How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a safety hazard
Major DefectCorrection likely involves a significant expense
Repair/ReplaceRecommend repairing or replacing
Repair/MaintainRecommend repair and/or maintenance
Minor DefectCorrection likely involves only a minor expense
MaintainRecommend ongoing maintenance
EvaluateRecommend evaluation by a specialist
MonitorRecommend monitoring in the future
CommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Basement
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows

General InformationTable of contents
Report number: 1757
Time started: 12pm
Time finished: 4pm
Present during inspection: Client, Realtor
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain), Sunny
Temperature during inspection: Hot
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: Various
Source for main building age: Municipal records or property listing
Front of building faces: North
Main entrance faces: North
Occupied: Yes, Furniture or stored items were present
1) Repair/Replace -  Evidence of rodent activity was found in the form of feces in the attic. Consider having a qualified person make repairs to seal openings in the structure, set traps, and clean rodent waste as necessary. Recommend following guidelines in these Center for Disease Control articles:
http://www.reporthost.com/?SEALUP
http://www.reporthost.com/?TRAPUP
http://www.reporthost.com/?CLEANUP
Photo
Photo 1-1 
2) Comment -  Many areas and items at this property were obscured by furniture and/or stored items. This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Moderate slope
Condition of driveway: Required repair, replacement and/or evaluation (see comments below)
Driveway material: Asphalt
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Paving stones
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Wood
Condition of stairs, handrails and guardrails: Required repairs, replacement and/or evaluation (see comments below)
Exterior stair material: Wood
3) Safety, Repair/Replace -  Handrails at one of the flights of stairs were missing. This is a potential fall hazard. Handrails should be installed at stairs with four or more risers or where stairs are greater than 30 inches high.
Photo
Photo 3-1 
4) Safety, Repair/Maintain -  One of the treads at exterior stairs was substandard. This is a potential fall hazard.
Photo
Photo 4-1 
5) Safety, Repair/Maintain -  The self-closing and/or self-latching devices on one or more gates used with the pool fencing were missing. This is a safety hazard because these devices are intended to control access to areas with a drowning hazard. Recommend that a qualified person repair as necessary and per standard building practices.
Photo
Photo 5-1 
Photo
Photo 5-2 
6) Repair/Maintain, Comment -  The condition of the driveway was marginal. While serviceable, deterioration such as cracks, holes, settlement and/or heaving was found in the driveway. This is an indication that the driveway is in the latter half of its useful life and will need ongoing repairs and eventual replacement.
Photo
Photo 6-1 
Exterior and FoundationTable of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Wood
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Unfinished basement, Finished basement, Daylight basement
Foundation/stem wall material: Poured in place concrete, Concrete slab on grade
7) Maintain -  Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 7-1 
Photo
Photo 7-2 
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Steel
Beam material: Built-up wood
Floor structure above: Solid wood joists
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Viewed from ground with binoculars, Viewed from windows
Condition of roof surface material: Required repair, replacement and/or evaluation (see comments below)
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable
8) Major Defect, Evaluate -  The roof surface appeared to be in the later half of its useful life. However; no areas of immediate concern where observed. The customer should be aware of the approximate age of the roof and that repairs and/or replacement may be needed in the future.
Photo
Photo 8-1 
9) Maintain -  Significant amounts of debris have accumulated in one or more gutters or downspouts. Gutters can overflow and cause water to come in contact with the building exterior, or water can accumulate around the foundation. This is a conducive condition for wood-destroying organisms. Recommend cleaning gutters and downspouts now and as necessary in the future.
Photo
Photo 9-1 
10) Maintain -  Moss was growing on the roof. As a result, shingles can lift or be damaged.
Photo
Photo 10-1 
Photo
Photo 10-2 
Attic and Roof StructureTable of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Partially traversed
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass roll or batt
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Ridge vent(s), Gable end vents, Mechanical vents with powered fan
Garage or CarportTable of contents
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of door between garage and house: Appeared serviceable
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 2
Condition of automatic opener(s): Appeared serviceable
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
11) Repair/Replace, Comment -  Two areas of the concrete slab in the garage were substandard.
Photo
Photo 11-1 
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: 3
Service voltage (volts): 120-240
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 200
System ground: Ground rod(s) in soil, Cold water supply pipes
Condition of main service panel: Appeared serviceable
Condition of sub-panel(s): Appeared serviceable
Location of main service panel #A: Basement
Location of sub-panel #C: Garage
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Required repair, replacement and/or evaluation (see comments below)
Branch circuit wiring type: non-metallic sheathed, copper
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: No
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: Installed and appear to be functioning properly at this time, Installed, but one or more could not be tested
Carbon monoxide alarms installed: Yes and appeared to be working property at this time, Yes, but one or more could not be tested
12) Safety, Repair/Maintain -  Based on the age of this structure and the appearance of existing smoke alarms, the alarms may have been installed more than 10 years ago. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
https://www.reporthost.com/?SMKALRMLS
Photo
Photo 12-1 
13) Repair/Replace, Evaluate -  Two electric receptacles appeared to have no power. Recommend asking the property owner about this. Switches may need to be operated or GFCI/AFCI protection may need to be reset to make some receptacles energized. If necessary, recommend that a qualified electrician evaluate and repair.
Photo
Photo 13-1 
Photo
Photo 13-2 
Plumbing / Fuel SystemsTable of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Private well
Location of main water shut-off: Basement
Condition of supply lines: Required repair, replacement and/or evaluation (see comments below)
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic, Cast iron
Vent pipe condition: Appeared serviceable
Condition of fuel system: Required repair, replacement and/or evaluation (see comments below)
Visible fuel storage systems: Above ground
Location of main fuel shut-off valve: At propane tank, At oil tank
14) Safety, Repair/Maintain -  The propane gas supply pipes had substandard support or were loose. Gas leaks may occur as a result. Recommend that a qualified person install hangers or secure pipes per standard building practices.
Photo
Photo 14-1 
15) Repair/Maintain -  One of the copper water supply pipes had substandard support or were loose. Leaks can occur as a result. Copper supply pipes should have approved hangers every 6-8 feet. If hangers are in contact with the copper pipe, they should be made of a material that doesn't cause the pipes or hangers to corrode due to contact of dissimilar metals. Recommend that a qualified person install hangers or secure pipes per standard building practices.
Photo
Photo 15-1 
Photo
Photo 15-2 
16) Repair/Maintain -  The propane tank was leaning. It may tip or fall. Propane tanks should rest on sound and firm footing (not dirt or wood), and have additional support depending on local ordinances. Consider that a qualified contractor repair per standard building practices.
Photo
Photo 16-1 
Water HeaterTable of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Integral with heating system, with storage tank
Capacity (in gallons): 30
Temperature-pressure relief valve installed: Yes
Location of water heater: Basement
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 145
17) Safety -  The hot water temperature was greater than 120 degrees Fahrenheit. This is a safety hazard due to the risk of scalding. The thermostat should be adjusted so the water temperature doesn't exceed 120 degrees. If the water heater is powered by electricity, a qualified person should perform the adjustment, since covers that expose energized equipment normally need to be removed. For more information on scalding dangers, visit:
https://www.reporthost.com/?SCALD
Photo
Photo 17-1 
Heating, Ventilation and Air Condition (HVAC)Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Hot water
General heating distribution type(s): Ducts and registers, Pipes and radiators
Last service date of primary heat source: 2024
Source for last service date of primary heat source: Label
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Hot water
Location of forced air furnace: Attic
Location for forced air filter(s): Inside air handler
Condition of forced air ducts and registers: Appeared serviceable
Condition of hydronic or steam heat system: Appeared serviceable
Type of hydronic or steam heat: Hydronic (hot water), Circulating pump
Hydronic or steam heat fuel type: Oil
Condition of burners: Appeared serviceable
Type of combustion air supply: No dedicated source visible, uses room air
Condition of venting system: Appeared serviceable
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Type: Split system
Condition of controls: Appeared serviceable
18) Safety, Repair/Replace -  Significant amounts of debris, dirt and/or dust were visible in one or more sections of supply and/or return air ducts for the heating or cooling system. This can be a health hazard, especially for those with allergies or respiratory problems. The Environmental Protection Association (EPA) recommends considering having ducts professionally cleaned when "ducts are clogged with excessive amounts of dust and debris and/or particles are actually released into the home from your supply registers." At a minimum, the visible debris should be thoroughly cleaned. Recommend that a qualified contractor clean the ducts. For more information on duct cleaning in relation to indoor air quality, visit:
http://www.reporthost.com/?DUCTCLEAN
Photo
Photo 18-1 
Fireplaces, Stoves, Chimneys and FluesTable of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Required repair, replacement and/or evaluation (see comments below)
Wood-burning fireplace type: Masonry
Condition of gas-fired fireplaces or stoves: Appeared serviceable
Condition of chimneys and flues: Appeared serviceable
Wood-burning chimney type: Masonry
19) Safety, Repair/Replace, Evaluate -  A significant amount of creosote or burning by-products (ash, soot, etc.) was visible in one of the chimneys. This is a potential fire hazard and a sign that chimney system maintenance has been deferred. The client should be aware that the type and quality of wood burned, and the moisture content of the wood, will affect the rate at which burning by-products accumulate in the chimney. When solid fuel-burning devices are used regularly, they should be cleaned annually at a minimum. A qualified contractor should evaluate, clean, and repair if necessary.
Photo
Photo 19-1 
Photo
Photo 19-2 
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of ranges, cooktops and/or ovens: Appeared serviceable
Range, cooktop, oven type: Propane, Electric
Type of ventilation: Down draft exhaust
Condition of refrigerator: Appeared serviceable
20) Repair/Replace -  The cooktop exhaust fan was noisy or vibrated excessively when the highest setting was selected. Consider that a qualified person repair or replace as necessary.
Photo
Photo 20-1 
21) Repair/Replace -  The refrigerator's water dispenser was inoperable. Recommend that a qualified person repair as necessary.
Photo
Photo 21-1 
Bathrooms, Laundry and SinksTable of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Half bath, first floor
Location #B: Full bath, Master bath, second floor
Location #C: 3/4 bath, second floor
Location #D: Full bath, second floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Required repair, replacement and/or evaluation (see comments below)
Bathroom and laundry ventilation type: Windows, Central exhaust fan, with individual ducts
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes
22) Repair/Replace -  The exhaust fan at location(s) #C was noisy. Moisture may accumulate and result in mold, bacteria or fungal growth.
Photo
Photo 22-1 
23) Repair/Replace -  The bathroom with a shower or bathtub at location(s) #D didn't have an exhaust fan installed. Moisture can accumulate and result in mold, bacteria or fungal growth. Even if the bathroom has a window that opens, it may not provide adequate ventilation, especially during cold weather when windows are closed or when wind blows air into the bathroom. Recommend that a qualified contractor install exhaust fans per standard building practices where missing in bathrooms with showers or bathtubs.
Photo
Photo 23-1 
24) Repair/Replace -  No catch pan or drain was installed at the clothes washing machine location, and a finished space was located below. Catch pans and drains prevent water damage to finished interior spaces below if or when the washing machine leaks, overflows or is drained. If concerned, consult with a qualified contractor about installing a catch pan. Note that installing a drain line for a catch pan routed to the outdoors may not be feasible. As an alternative, a water alarm can be installed in the catch pan. For more information visit:
http://www.reporthost.com/?WTRALRM
Photo
Photo 24-1 
Interior, Doors and WindowsTable of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Required repair, replacement and/or evaluation (see comments below)
Exterior door material: Wood
Condition of interior doors: Required repair, replacement and/or evaluation (see comments below)
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Wood, Single-pane
Condition of walls and ceilings: Required repairs, replacement and/or evaluation (see comments below)
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Required repairs, replacement and/or evaluation (see comments below)
Flooring type or covering: Wood or wood products, Tile
Condition of stairs, handrails and guardrails: Appeared serviceable
25) Repair/Replace -  The basement entry door wouldn't latch when closed. This is a security concern if no deadbolt is installed. A qualified person should repair as necessary.
Photo
Photo 25-1 
26) Repair/Maintain -  Wood flooring in some areas was worn. Consider that a qualified contractor refinish wood flooring as necessary.
Photo
Photo 26-1 
27) Repair/Maintain -  One or more bifold doors were off their track(s) or difficult to operate. Recommend that a qualified person repair as necessary.
Photo
Photo 27-1 
Photo
Photo 27-2 
28) Minor Defect -  Minor cracks, nail pops and/or blemishes were found in walls and/or ceilings in one or more areas. Cracks and nail pops are common, are often caused by lumber shrinkage or minor settlement, and can be more or less noticeable depending on changes in humidity. They did not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons. For recurring cracks, consider using an elastic crack covering product:
https://www.reporthost.com/?ECC
Photo
Photo 28-1 
Photo
Photo 28-2 
29) Monitor -  Stains were found in one or more ceiling areas. However, no elevated levels of moisture were found.
Photo
Photo 29-1 
30) Comment -  Some windows that were designed to open and close were difficult to open and close.
Photo
Photo 30-1 
31) Comment -  Glass in one of the windows was cracked.
Photo
Photo 31-1 
Photo
Photo 31-2 
32) Comment -  Floors in one of the areas were not level.
Photo
Photo 32-1