Summary

Client(s):  Example
Property address:  18714 Woodburn Ct SE
Yelm Wa
Inspection date:  Thursday, June 10, 2021

This report published on Tuesday, June 29, 2021 1:52:29 PM PDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

PLEASE NOTE THE PICTURES PROVIDED ARE NOT EXCLUSIVE OF ALL FINDINGS AND ARE USED TO HELP VISUALIZE THE DEFECTS NOTED.

Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a risk of injury or death
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information
Concern typeConducive conditionsConditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)
Attachments
Olive Inspection agreement(1).pdf


General Information
1) Evidence of rodent infestation was found in the form of feces and/or damaged insulation in the crawl space. Consult with the property owner about this. A qualified person should make repairs to seal openings in the structure, set traps, and clean rodent waste as necessary. Recommend following guidelines in these Center for Disease Control articles:
http://www.cdc.gov/rodents/prevent_infestations/seal_up.html
http://www.cdc.gov/rodents/prevent_infestations/trap_up.html
http://www.cdc.gov/rodents/prevent_infestations/clean_up.html

Grounds
3) Fungal rot was found at one or more guardrail top rails. Recommend that a qualified person evaluate and repair as necessary. All rotten wood should be replaced.
Photo
Photo 3-1 
Photo
Photo 3-2 
4) Risers for stairs at one or more locations were higher than 7 3/4 inches and posed a fall or trip hazard. Risers should be 7 3/4 inches or shorter. At a minimum, be aware of this hazard, especially when guests who are not familiar with the stairs are present. Recommend that a qualified contractor repair per standard building practices.
Photo
Photo 4-1 
5) The risers for stairs at one or more locations varied in height and pose a fall or trip hazard. Risers within the same flight of stairs should vary by no more than 3/8 inch. At a minimum, be aware of this hazard, especially when guests who are not familiar with the stairs are present. Recommend that a qualified contractor repair per standard building practices.
Photo
Photo 5-1 
6) One or more sets of stairs were unstable and/or wobbly. A qualified contractor should repair as necessary. For example, by installing additional bracing or supports.
Photo
Photo 6-1 
7) Guardrails at one or more locations with drop-offs higher than 30 inches were loose and/or wobbly, and pose a fall hazard. Recommend that a qualified person repair guardrails as necessary.
Photo
Photo 7-1 
Photo
Photo 7-2 

Exterior and Foundation
12) Some sections of siding and/or trim were missing. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo
Photo 12-1 

Roof
25) Conducive conditionsFungal rot or significant water damage was found at one or more roof areas at edges of roof sheathing. Recommend that a qualified contractor repair as necessary. For example, by replacing all rotten wood, priming and painting new wood and installing flashing.
Photo
Photo 25-1 
Photo
Photo 25-2 
Photo
Photo 25-3 
Photo
Photo 25-4 
26) Conducive conditionsThe siding on one or more exterior walls was in contact with or too close to roof surfaces below. This is a conducive condition for wood-destroying organisms. There should be a gap of 1 1/2 to 2 inches between a roof surface and siding above. The gap is meant to prevent water from wicking up into the bottom edge of the siding and causing fugal rot, or damaging the siding. There may also be inadequate space for additional layers of roofing materials in the future. Recommend that a qualified contractor repair per standard building practices. For example, by trimming the siding.
Photo
Photo 26-1 
Photo
Photo 26-2 
27) Conducive conditionsSome composition shingles were damaged. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor repair as necessary. For example, by replacing shingles.
Photo
Photo 27-1 
Photo
Photo 27-2 
28) Extensions such as splash blocks or drain pipes for one or more downspouts were misaligned. Water can accumulate around the building foundation or inside crawl spaces or basements as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure.
Photo
Photo 28-1 
Photo
Photo 28-2 
29) Loose zinc strips were found on the roof. Recommend re securing.
Photo
Photo 29-1 

Garage or Carport
43) Weatherstripping around or at the base of the door between the garage and the house was damaged. House to garage doors should prevent fire and fumes from spreading from the garage to the house. Weatherstripping should form a seal around this door. This is a potential safety hazard. Recommend that a qualified person replace or install weatherstripping as necessary.
Photo
Photo 43-1 
44) The attic access hatch cover in the attached garage ceiling was missing. Current standard building practices call for wooden-framed ceilings and walls that divide the house and garage to provide limited fire-resistance rating to prevent the spread of fire from the garage to the house. This includes having an access hatch cover installed that is in good condition, with similar fire-resistance. Recommend that a qualified person replace or repair hatch cover(s) per standard building practices. For more information, visit:
http://www.google.com/search?q=attached+garage+fire+resistance
Photo
Photo 44-1 

Electric
49) No arc fault circuit interrupter (AFCI) breakers were installed for bedroom circuits. These are relatively new devices, and reduce the risk of fire by protecting against overheated or arcing receptacles (outlets) or light fixtures. Consult with a qualified electrician about upgrading circuits to AFCI protection per standard building practices. For more information, visit:
http://www.google.com/search?q=arc+fault+circuit+interrupter
50) Wire splices were exposed and were not contained in a covered junction box. This is a potential shock or fire hazard. Recommend that a qualified electrician repair per standard building practices. For example, by installing permanently mounted junction boxes with cover plates where needed to contain wiring splices.
Photo
Photo 50-1 
51) One or more receptacles (outlets) were installed directly above electric baseboard heaters. This was a common practice in the past, but insulation on appliance cords in contact with the heater(s) can be damaged by heaters. This is a shock and fire hazard. Recommend that a qualified electrician make repairs or modifications as necessary. For example, by converting receptacles to junction boxes, moving receptacles and/or moving baseboard heaters.
Photo
Photo 51-1 
52) Smoke alarms were missing from bedrooms. Additional smoke alarms should be installed as necessary so a functioning detector exists in each hallway leading to bedrooms, in each bedroom, on each level and in any attached garage. For more information, visit:
http://www.cpsc.gov/cpscpub/pubs/5077.html
53) Based on the age of this structure and the appearance of existing smoke alarms, the alarms may have been installed more than 10 years ago. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
http://www.google.com/search?q=old+smoke+alarms
54) No carbon monoxide alarms were visible. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed for new construction and/or for homes being sold. Recommend installing approved CO alarms outside of each separate sleeping area in the immediate vicinity of the bedrooms on each level and in accordance with the manufacturer's recommendations. For more information, visit:
http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html
55) One or more exterior receptacle (outlet) covers were broken. This is a potential shock hazard. Recommend that a qualified person replace covers where necessary.
Photo
Photo 55-1 
56) Batteries in all the smoke alarms should be replaced after taking occupancy, and annually in the future. "Chirping" noises emitted from smoke alarms typically indicate that batteries need replacing. For more information, visit:
http://www.cpsc.gov/cpscpub/pubs/5077.html
57) The inspector was unable to open and evaluate panel(s) #A because items were blocking access. These panel(s) are excluded from this inspection. Recommend that repairs, modifications and/or cleanup should be made as necessary so panels can be opened and fully evaluated.
Photo
Photo 57-1 

Water Heater
59) The water heater's earthquake straps or struts were substandard. For example, they may allow significant movement or use substandard fasteners. This is a potential safety hazard in the event of an earthquake due to the risk of the water heater tipping over, gas lines breaking if it's gas-fired, or electric wiring being damaged if powered by electricity. Leaks can also occur in water-supply pipes. Recommend that a qualified person repair or replace existing earthquake reinforcement per standard building practices.
Photo
Photo 59-1 
60) One or more sections of the temperature-pressure relief valve drain line were sloped upwards. This is a potential safety hazard due to the risk of explosion. Water and/or minerals can accumulate in the drain line after periodic discharges and impair the operation of the valve. Also, mineral deposits from accumulated water can accumulate on the valve and impair its operation. A qualified plumber should repair per standard building practices, and so the drain line doesn't slope upwards. For more information, visit: https://www.reporthost.com/_docs/TPvalve.pdf
Photo
Photo 60-1 
61) One or more flexible connectors were used for the temperature-pressure relief valve drain line. Flex connectors can be bent or kinked so as to restrict the flow of the drain line and impair the operation of the valve. They typically are not rated for the temperature and pressure of water being discharged (potentially 150 psi and 210 degrees F). Flex connectors used this way pose a potential safety hazard for explosion. Recommend that a qualified plumber repair per standard building practices. For example, by installing a drain line made of rigid copper or CPVC plastic pipe.
Photo
Photo 61-1 
62) The hot water temperature was greater than 120 degrees Fahrenheit. This is a safety hazard due to the risk of scalding. The thermostat should be adjusted so the water temperature doesn't exceed 120 degrees. If the water heater is powered by electricity, a qualified person should perform the adjustment, since covers that expose energized equipment normally need to be removed. For more information on scalding dangers, visit:
http://www.cpsc.gov/CPSCPUB/PUBS/5098.pdf
63) Significant corrosion or rust was found at the supply pipes or fittings. This can indicate past leaks, or that leaks are likely to occur in the future. Recommend that a qualified plumber evaluate and replace components or make repairs as necessary.
Photo
Photo 63-1 
Photo
Photo 63-2 

Heating, Ventilation and Air Condition (HVAC)
66) One or more recalled Cadet brand wall heaters were found. Cadet models FW, FX, LX, TK, ZA, Z, RA, RK, RLX, RX, RW and ZC wall heaters have been recalled. The client should ask the property owner if repairs have been made related to the recalls. If so, documentation for the repairs should be reviewed. If not, then a qualified electrician should evaluate and replace or repair heaters as necessary. For more info visit:
http://www.cadetco.com/
http://www.cpsc.gov/CPSCPUB/PREREL/PRHTML00/00070.html

Fireplaces, Stoves, Chimneys and Flues
69) A pellet stove was installed. The inspector performs a visual evaluation of such wood-burning devices and their components, and does not light fires. Unlike wood stoves, there are no generic standards or guidelines for pellet stove installations, so they're installed per the manufacturer's instructions. Recommend that a qualified specialist evaluate to determine if the installation is in accordance with the manufacturer's specifications (e.g. clearances, hearth size, flue configuration). For more information, visit:
http://www.google.com/search?q=pellet+stove+safety
Photo
Photo 69-1 

Kitchen
70) The sink sprayer was inoperable. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 70-1 
71) Substandard repairs were found at the sink drain (e.g. tape, sealant, non-standard components). Recommend that a qualified plumber repair per standard building practices.
Photo
Photo 71-1 
Photo
Photo 71-2 

Bathrooms, Laundry and Sinks
74) Conducive conditionsVinyl floor tiles was installed in the bathroom at location(s) #C. Spilled water can penetrate seams and damage the subfloor. Recommend that a qualified contractor install continuous waterproof flooring in wet areas such as bathrooms.
Photo
Photo 74-1 
75) The sink at location(s) #B was damaged or significantly deteriorated. Recommend that a qualified contractor replace the sink.
Photo
Photo 75-1 
Photo
Photo 75-2 
76) The laundry room didn't have an exhaust fan installed. Moisture can accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified contractor install an exhaust fan per standard building practices.
77) The clothes washer was installed over a finished space and had no catch pan or drain installed. Catch pans and drains prevent water damage to finished interior spaces below if or when the washing machine leaks, overflows or is drained. Recommend that a qualified contractor install both a catch pan and drain per standard building practices.

Interior, Doors and Windows
86) One or more handrails had no "returns" installed, where ends of handrails turn and connect to adjacent walls so objects or clothing will not catch on the open ends. This is a safety hazard. Recommend that a qualified person install returns per standard building practices.
Photo
Photo 86-1 
87) Conducive conditionsCondensation or staining was visible between multi-pane glass in one or more windows. This usually indicates that the seal between the panes of glass has failed or that the desiccant material that absorbs moisture is saturated. As a result, the view through the window may be obscured, the window's R-value will be reduced, and accumulated condensation may leak into the wall structure below. Recommend that a qualified contractor evaluate and repair windows as necessary. Usually, this means replacing the glass in window frames.

Be aware that evidence of failed seals or desiccant may be more or less visible depending on the temperature, humidity, sunlight, etc. Windows or glass-paneled doors other than those that the inspector identified may also have failed seals and need glass replaced. It is beyond the scope of this inspection to identify every window with failed seals or desiccant.
Photo
Photo 87-1 
Photo
Photo 87-2 
88) The seal between multi-pane glass in one or more sliding glass doors appeared to have failed based on condensation or stains between the panes of glass. Recommend that a qualified contractor evaluate and replace glass where necessary.

Be aware that evidence of broken seals may be more or less visible from one day to the next depending on the temperature, humidity, sunlight, etc. Glass doors or windows other than those that the inspector identified may also have failed seals and need glass replaced too.
Photo
Photo 88-1 
89) One or more interior doors were missing. Recommend that a qualified person replace or repair doors as necessary.
Photo
Photo 89-1 
Photo
Photo 89-2 
Photo
Photo 89-3 
90) One or more walls had substandard repairs. Recommend that a qualified person repair as necessary.
Photo
Photo 90-1 
91) Carpeting in one or more areas was loose. Recommend that a qualified contractor repair as necessary. For example, by stretching or replacing carpeting.
Photo
Photo 91-1