 | Client(s): | John Doe | 
| Property address: | 123 Any Avenue Montclair, NJ 07043-1122 | 
| Inspection date: | Monday, May 16, 2016 | 
This report published on Friday, January 4, 2019 7:46:50 PM EST
|  | Safety | Poses a risk of injury | 
|  | Major Defect | Correction likely involves a significant expense | 
|  | Repair/Replace | Recommend repairing or replacing | 
|  | Repair/Maintain | Recommend repair and/or maintenance | 
|  | Maintain | Recommend ongoing maintenance | 
|  | Evaluate | Recommend evaluation by a specialist | 
|  | Monitor | Recommend monitoring in the future | 
|  | Summary Item | Item or component will appear on the summary page of the report | 
|  | Comment | For your information | 
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

 Structures built prior to 1980 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client should consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
Structures built prior to 1980 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client should consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
 The following additions, renovations and/or installations were noted. Obtain all permits and final approvals by the local building department officials from the present owner for the following:
The following additions, renovations and/or installations were noted. Obtain all permits and final approvals by the local building department officials from the present owner for the following: Some wall and floor surfaces were obscured by furniture and/or stored items and couldn't be fully evaluated.
Some wall and floor surfaces were obscured by furniture and/or stored items and couldn't be fully evaluated.
 Recommend evaluation by licensed environmental contractor for environmental hazards (hazardous plants, animals, diseases, suspected hazardous substances or adverse conditions such as lead, asbestos, fungus and mold, toxins, carcinogens, noise and contaminants in soil, water and air, etc.).
Recommend evaluation by licensed environmental contractor for environmental hazards (hazardous plants, animals, diseases, suspected hazardous substances or adverse conditions such as lead, asbestos, fungus and mold, toxins, carcinogens, noise and contaminants in soil, water and air, etc.).
 Failure probability of any appliance is unpredictable. It is highly recommended to obtain a Home Warranty Agreement to protect against unexpected appliance failure expenses.
Failure probability of any appliance is unpredictable. It is highly recommended to obtain a Home Warranty Agreement to protect against unexpected appliance failure expenses.
 Due to closed walls, fixed or suspended ceilings in the lower level of this structure, there is extremely limited to no accessibility to wood framing for inspection. Many buildings have hidden termite and/or wood destroying insect infestation/damage that a competently performed wood destroying inspection may not disclose under these conditions.
Due to closed walls, fixed or suspended ceilings in the lower level of this structure, there is extremely limited to no accessibility to wood framing for inspection. Many buildings have hidden termite and/or wood destroying insect infestation/damage that a competently performed wood destroying inspection may not disclose under these conditions.
 Security system installed. Obtain all documents pertaining to ownership and costs of operation. Recommend evaluation by licensed security technician for integrity and functionality of system.
Security system installed. Obtain all documents pertaining to ownership and costs of operation. Recommend evaluation by licensed security technician for integrity and functionality of system.

 One or more retaining walls higher than three feet were found on this property and guardrails or barriers were missing. Handrails were missing from the terraced steps. This is a safety hazard due to the risk of falling. A qualified contractor should install or repair guardrails as necessary above retaining walls higher than 3 feet to eliminate fall hazards.
One or more retaining walls higher than three feet were found on this property and guardrails or barriers were missing. Handrails were missing from the terraced steps. This is a safety hazard due to the risk of falling. A qualified contractor should install or repair guardrails as necessary above retaining walls higher than 3 feet to eliminate fall hazards.



 One or more large trees were very close to the foundation. Tree roots can cause  significant structural damage to foundations. Recommend having a qualified tree service contractor or arborist remove trees as necessary to prevent damage to the building's foundation.
One or more large trees were very close to the foundation. Tree roots can cause  significant structural damage to foundations. Recommend having a qualified tree service contractor or arborist remove trees as necessary to prevent damage to the building's foundation.
 The curb at the street was deteriorated. Determine responsibility for repairs.
The curb at the street was deteriorated. Determine responsibility for repairs.


 Vegetation such as trees, shrubs and/or vines was in contact with or less than twelve inches from the building exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a twelve inch clearance between it and the building exterior.
Vegetation such as trees, shrubs and/or vines was in contact with or less than twelve inches from the building exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a twelve inch clearance between it and the building exterior.


 Wooden shed on property. Manufactured August of 2010. Repairs recommended.
Wooden shed on property. Manufactured August of 2010. Repairs recommended.





 Inground pool and equipment installed. Recommend full evaluation of all components by a qualified pool/spa contractor for integrity and functionality.
Inground pool and equipment installed. Recommend full evaluation of all components by a qualified pool/spa contractor for integrity and functionality.


 Minor cracks, settlement, heaving and/or deterioration were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
Minor cracks, settlement, heaving and/or deterioration were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client may wish to have repairs made or have cracked sections replaced for aesthetic reasons.


 Minor cracks, settlement, heaving and/or deterioration were found in one or more sidewalk or patio sections. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
Minor cracks, settlement, heaving and/or deterioration were found in one or more sidewalk or patio sections. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client may wish to have repairs made or have cracked sections replaced for aesthetic reasons.




 Major cracks (more than 3/4 inch wide) and or leaning were found in the foundation on the northeast side of the building. These appear to be a structural concern, and may indicate that settlement is ongoing. The client are strongly advised  to hire qualified contractors and/or engineers as necessary for further evaluation. Such contractors may include:
Major cracks (more than 3/4 inch wide) and or leaning were found in the foundation on the northeast side of the building. These appear to be a structural concern, and may indicate that settlement is ongoing. The client are strongly advised  to hire qualified contractors and/or engineers as necessary for further evaluation. Such contractors may include:






 Minor cracks or deterioration were found in one or more sections of brick veneer. A qualified contractor should evaluate and make repairs as necessary, such as repointing mortar to prevent water intrusion and further deterioration in the future.
Minor cracks or deterioration were found in one or more sections of brick veneer. A qualified contractor should evaluate and make repairs as necessary, such as repointing mortar to prevent water intrusion and further deterioration in the future.



 Many foundation and/or footings sections were obscured by being below grade and couldn't be fully evaluated.
Many foundation and/or footings sections were obscured by being below grade and couldn't be fully evaluated.

 Paper facing on batt insulation in the attic was exposed. The paper facing is flammable, and poses a safety hazard due to the risk of fire. Also, the paper facing typically acts as a vapor barrier, and if located away from the interior surfaces, can trap moisture from condensation in the cavity between the paper facing and the interior spaces. This is a conducive condition for wood destroying insects. The inspector was unable to evaluate the structure obscured by the insulation. A qualified person should reinstall or replace the insulation as per standard building practices and as per the manufacturer's instructions.
Paper facing on batt insulation in the attic was exposed. The paper facing is flammable, and poses a safety hazard due to the risk of fire. Also, the paper facing typically acts as a vapor barrier, and if located away from the interior surfaces, can trap moisture from condensation in the cavity between the paper facing and the interior spaces. This is a conducive condition for wood destroying insects. The inspector was unable to evaluate the structure obscured by the insulation. A qualified person should reinstall or replace the insulation as per standard building practices and as per the manufacturer's instructions.




 Roof repairs were needed because many slate tiles were cracked, broken, loose and/or deteriorated. Leaks may occur as a result. A qualified contractor should fully evaluate and repair as necessary.
Roof repairs were needed because many slate tiles were cracked, broken, loose and/or deteriorated. Leaks may occur as a result. A qualified contractor should fully evaluate and repair as necessary.










 The interior of the garage has been finished. There are water pipes in the walls. Recommend further evaluation for purpose, integrity and functionality of the plumbing. One supply valve is in the closed position.
The interior of the garage has been finished. There are water pipes in the walls. Recommend further evaluation for purpose, integrity and functionality of the plumbing. One supply valve is in the closed position.






 One or more overcurrent protection devices (circuit breakers or fuses) in panel #D were "double tapped", where 2 or more wires were clamped in a terminal designed for only one wire. This is a safety hazard since the bolt or screw may tighten securely against one wire, but leave others loose. Arcing, sparks and fires may result. A qualified electrician should evaluate and repair as necessary.
One or more overcurrent protection devices (circuit breakers or fuses) in panel #D were "double tapped", where 2 or more wires were clamped in a terminal designed for only one wire. This is a safety hazard since the bolt or screw may tighten securely against one wire, but leave others loose. Arcing, sparks and fires may result. A qualified electrician should evaluate and repair as necessary.






 Neutral wires were doubled or bundled together on the neutral bus bar in panel #A. This is unsafe due to the need to turn off multiple circuit breakers to work on any of the circuits using these wires. A qualified electrician should evaluate and repair as necessary.
Neutral wires were doubled or bundled together on the neutral bus bar in panel #A. This is unsafe due to the need to turn off multiple circuit breakers to work on any of the circuits using these wires. A qualified electrician should evaluate and repair as necessary.





 Neutral and equipment ground conductors were combined at sub-panel # E. This should only occur in the main service panel, and is a safety hazard due to the risk of shock. Neutral conductors should be attached to a "floating" neutral bar not bonded to the panel, while grounding conductors should be attached to a separate grounding bar bonded to the sub-panel. A qualified electrician should evaluate and repair as necessary.
Neutral and equipment ground conductors were combined at sub-panel # E. This should only occur in the main service panel, and is a safety hazard due to the risk of shock. Neutral conductors should be attached to a "floating" neutral bar not bonded to the panel, while grounding conductors should be attached to a separate grounding bar bonded to the sub-panel. A qualified electrician should evaluate and repair as necessary.





 Two-pronged electric receptacles rather than three-pronged, grounded receptacles were installed in some areas. They are considered to be unsafe by today's standards and limit the ability to use appliances that require a ground in these rooms. Examples of appliances that require grounded receptacles include:
Two-pronged electric receptacles rather than three-pronged, grounded receptacles were installed in some areas. They are considered to be unsafe by today's standards and limit the ability to use appliances that require a ground in these rooms. Examples of appliances that require grounded receptacles include:


 Some open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.
Some open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary. 


 One or more electric receptacles at the kitchen and/or garage had no visible ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. Recommend having a qualified electrician evaluate to determine if GFCI protection exists, and if not, repair as necessary. For more information, visit:
One or more electric receptacles at the kitchen and/or garage had no visible ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. Recommend having a qualified electrician evaluate to determine if GFCI protection exists, and if not, repair as necessary. For more information, visit:

 One or more wires were damaged in panel #A. A qualified electrician should evaluate and repair or replace wiring as necessary.
One or more wires were damaged in panel #A. A qualified electrician should evaluate and repair or replace wiring as necessary.




 Some switches were damaged. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair or replace as necessary.
Some switches were damaged. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair or replace as necessary.
 Recommend having a qualified electrician install a main disconnect switch at sub-panels #B, #C, #D and #E because the sub-panels were far from the main panel.
Recommend having a qualified electrician install a main disconnect switch at sub-panels #B, #C, #D and #E because the sub-panels were far from the main panel.

 Based on the age of this structure and the appearance of existing smoke alarms, the alarms may be older than 10 years old. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
Based on the age of this structure and the appearance of existing smoke alarms, the alarms may be older than 10 years old. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
 One or more screws were missing from the cover to panel #A and should be replaced. Because energized wiring may exist behind the holes with the missing screws, recommend that a qualified, licensed electrician replace these screws, or that care be taken to ensure that the new screws do not come in contact with wiring inside the panel when they are installed. Stock screws from the panel manufacturer should be used, or their equivalent.
One or more screws were missing from the cover to panel #A and should be replaced. Because energized wiring may exist behind the holes with the missing screws, recommend that a qualified, licensed electrician replace these screws, or that care be taken to ensure that the new screws do not come in contact with wiring inside the panel when they are installed. Stock screws from the panel manufacturer should be used, or their equivalent.

 Some junction box cover plates were missing. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. A qualified person should repair as necessary.
Some junction box cover plates were missing. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. A qualified person should repair as necessary.


 Water supply lines were routed outside and are subject to freezing. Inside shut-off valves exist for these supply pipes. In the fall remove hoses, open hose bibbs and shut off interior shut-off valves as necessary to drain to prevent pipes from freezing and bursting.
Water supply lines were routed outside and are subject to freezing. Inside shut-off valves exist for these supply pipes. In the fall remove hoses, open hose bibbs and shut off interior shut-off valves as necessary to drain to prevent pipes from freezing and bursting.
 Copper water supply pipes in buildings built prior to 1986 may be joined with solder that contains lead. Lead is a known health hazard, especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained about 50 percent lead. The client should be aware of this, especially if children will be living in this structure. Evaluating for the presence of lead in this structure is not included in this inspection. The client should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions such as these may be advised:
Copper water supply pipes in buildings built prior to 1986 may be joined with solder that contains lead. Lead is a known health hazard, especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained about 50 percent lead. The client should be aware of this, especially if children will be living in this structure. Evaluating for the presence of lead in this structure is not included in this inspection. The client should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions such as these may be advised:

 The main water service pipe material was galvanized steel. Based on the age of the building or apparent age of the pipe, and the low-flow condition of the water supply system, this service pipe may have significant interior corrosion and need replacing. Replacing the service pipe may significantly increase flow to the water supply pipes. A qualified plumber should evaluate and repair as necessary.
The main water service pipe material was galvanized steel. Based on the age of the building or apparent age of the pipe, and the low-flow condition of the water supply system, this service pipe may have significant interior corrosion and need replacing. Replacing the service pipe may significantly increase flow to the water supply pipes. A qualified plumber should evaluate and repair as necessary.




 Evidence of one or more possible abandoned underground oil tanks was found (metal supply lines, etc.). The client should determine if underground oil tank(s) exist on this property, and if tank(s) have been removed or legally decommissioned.
Evidence of one or more possible abandoned underground oil tanks was found (metal supply lines, etc.). The client should determine if underground oil tank(s) exist on this property, and if tank(s) have been removed or legally decommissioned. 
 No expansion tank was installed on this structure's water supply system. Expansion tanks are recommended when a property is on a public water supply system and the property's water system is "closed" via a pressure reducing valve (PRV), check valve, or backflow preventer. No room for expansion of water exists in this type of system. Thermal expansion occurs when water is heated during non-use periods. In a closed system with no provision for expansion, its effects may include:
No expansion tank was installed on this structure's water supply system. Expansion tanks are recommended when a property is on a public water supply system and the property's water system is "closed" via a pressure reducing valve (PRV), check valve, or backflow preventer. No room for expansion of water exists in this type of system. Thermal expansion occurs when water is heated during non-use periods. In a closed system with no provision for expansion, its effects may include:

 Culligan Reverse Osmosis System installed. Change all filter elements and test membrane for water quality. Replace as needed.
Culligan Reverse Osmosis System installed. Change all filter elements and test membrane for water quality. Replace as needed.


 Water supply pipes were noted in the 3rd floor attic space. Monitor this area and maintain temperatures to prevent freezing conditions and damage to the pipes.
Water supply pipes were noted in the 3rd floor attic space. Monitor this area and maintain temperatures to prevent freezing conditions and damage to the pipes.


 The client should be aware that they are responsible for repairs to the side sewer line, and usually for the publicly owned lateral line. Recommend having a qualified plumber inspect the waste lines using a video scope device to determine if they need repair or replacement. Note that repairs are often expensive due to the need for excavation.
The client should be aware that they are responsible for repairs to the side sewer line, and usually for the publicly owned lateral line. Recommend having a qualified plumber inspect the waste lines using a video scope device to determine if they need repair or replacement. Note that repairs are often expensive due to the need for excavation.

 An landscape irrigation system is installed. Damaged components noted. Recommend full evaluation of the system for integrity and functionality by a qualified irrigation specialist. The system must be purged of water in the fall before freezing conditions exist to prevent damage to the components.
An landscape irrigation system is installed. Damaged components noted. Recommend full evaluation of the system for integrity and functionality by a qualified irrigation specialist. The system must be purged of water in the fall before freezing conditions exist to prevent damage to the components.





 No temperature-pressure relief valve was installed on the water heater tank. This is a potential safety hazard due to the risk of explosion. A qualified plumber should install a temperature-pressure relief valve and drain line as per standard building practices.
No temperature-pressure relief valve was installed on the water heater tank. This is a potential safety hazard due to the risk of explosion. A qualified plumber should install a temperature-pressure relief valve and drain line as per standard building practices.



 The last service date of this system appeared to be more than one year ago. A qualified heating contractor should inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas, this servicing should be performed annually in the future. For more information visit:
The last service date of this system appeared to be more than one year ago. A qualified heating contractor should inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas, this servicing should be performed annually in the future. For more information visit:

 A water heater was installed over finished living spaces and had no catch pan and drain installed. Recommend having a qualified contractor install a catch pan and drain to prevent water damage to finished interior spaces below if/when the water heater develops a leak or is drained.
A water heater was installed over finished living spaces and had no catch pan and drain installed. Recommend having a qualified contractor install a catch pan and drain to prevent water damage to finished interior spaces below if/when the water heater develops a leak or is drained.
 Screws were missing from one or more single wall flue pipe joints in the venting system. Standard building practices require that three screws be installed at each joint, and at the flue collar and chimney ends. A qualified person should repair as necessary.
Screws were missing from one or more single wall flue pipe joints in the venting system. Standard building practices require that three screws be installed at each joint, and at the flue collar and chimney ends. A qualified person should repair as necessary.

 The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be beyond this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future.
The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be beyond this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future.





 The last service date of this system appeared to be more than one year ago. A qualified heating contractor should inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas, this servicing should be performed annually in the future. For more information visit:
The last service date of this system appeared to be more than one year ago. A qualified heating contractor should inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas, this servicing should be performed annually in the future. For more information visit:

 Hydronic zone was installed. This system was disconnected. Further evaluate for purpose.
Hydronic zone was installed. This system was disconnected. Further evaluate for purpose.







 The following conditions were noted with the steam boiler: heavy sediment in water. A qualified contractor should evaluate and repair as necessary.
The following conditions were noted with the steam boiler: heavy sediment in water. A qualified contractor should evaluate and repair as necessary.


 The low water cut-off switch was installed . This switch should turn off the burner when the water is too low and activate the automatic feeder control. A qualified contractor should evaluate and repair as necessary.
The low water cut-off switch was installed . This switch should turn off the burner when the water is too low and activate the automatic feeder control. A qualified contractor should evaluate and repair as necessary.



 The high pressure limit switch was installed . This switch should turn off the burner when the boiler pressure exceeds a preset level, usually 5 to 7 psi. A qualified contractor should evaluate and repair as necessary.
The high pressure limit switch was installed . This switch should turn off the burner when the boiler pressure exceeds a preset level, usually 5 to 7 psi. A qualified contractor should evaluate and repair as necessary.


 The estimated useful life for most cast iron boilers is 30 years.
The estimated useful life for most cast iron boilers is 30 years.


 The air filters were located so that they're difficult to access. Recommend relocating filters as necessary to more accessible locations, such as behind return air grills in interior living spaces.
The air filters were located so that they're difficult to access. Recommend relocating filters as necessary to more accessible locations, such as behind return air grills in interior living spaces.



 The last service date of this system appeared to be more than one year ago. A qualified contractor should service this system and make repairs as necessary. This servicing should be performed annually in the future.
The last service date of this system appeared to be more than one year ago. A qualified contractor should service this system and make repairs as necessary. This servicing should be performed annually in the future.
 Little Giant condensate pump installed. Service and clean annually or as needed.
Little Giant condensate pump installed. Service and clean annually or as needed.



 The estimated useful life for most cooling systems and heat pumps is 10 to 15 years. This system appears to be at this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
The estimated useful life for most cooling systems and heat pumps is 10 to 15 years. This system appears to be at this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.

 The last service date of this system appeared to be more than one year ago. A qualified contractor should service this system and make repairs as necessary. This servicing should be performed annually in the future.
The last service date of this system appeared to be more than one year ago. A qualified contractor should service this system and make repairs as necessary. This servicing should be performed annually in the future.

 The estimated useful life for most cooling systems and heat pumps is 10 to 15 years. This system appears to be at this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
The estimated useful life for most cooling systems and heat pumps is 10 to 15 years. This system appears to be at this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.



 No metal liner was installed in the masonry chimney at location #B, and one or more gas appliances use the chimney for a flue. Standard building practices require that a metal liner be installed in masonry chimneys used to vent gas appliances such as furnaces and water heaters. The purpose of the metal liner is to ensure a correct draft, and to prevent damage to the masonry flue from corrosive exhaust deposits and moisture in the exhaust gases. A qualified chimney service contractor should evaluate and install a metal liner as necessary. For more information search for "gas liner" at:
No metal liner was installed in the masonry chimney at location #B, and one or more gas appliances use the chimney for a flue. Standard building practices require that a metal liner be installed in masonry chimneys used to vent gas appliances such as furnaces and water heaters. The purpose of the metal liner is to ensure a correct draft, and to prevent damage to the masonry flue from corrosive exhaust deposits and moisture in the exhaust gases. A qualified chimney service contractor should evaluate and install a metal liner as necessary. For more information search for "gas liner" at:

 The hearth at location #A was deteriorated with missing and/or cracked grout. A qualified person should evaluate and repair as necessary.
The hearth at location #A was deteriorated with missing and/or cracked grout. A qualified person should evaluate and repair as necessary.



 The glass doors at location #A were difficult to operate. A qualified person should repair or replace as necessary.
The glass doors at location #A were difficult to operate. A qualified person should repair or replace as necessary.



 Recommend NFPA 211 (Level II Internal Chimney Inspection). Recommend evaluation by qualified licensed chimney specialist with optical equipment to verify integrity and functionality of flue liner and chimney system. Interior flue liner not completely accessible for visual inspection.
Recommend NFPA 211 (Level II Internal Chimney Inspection). Recommend evaluation by qualified licensed chimney specialist with optical equipment to verify integrity and functionality of flue liner and chimney system. Interior flue liner not completely accessible for visual inspection.



 The garbage disposal was significantly corroded. A qualified plumber or contractor should evaluate and repair or replace the food disposal as necessary.
The garbage disposal was significantly corroded. A qualified plumber or contractor should evaluate and repair or replace the food disposal as necessary.




 1 cooktop burner was inoperable. A qualified person should evaluate and repair as necessary.
1 cooktop burner was inoperable. A qualified person should evaluate and repair as necessary.


 Wine cooler.
Wine cooler.


 Leaking or dripping was found at the sink spout at location #F. A qualified plumber should evaluate and repair as necessary.
Leaking or dripping was found at the sink spout at location #F. A qualified plumber should evaluate and repair as necessary.

 The exhaust fans at locations #C and #D were noisy or vibrated excessively. Moisture may accumulate as a result. A qualified person should evaluate and repair or replace as necessary.
The exhaust fans at locations #C and #D were noisy or vibrated excessively. Moisture may accumulate as a result. A qualified person should evaluate and repair or replace as necessary.

 Moderate damage was found at the sink at location #D. The client(s) should consider replacing sinks as necessary.
Moderate damage was found at the sink at location #D. The client(s) should consider replacing sinks as necessary.

 The sink drain stopper mechanism at location #D was inoperable. A qualified person should repair or replace as necessary.
The sink drain stopper mechanism at location #D was inoperable. A qualified person should repair or replace as necessary. The bathroom at locations #A, #B and #E didn't have an exhaust fan installed. Moisture accumulation will occur and may damage the structure. Even if the bathroom has a window that opens, it likely does not provide adequate ventilation, especially during cold weather when the window is closed. A qualified contractor should install exhaust fans as per standard building practices where missing in bathrooms with showers.
The bathroom at locations #A, #B and #E didn't have an exhaust fan installed. Moisture accumulation will occur and may damage the structure. Even if the bathroom has a window that opens, it likely does not provide adequate ventilation, especially during cold weather when the window is closed. A qualified contractor should install exhaust fans as per standard building practices where missing in bathrooms with showers.
 The clothes washer supply hoses were rubber. Significant water damage may occur if these hoses fail. Recommend replacing hoses with braided, stainless steel hoses.
The clothes washer supply hoses were rubber. Significant water damage may occur if these hoses fail. Recommend replacing hoses with braided, stainless steel hoses.
 The caulk between the tub and the walls at location #C was deteriorated. A qualified person should repair as necessary.
The caulk between the tub and the walls at location #C was deteriorated. A qualified person should repair as necessary.



 The inspector was unable to verify that the glass used in one or more exterior doors was approved safety glass. Glazing that is not approved safety glass located in areas subject to human impact is a safety hazard. Standard building practices generally require that approved safety glass be used in swinging and sliding doors except where "art glass", jalousie windows or glazing smaller than a three inch opening are used. A qualified contractor should evaluate and replace glass if necessary, and as per standard building practices.
The inspector was unable to verify that the glass used in one or more exterior doors was approved safety glass. Glazing that is not approved safety glass located in areas subject to human impact is a safety hazard. Standard building practices generally require that approved safety glass be used in swinging and sliding doors except where "art glass", jalousie windows or glazing smaller than a three inch opening are used. A qualified contractor should evaluate and replace glass if necessary, and as per standard building practices.

 The inspector was unable to verify that the glass used in one or more interior doors was approved safety glass. Glazing that is not approved safety glass located in areas subject to human impact is a safety hazard. Standard building practices generally require that approved safety glass be used in swinging and sliding doors except where "art glass", jalousie windows or glazing smaller than a three inch opening are used. A qualified contractor should evaluate and replace glass if necessary, and as per standard building practices:
The inspector was unable to verify that the glass used in one or more interior doors was approved safety glass. Glazing that is not approved safety glass located in areas subject to human impact is a safety hazard. Standard building practices generally require that approved safety glass be used in swinging and sliding doors except where "art glass", jalousie windows or glazing smaller than a three inch opening are used. A qualified contractor should evaluate and replace glass if necessary, and as per standard building practices:
 One or more exterior doors had double-cylinder deadbolts installed, where a key is required to open them from the inside. This can be a safety hazard in the event of a fire because egress may be obstructed or delayed. Recommend replacing double-cylinder deadbolts with single-cylinder deadbolts where a handle is installed on the interior side:
One or more exterior doors had double-cylinder deadbolts installed, where a key is required to open them from the inside. This can be a safety hazard in the event of a fire because egress may be obstructed or delayed. Recommend replacing double-cylinder deadbolts with single-cylinder deadbolts where a handle is installed on the interior side:

 Some windows that were built to open wouldn't open. A qualified person should evaluate and repair as necessary:
Some windows that were built to open wouldn't open. A qualified person should evaluate and repair as necessary:

 Seals between multi-pane glass in some windows appear to have failed based on condensation or stains between the panes of glass. The view through the window may be obscured, and accumulated condensation leaking into wall cavities is a conducive condition for wood destroying organisms. A qualified contractor should evaluate and replace glass where necessary.
Seals between multi-pane glass in some windows appear to have failed based on condensation or stains between the panes of glass. The view through the window may be obscured, and accumulated condensation leaking into wall cavities is a conducive condition for wood destroying organisms. A qualified contractor should evaluate and replace glass where necessary.
 Some interior doors were sticking. A qualified person should evaluate and repair as necessary.
Some interior doors were sticking. A qualified person should evaluate and repair as necessary.
 Glass in one or more windows was cracked, broken and/or missing. A qualified contractor should replace glass where necessary:
Glass in one or more windows was cracked, broken and/or missing. A qualified contractor should replace glass where necessary:
 Some window screens were damaged. A qualified person should repair or replace as necessary:
Some window screens were damaged. A qualified person should repair or replace as necessary: Lock mechanisms on some windows were damaged. A qualified person should repair as necessary:
Lock mechanisms on some windows were damaged. A qualified person should repair as necessary: Some window screens were missing:
Some window screens were missing: Minor cracks and/or holes were found in walls in one or more areas. They do not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons.
Minor cracks and/or holes were found in walls in one or more areas. They do not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons.
 Minor cracks and/or holes were found in ceilings in one or more areas. They do not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons.
Minor cracks and/or holes were found in ceilings in one or more areas. They do not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons.
 Many windows used single-pane glass. Single-pane windows are one of the largest sources of heat loss in winter and heat gain in the summer due to their low insulating ability and high air leakage rates. They're estimated to be responsible for 25 to 50 percent of the energy used to heat and cool homes. The client should consider replacing single-pane windows with new, multi-pane windows.
Many windows used single-pane glass. Single-pane windows are one of the largest sources of heat loss in winter and heat gain in the summer due to their low insulating ability and high air leakage rates. They're estimated to be responsible for 25 to 50 percent of the energy used to heat and cool homes. The client should consider replacing single-pane windows with new, multi-pane windows.