Property Inspection Report

Client(s):  Ramiro Gonsalez Alvarado
Property address:  6213 Santa Fe Ave
Huntington Park CA 90255
Inspection date:  Sunday, March 15, 2020

This report published on Saturday, April 25, 2020 7:22:05 PM PDT

Thank you for allowing Inspection Pro to inspect your new home. Please read the report in it's entirety and feel free to contact us should you have any questions. Bill Abalos - Inspector / Appraiser - 626-374-1076 - billabalos@ymail.com

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Repair/ReplaceRecommend repairing or replacing

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

Summary
General Information
Exterior
Roof & Attic
Garage
Electrical / Solar Panels
Plumbing
Heating & Air Conditioning
Fireplaces
INTERIORS
Front Unit
Rear Unit
Foundation

View summary

Property Address: 6213 Santa Fe Ave Huntington Park CA 90255 Inspection date: Sunday, March 15, 2020 @ 1 pm
1) Repair/Replace - The following items were observed and will require repair to correct an existing condition:

EXTERIOR:
1- Several roof vent screens are either missing or torn. Recommend to repair or install as needed to prevent mice or birds from entering into the attic.
2-The crawl space screen is missing on the south side of the front unit.
3- Recommend to install covers over the outside outlets at the front unit porch right side and also outside of the garage side door.
4- Recommend to patch the stucco holes where needed and also replace the cracked floor tiles at the rear porch of the front unit.

ROOF:
1-Roof metal flashing is loose at the rear side of the garage.
2-The roof is a mix of some new and older materials. Recommend to either apply 2 coats of a clear roof sealant or contact a roofer for further review.

GARAGE:
1- Recommend to cover the exposed wires inside the electrical boxes in the rear garage and also above the side door of the detached garage.
2- There was no electrical service for the garage behind the 2nd unit.

ELECTRICAL:
1-The electricity to the rear unit was off at the time of inspection. Could not test the light switches, outlets, fans, or wall heater.

PLUMBING:
1-Mice droppings were observed on the water heaters. May need to have a pest inspection performed.
2- Recommend to replace the faucets in the kitchen and bathrooms to improve the inside water pressure.

HVAC:
1-Could not test the wall heater in the rear unit as the electricity was turned off at the time of inspection. Recommend to contact the gas company to test when power is turned on within the rear unit.

FRONT UNIT:
1-Improper wiring observed in the front bedroom closet, the hallway closet, and in the 1/4 bathroom near the kitchen area. Wires should be within conduit to prevent any electrical shock.
2-The rear bedroom window is missing a screen. Additionally, the closet door is missing, and the outlet below the window is missing a cover.
3-All bedrooms are missing smoke detectors.
4-The bathroom fan exhaust wont turn on and is missing a cover. Recommend replacement for proper ventilation.
5-Recommend to re caulk around the counter top in the kitchen area as the caulking is worn out and can lead to water trailing into the back side of the cabinet.
6-The middle bedroom window is cracked and needs replacement.
7- The kitchen vent for the front unit does not properly vent to the exterior. It is currently venting into the attic. Recommend to install an elbow vent to the exterior for proper ventilation.

REAR UNIT:
1-The electricity was off at the time of inspection.
2-Exposed wiring in the rear bedroom. Recommend to remove or cover up to prevent any electrical shorts or electrical shock.
3-The rear bedroom window is missing a screen.
4-Both side of the kitchen sink are leaking from the drain and sink base connection. Recommend to replace the washers as they are worn out and seal accordingly.
5-Both bedrooms are missing smoke detectors and one in the living room area.
6-The bathroom window is painted over and cannot properly be locked.
7-Common settlement cracks observed on the ceiling in the living room area. No signs of significant damage regarding the foundation.
8-Water stain observed on the ceiling in the front bedroom. Recommend to contact a roofer for a further evaluation.
9-The drainage for the tub is slow. Recommend to clean the drain with a drain cleaning solution or contact a plumber for rooter service.

CRAWL SPACE:
1-Termite activity was observed at the opening for both crawl space vents for both units. Recommend to have a termite inspection performed.
Photo
Photo 1-1 
Photo
Photo 1-2 
Photo
Photo 1-3 
Photo
Photo 1-4 
Photo
Photo 1-5 
Photo
Photo 1-6 
Photo
Photo 1-7 
Photo
Photo 1-8 
Photo
Photo 1-9 
Photo
Photo 1-10 
Photo
Photo 1-11 
Photo
Photo 1-12 
Photo
Photo 1-13 
Photo
Photo 1-14 
Photo
Photo 1-15 
Photo
Photo 1-16 
General Information
Table of contents
Report number: IP395
Weather conditions during inspection: Cool
Inspection fee: 375.00
Type of building: Duplex
Front of building faces: East
Utilities on for inspection?: Yes
2) - The subject property is two units. The front unit is composed of three bedrooms and 1 bathroom. The rear unit is composed of 2 bedrooms and one bathroom. The roof is composition shingles, copper and galvanized plumbing pipes, sliding windows, stucco exterior and the units are on a raised foundation.

The main components such as the roof, plumbing, electrical, foundation and structure were all inspected as well as the other components that make up the property and it's functionality.

Any issues observed will be discussed in the various sections of the report and any items requiring repair, immediate attention or further inspection by a licensed professional will also be identified.
Wall exterior covering: Stucco
Apparent wall structure: Wood frame
Doors: Wood
Windows: Dual Pane Sliders
Foundation Type: Raised
Wood trim condition: Appeared Serviceable
Grounds: Maintained
Driveway: Concrete
3) - The exterior was inspected and found to be in average condition with normal wear and use. The grounds have been generally maintained, the windows and doors were in working condition.

However, the following items were observed: See pictures.
1- Several roof vent screens are either missing or torn. Recommend to repair or install as needed to prevent mice or birds from entering into the attic.
2-The crawl space screen is missing on the south side of the front unit.
3- Recommend to install covers over the outside outlets at the front unit porch right side and also outside of the garage side door.
4- Recommend to patch the stucco holes where needed and also replace the cracked floor tiles at the rear porch of the front unit.

The inspection consisted of the following: Overall condition, foundation, walls, trim, windows, doors, grounds, driveway, exterior lighting, electrical connections, gutters, porches and patios.
Photo
Photo 3-1 
Photo
Photo 3-2 
Photo
Photo 3-3 
Photo
Photo 3-4 
Photo
Photo 3-5 
Photo
Photo 3-6 
Photo
Photo 3-7 
Photo
Photo 3-8 
Photo
Photo 3-9 
Photo
Photo 3-10 
Photo
Photo 3-11 
Photo
Photo 3-12 
Photo
Photo 3-13 
Photo
Photo 3-14 
Photo
Photo 3-15 
Photo
Photo 3-16 
Photo
Photo 3-17 
Photo
Photo 3-18 
Photo
Photo 3-19 
Photo
Photo 3-20 
Photo
Photo 3-21 
Roof & Attic
Table of contents
Roof inspection method: Walked on
Condition of roof surface material: Normal wear and use
Roof surface material: Composition Shingles
Condition of exposed flashings: Appeared serviceable
Attic Condition: Appeared Serviceable
Insulation Type: Loose fill - Blown in
4) - The roof and attic was inspected and found the following was observed: The shingles were in average condition with normal wear and use. The roof underside was also inspected inside the attic and found to have normal wear and use. The structural components were intact, the ventilation was sufficient and neither unit had insulation in the attic.

However, the following items were observed: See pictures.
1-Roof metal flashing is loose at the rear side of the garage.
2-The roof is a mix of some new and older materials. Recommend to either apply 2 coats of a clear roof sealant or contact a roofer for further review.

The inspection consisted of the roof-covering, underside, trim, fascia boards, flashing, roof underside, vents and framing, quality of construction, electrical, ventilation, insulation and accessibility.

NOTE: Home inspectors are not licensed roofing contractors and as such, only report on what is observable at the time of the inspection. We cannot determine the age of water stains or determine the remaining service life of the roof covering.
Photo
Photo 4-1 
Photo
Photo 4-2 
Photo
Photo 4-3 
Photo
Photo 4-4 
Photo
Photo 4-5 
Photo
Photo 4-6 
Photo
Photo 4-7 
Photo
Photo 4-8 
Photo
Photo 4-9 
Photo
Photo 4-10 
Photo
Photo 4-11 
Photo
Photo 4-12 
Photo
Photo 4-13 
Photo
Photo 4-14 
Photo
Photo 4-15 
Photo
Photo 4-16 
Photo
Photo 4-17 
Photo
Photo 4-18 
Photo
Photo 4-19 
Photo
Photo 4-20 
Photo
Photo 4-21 
5) - The garage was inspected and found to have normal conditions. The walls, ceiling and flooring have been maintained.

However, the following items were observed: See pictures.
1- Recommend to cover the exposed wires inside the electrical boxes in the rear garage and also above the side door of the detached garage.
2- There was no electrical service for the garage behind the 2nd unit.

The following was inspected: Ceiling, Walls, Flooring, Electrical, Automatic door opener and safety reverse sensors, doors, duct work and ventilation.
Photo
Photo 5-1 
Photo
Photo 5-2 
Photo
Photo 5-3 
Photo
Photo 5-4 
Photo
Photo 5-5 
Photo
Photo 5-6 
Electrical / Solar Panels
Table of contents
Electric System: 60 / 100 amperes
Breaker type: Standard
Condition of Breakers & Wiring: Appeared serviceable
System ground: Yes
Branch Wiring: Standard 120-240 / with main shutoff Breaker
6) - The electrical system was inspected and found to be sufficient for the size of home. The breakers and wiring inside the service panel were in good condition. The lights, outlets and switches were in working condition. The solar panels were inspected and found to be properly installed.

However, the following items were observed: See pictures.
1-The electricity to the rear unit was off at the time of inspection. Could not test the light switches, outlets, fans, or wall heater.

The following was inspected: Service drop, service panel, breakers, wire connections and sizing, bonding, grounding, neutral bus bar, interior and exterior lighting, outlets, switches and overall condition of the electrical system.

NOTE: Home inspectors are not licensed electricians and as such, only report on what is observable at the time of the inspection. We cannot determine where every outlet or light switch is connected to and/or how many outlets are connected to each other. We do not open walls to inspect the wiring.
Photo
Photo 6-1 
Photo
Photo 6-2 
Photo
Photo 6-3 
Photo
Photo 6-4 
Photo
Photo 6-5 
Water service: Public
Water pressure (psi): 40-50 psi
Location of main water shut-off: Exterior
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper & Galvanized
Condition of drainage: Leaking Pipes observed under the units
Condition of water heaters: Working Condition
7) - The plumbing system was inspected and found to be in generally good condition. The water pressure and drainage were sufficient. The water heater was in working condition and is strapped and vented.

However, the following items were observed: See pictures.
1-Mice droppings were observed on the water heaters. May need to have a pest inspection performed.
2- Recommend to replace the faucets in the kitchen and bathrooms to improve the inside water pressure.

The following was inspected. Water meter, main shut off, exterior water pressure, interior water pressure, sinks, bathtubs, showers, presence of any leaks inside and under the home, the drain lines and plumbing under the home.

Note: Home inspectors are not licensed plumbers and can only observe and report what is visible at the time of the inspection. We do not open walls to inspect the pipes.
Photo
Photo 7-1 
Photo
Photo 7-2 
Photo
Photo 7-3 
Photo
Photo 7-4 
Photo
Photo 7-5 
Photo
Photo 7-6 
Heating & Air Conditioning
Table of contents
Heating: Wall heaters / Gas pilot On at inspection-Front Unit / Off in Rear Unit
Air conditioning: Window type
8) - The wall heaters were on at the time of the inspection and as a result, were tested. It is recommended to contact the local gas company to turn on and test for operation. The wall AC's were in working condition.

However, the following items were observed: See pictures.
1-Could not test the wall heater in the rear unit as the electricity was turned off at the time of inspection. Recommend to contact the gas company to test when power is turned on within the rear unit.
Photo
Photo 8-1 
Photo
Photo 8-2 
Photo
Photo 8-3 
Photo
Photo 8-4 
Photo
Photo 8-5 
Fireplaces
Table of contents
Fireplace: Damper Door
9) - The fireplace and chimney were inspected as follows: The firebox, hearth, damper, gas connections, chimney flue, the spark screen and overall condition.

However, it is recommended to install a proper cover for the outside of the fireplace clean out. Birds or mice can enter and nest inside. See picture.
Photo
Photo 9-1 
Photo
Photo 9-2 
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood
Condition of interior doors: Appeared serviceable
Condition of windows: Appeared serviceable
Type of windows: Aluminum / Some Vinyl
Condition of walls and ceilings: Settlement cracks observed
Wall type or covering: Plaster
Ceiling type or covering: Plaster
Condition of flooring: Appeared Serviceable
Smoke & Carbon Monoxide Detectors: Installed and working
Front Unit
Table of contents
10) - The interior was inspected and found to be in average condition with normal wear and use. Common cosmetic issues were observed. The windows and doors opened and closed properly. The lights, outlets and switches were in working condition.

The following was observed:
1-Improper wiring observed in the front bedroom closet, the hallway closet, and in the 1/4 bathroom near the kitchen area. Wires should be within conduit to prevent any electrical shock.
2-The rear bedroom window is missing a screen. Additionally, the closet door is missing, and the outlet below the window is missing a cover.
3-All bedrooms are missing smoke detectors.
4-The bathroom fan exhaust wont turn on and is missing a cover. Recommend replacement for proper ventilation.
5-Recommend to re caulk around the counter top in the kitchen area as the caulking is worn out and can lead to water trailing into the back side of the cabinet.
6-The middle bedroom window is cracked and needs replacement.
7- The kitchen vent for the front unit does not properly vent to the exterior. It is currently venting into the attic. Recommend to install an elbow vent to the exterior for proper ventilation.

The inspection consisted of the following: The walls, ceilings, windows, doors, closets, and flooring, cabinets, outlets, switches and light fixtures.
Photo
Photo 10-1 
Photo
Photo 10-2 
Photo
Photo 10-3 
Photo
Photo 10-4 
Photo
Photo 10-5 
Photo
Photo 10-6 
Photo
Photo 10-7 
Photo
Photo 10-8 
Photo
Photo 10-9 
Photo
Photo 10-10 
Photo
Photo 10-11 
Photo
Photo 10-12 
Photo
Photo 10-13 
Photo
Photo 10-14 
Photo
Photo 10-15 
Photo
Photo 10-16 
Photo
Photo 10-17 
Photo
Photo 10-18 
11) - The interior was inspected and found to be in average condition with normal wear and use. Common cosmetic issues were observed. The windows and doors opened and closed properly. The lights, outlets and switches were in working condition.

The following was observed:
1-The electricity was off at the time of inspection.
2-Exposed wiring in the rear bedroom. Recommend to remove or cover up to prevent any electrical shorts or electrical shock.
3-The rear bedroom window is missing a screen.
4-Both side of the kitchen sink are leaking from the drain and sink base connection. Recommend to replace the washers as they are worn out and seal accordingly.
5-Both bedrooms are missing smoke detectors and one in the living room area.
6-The bathroom window is painted over and cannot properly be locked.
7-Common settlement cracks observed on the ceiling in the living room area. No signs of significant damage regarding the foundation.
8-Water stain observed on the ceiling in the front bedroom. Recommend to contact a roofer for a further evaluation.
9-The drainage for the tub is slow. Recommend to clean the drain with a drain cleaning solution or contact a plumber for rooter service.

The inspection consisted of the following: The walls, ceilings, windows, doors, closets, and flooring, cabinets, outlets, switches and light fixtures.
Photo
Photo 11-1 
Photo
Photo 11-2 
Photo
Photo 11-3 
Photo
Photo 11-4 
Photo
Photo 11-5 
Photo
Photo 11-6 
Photo
Photo 11-7 
Photo
Photo 11-8 
Photo
Photo 11-9 
Photo
Photo 11-10 
Photo
Photo 11-11 
Photo
Photo 11-12 
Photo
Photo 11-13 
Foundation
Table of contents
Foundation Type: Raised
Footing material: Concrete
Condition of foundation: Appeared Serviceable
Condition of support beams: Appeared serviceable
Wood framing: Appeared Serviceable
12) - The crawl space was inspected and found to have normal conditions in consideration of the home's age. The foundation walls are in stable condition as well as the support posts and sub flooring. Common house and ground settlement was observed in the units, making the floors a little uneven in some rooms.

However, the following items were observed: See pictures.
1-Termite activity was observed at the opening for both crawl space vents for both units. Recommend to have a termite inspection performed.

The following was inspected: Sub flooring, foundation, framing, supports, vapor barrier, ground, plumbing, drainage and vents.
Photo
Photo 12-1 
Photo
Photo 12-2 
Photo
Photo 12-3 
Photo
Photo 12-4 
Photo
Photo 12-5 
Photo
Photo 12-6 
Photo
Photo 12-7 
Photo
Photo 12-8 


THE SERVICES PERFORMED AND THE REPORT DELIVERED, DO NOT CONSTITUTE A WARRANTY, AN INSURANCE POLICY, OR A GUARANTEE OF ANY KIND; NOR DO THEY SUBSTITUTE FOR ANY DISCLOSURE STATEMENT AS MAY BE REQUIRED BY LAW. THIS REPORT IS FOR THE EXCLUSIVE USE OF OUR CLIENT AS NAMED IN THE REPORT.

There are no warranties made against roof leaks, wet basements, or mechanical breakdowns and Inspection Pro Home Inspections is not responsible for future failure and/or repairs.

The report may not be used or relied upon by any other person not party to the sales transaction unless that person is specifically named prior to the inspection. We are not responsible for the non-discovery of/or latent defects in material, workmanship, or other conditions of the property, which may occur or become evident after the date the services were performed; nor for any alleged non-disclosure of conditions that is the express responsibility of the seller of the property. PLEASE READ THE SELLER'S TRANSFER DISCLOSURE STATEMENT THOROUGHLY.

Inspection Pro Home Inspections does not assume risk for conditions, which are concealed from view or inaccessible to us at the time that the services were performed. Distribution of this report to any third party not involved in the sale transaction without the written consent of Inspection Pro Home Inspections is prohibited. As the client, you agree to maintain the confidentiality of this report and to reasonably protect the report from distribution to any uninvolved third party. You agree to indemnify, defend and hold Inspection Pro Home Inspections harmless if any third party brings a claim against us relating to the inspection or to this report.

SCOPE OF WORK
This report is prepared and written based on a physical inspection of the structure and the availability of access to the mechanical components of the property. Complete access to the property must be given to the inspector and the utilities should be on to ensure a thorough inspection.