Grounds
2) 

An insect nest was observed in the front softening. Recommended for the revaluation and removal as needed.
4) 

A damage light fixture was observed on the north side of the home. Recommend hiring a qualified contractor to repair over place as needed
5) 

An area of vinyl siding was observed to be loose on the north side of the home. Recommend having a qualified contractor reinstall or replace as needed as this can cause active water infiltration in the home.
6) 
One or more gates were difficult to latch and need repair.
Chain link gates on both sides of the main home were observed to be difficult to open with the latches. Recommend hiring a certified contractor to repair or replace as needed.
7) 

Wooden deck or porch surfaces were overdue for normal maintenance. Recommend that a qualified person clean and preserve as necessary. Where decks have been coated with a finish such as opaque stains or paint, it may be too difficult to strip the finish and apply anything but paint or opaque stain. Where transparent stain or penetrating oil has been applied in the past, recommend that a penetrating oil be used. For more information, visit:
http://www.google.com/search?q=penetrating+oil+deckshttp://www.google.com/search?q=deck+maintenanceTree branches were also observed to be in contact with the deck railing. Recommend hiring a qualified professional to trim branches as needed.
8) 
Significant amounts of debris, stored items and/or junk were found in the yard or around buildings.
9) 
Significant cracking was located around the sewer access cover in the sidewalk. Recommend contacting the city to determine if the maintenance and repair/ replacement falls within the city of the homeowner due to the location of the sewer.
10) 
A section of picket fencing was placed against the porch and not properly attached.This is suspected to be set in place to make the house have more curbside appeal. Recommend removal our installation as preferred.
Exterior and Foundation
15) 
Some sections of siding and/or trim were split. Recommend that a qualified person repair, replace or install siding or trim as necessary.
16) 

One or more minor cracks (1/8 inch or less) were found in the foundation. These didn't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitor them in the future. Numerous products exist to seal such cracks including hydraulic cement, non-shrinking grout, resilient caulks and epoxy sealants.
17) 
Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
18) 
Trees were in contact with or were close to the building at one or more locations. Damage to the building can occur, especially during high winds, or may have already occurred (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.
Roof
23) 

Extensions such as splash blocks or drain pipes for one or more downspouts were missing. Water can accumulate around the building foundation or inside crawl spaces or basements as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure.
Although some splash blocks are in ues, the Inspector recommends the installation of downspout extensions at least 36 inches in length as most building codes require this and do not permit the use of splash blocks.
24) 
Vegetation such as trees, shrubs, and/or vines overhung the roof surface or were in contact with the roof edge. Organic debris such as leaves or needles are likely to accumulate in gutters and on the roof surface. Gutters can overflow and cause water to come in contact with the building exterior or water can accumulate around the foundation. This is a conducive condition for wood-destroying organisms. Vegetation in contact with the roof can damage the roof surface and/or the roof drainage system. Recommend pruning vegetation so as to not be in contact with the roof and to not overhang the roof surface. If vegetation is too tall then it should be pruned at least 10 feet above the roof surface.
25) 
Normally the inspector attempts to traverse roof surfaces during the inspection. However, due to safety concerns about the slippery conditions, the inspector was unable to traverse the roof and wasn't able to fully evaluate the entire roof surface.
Due to current rain at time of the inspection, the inspector was unable to completely
inspect the entire roof due to safety concerns. Any comments listed are as a courtesy from what could be seen during the limited inspection of the roof surfaces. However, the inspector did not notice any signs of leakage or problem areas and believes the roof to be in excellent serviceable condition with less than 5 years of service and used.
Electric
29) 

No arc fault circuit interrupter (AFCI) breakers were installed for bedroom circuits. These are relatively new devices, and reduce the risk of fire by protecting against overheated or arcing receptacles (outlets) or light fixtures. Consult with a qualified electrician about upgrading circuits to AFCI protection per standard building practices. For more information, visit:
http://www.google.com/search?q=arc+fault+circuit+interrupter
30) 

One or more cover plates installed outside were loose and/or damaged. This is a potential shock and/or fire hazard. Recommend that a qualified electrician repair as necessary.
Location: front porch.
31) 

One or more cover plates for switches, receptacles (outlets) or junction boxes were missing or broken. These plates are intended to contain fire and prevent electric shock from occurring due to exposed wires. Recommend that a qualified electrician repair per standard building practices.
The front porch exterior outlet cover plate was observed to be loose and the outlet was tested and found to be non-functioning.
32) 
One or more light fixtures were missing. Recommend that a qualified electrician repair or replace light fixtures as necessary.
Light fixture missing in stairwell to second floor.
33) 
The main electrical service panel was observed to be in excellent serviceable condition.
Plumbing / Fuel Systems
35) 

The sump pump appeared to be inoperable. Water may accumulate in the building substructure during periods of heavy rain. Recommend that a qualified contractor evaluate and repair or replace the sump pump as necessary.
36) 
The sump pump discharge pipe was routed so that it drained close to the foundation. Prolonged, high levels of moisture in soil can cause foundation settlement and failure. If drainage is near a crawl space or basement, water can accumulate in these spaces. Recommend that a qualified contractor repair as necessary so the discharge pipe terminates well away from the foundation and to soil that is sloping down and away from the foundation.
37) 
No battery backup system was found for the sump pump. If the power goes out during heavy rains, the sump pump won't be able to eliminate accumulated water. Consider installing a battery backup system for the sump pump.
38) 
The main water shutoff is located at the meter in the basement.
39) 
The main gas shut off is located at the gas meter on the east side of the house exterior
Heating, Ventilation and Air Condition (HVAC)
42) 

Because of the age and/or condition of the forced air furnace, recommend that a qualified HVAC contractor inspect the heat exchanger and perform a carbon monoxide test when it's serviced. Note that these tests are beyond the scope of a standard home inspection.
43) 

The estimated useful life for most heat pumps and air conditioning condensing units is 10-15 years. This unit appeared to be beyond this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
44) 

The HVAC ducts and return grills appeared to be in need of cleaning. Recommend hiring a qualified professional to clean the duct system as needed
45) 

The estimated useful life for most heat pumps and air conditioning condensing units is 10-15 years. The inspector was unable to determine the age of this unit. Be aware that it may be near, at, or beyond its useful life and may need replacing or significant repairs at any time. Recommend attempting to determine the age (ask property owner or service technician), and budgeting for a replacement if necessary.
46) 
The estimated useful life for most forced air furnaces is 15-20 years. This furnace appeared to be beyond this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
The furnace was manufactured the 11th week of year 1998. This does not reflect the install date, but units are usually installed within 1 year of manufacture.
47) 
The thermostat was observe to be in serviceable condition.