust fan with a 24 or 12 hour timer was installed and served as a simple ventilation system. The set pins for the timer are missing.Recommend installing set pins to make timer operational.

The timer can be configured to operate the fan automatically one or more times per day for a set length of time. These fans help reduce moisture and stale air inside the house. Guidelines vary for when and how long such fans should be configured to operate depending on the size of the house, number of occupants and rating of the fan. Recommend reviewing instructions or documentation for the timer and configuring the fan as necessary. The inspector notes these systems when present, but does not determine their adequacy, or if the timer is operable. For more information, visit:
http://www.google.com/search?q=configure+laundry+fan+ventilation
Photo
Photo 68-1 
Fireplaces, Stoves, Chimneys and FluesTable of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Required repair, replacement and/or evaluation (see comments below)
Wood-burning stove type: Pellet stove
Fan or blower installed in wood-burning fireplace or stove: Yes
69) A pellet stove was installed. The inspector performs a visual evaluation of such wood-burning devices and their components, and does not light fires. Unlike wood stoves, there are no generic standards or guidelines for pellet stove installations, so they're installed per the manufacturer's instructions. Recommend that a qualified specialist evaluate to determine if the installation is in accordance with the manufacturer's specifications (e.g. clearances, hearth size, flue configuration). For more information, visit:
http://www.google.com/search?q=pellet+stove+safety
Photo
Photo 69-1 
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Permanently installed kitchen appliances present during inspection: Range, Dishwasher, Refrigerator
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of under-sink food disposal: N/A (none installed)
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop: Appeared serviceable
Range, cooktop type: Electric
Condition of refrigerator: Appeared serviceable
Condition of built: N/A (none installed)
Condition of hot water dispenser: N/A (none installed)
Condition of trash compactor: N/A (none installed)
70) The sink sprayer was inoperable. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 70-1 
71) Substandard repairs were found at the sink drain (e.g. tape, sealant, non-standard components). Recommend that a qualified plumber repair per standard building practices.
Photo
Photo 71-1 
Photo
Photo 71-2 
72) The sink faucet was dripping. Recommend that a qualified person repair as necessary.
73) The countertops and/or areas below sink(s) were obscured by stored items or dishes and couldn't be fully evaluated.
Bathrooms, Laundry and SinksTable of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Half bath, first floor
Location #B: Full bath, second floor
Location #C: Master bath, second floor
Location #D: Laundry room/area
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable, Required repairs, replacement and/or evaluation (see comments below)
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom ventilation type: with individual exhaust ducts
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes
74) Conducive conditionsVinyl floor tiles was installed in the bathroom at location(s) #C. Spilled water can penetrate seams and damage the subfloor. Recommend that a qualified contractor install continuous waterproof flooring in wet areas such as bathrooms.
Photo
Photo 74-1 
75) The sink at location(s) #B was damaged or significantly deteriorated. Recommend that a qualified contractor replace the sink.
Photo
Photo 75-1 
Photo
Photo 75-2 
76) The laundry room didn't have an exhaust fan installed. Moisture can accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified contractor install an exhaust fan per standard building practices.
77) The clothes washer was installed over a finished space and had no catch pan or drain installed. Catch pans and drains prevent water damage to finished interior spaces below if or when the washing machine leaks, overflows or is drained. Recommend that a qualified contractor install both a catch pan and drain per standard building practices.
78) Conducive conditionsOne or more sink were leaking at location(s) #B. A qualified person should repair as necessary.
Photo
Photo 78-1 
79) Conducive conditionsCaulk was missing around the base of the the bathtub spout, or there was a gap behind it, at location(s) #B and C. Water may enter the wall structure behind the bathtub. Recommend that a qualified person repair as necessary to eliminate the gap. For example, by installing or replacing caulk if the gap is small enough. For larger gaps, a shorter spout nipple or an escutcheon plate can be installed.
Photo
Photo 79-1 
Photo
Photo 79-2 
80) Conducive conditionsGaps, no caulk, or substandard caulking were found between the bathtub and the floor at location(s) #B and C. Water may penetrate these areas and cause damage. Recommend that a qualified person re-caulk or install caulking as necessary.
Photo
Photo 80-1 
Photo
Photo 80-2 
81) The sink at location(s) #B drained slowly. Recommend clearing drain and/or having a qualified plumber repair if necessary.
Photo
Photo 81-1 
82) No caulk was installed around the base of the toilet at location(s) #A and C where fastened to the floor. Caulk should be applied approximately 3/4 of the way around the toilet base at the front for sanitary purposes and to prevent water intrusion. The back should be left uncaulked so water can escape if a leak ever occurs. Recommend that a qualified person caulk around the toilet base(s) per standard building practices.
83) The bathtub drain stopper mechanism at location(s) #B and C was missing and/or inoperable. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 83-1 
Photo
Photo 83-2 
84) No access or only limited access was available to the back of the clothes washer and dryer, and to utility hook-ups located behind the appliances. The inspector normally attempts to determine the presence of a gas vs. electric power supply, the configuration of the stand pipe, whether the dryer exhaust duct is serviceable, etc. Because of the lack of access, the inspector was unable to fully evaluate and/or describe the hook-ups and appliances.
85) The countertops and/or areas below sink(s) at location(s) #A, B and C were obscured by stored items and couldn't be fully evaluated.
Interior, Doors and WindowsTable of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Metal, Sliding glass
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Type(s) of windows: Vinyl, Multi-pane, Sliding, Single-hung, Fixed
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Flooring type or covering: Carpet, Laminate, Tile
Condition of stairs, handrails and guardrails: Required repairs, replacement and/or evaluation (see comments below)
86) One or more handrails had no "returns" installed, where ends of handrails turn and connect to adjacent walls so objects or clothing will not catch on the open ends. This is a safety hazard. Recommend that a qualified person install returns per standard building practices.
Photo
Photo 86-1 
87) Conducive conditionsCondensation or staining was visible between multi-pane glass in one or more windows. This usually indicates that the seal between the panes of glass has failed or that the desiccant material that absorbs moisture is saturated. As a result, the view through the window may be obscured, the window's R-value will be reduced, and accumulated condensation may leak into the wall structure below. Recommend that a qualified contractor evaluate and repair windows as necessary. Usually, this means replacing the glass in window frames.

Be aware that evidence of failed seals or desiccant may be more or less visible depending on the temperature, humidity, sunlight, etc. Windows or glass-paneled doors other than those that the inspector identified may also have failed seals and need glass replaced. It is beyond the scope of this inspection to identify every window with failed seals or desiccant.
Photo
Photo 87-1 
Photo
Photo 87-2 
88) The seal between multi-pane glass in one or more sliding glass doors appeared to have failed based on condensation or stains between the panes of glass. Recommend that a qualified contractor evaluate and replace glass where necessary.

Be aware that evidence of broken seals may be more or less visible from one day to the next depending on the temperature, humidity, sunlight, etc. Glass doors or windows other than those that the inspector identified may also have failed seals and need glass replaced too.
Photo
Photo 88-1 
89) One or more interior doors were missing. Recommend that a qualified person replace or repair doors as necessary.
Photo
Photo 89-1 
Photo
Photo 89-2 
Photo
Photo 89-3 
90) One or more walls had substandard repairs. Recommend that a qualified person repair as necessary.
Photo
Photo 90-1 
91) Carpeting in one or more areas was loose. Recommend that a qualified contractor repair as necessary. For example, by stretching or replacing carpeting.
Photo
Photo 91-1 
92) Trim was missing in one or more areas. Recommend that a qualified person repair as necessary.
93) Minor cracks, nail pops and/or blemishes were found in walls and/or ceilings in one or more areas. Cracks and nail pops are common, are often caused by lumber shrinkage or minor settlement, and can be more or less noticeable depending on changes in humidity. They did not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons. For recurring cracks, consider using an elastic crack covering product:
http://www.google.com/search?q=elastic+crack+cover
94) Carpeting in one or more areas was significantly stained or soiled. Recommend having carpeting professionally cleaned as necessary.
95) Patches or evidence of prior repairs were found in one or more walls or ceilings. Recommend asking the property owner about the repairs (e.g. why necessary, whether prior leaks have occurred).
Photo
Photo 95-1 

PLEASE NOTE THE PICTURES PROVIDED ARE NOT EXCLUSIVE OF ALL FINDINGS AND ARE USED TO HELP VISUALIZE THE DEFECTS NOTED.