Property Inspection Report

Client(s):  Jim Doe
Property address:  Anywhere, NY
Inspection date:  Monday, September 13, 2021

This report published on Monday, September 13, 2021 1:48:39 PM EDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a safety hazard
Repair/ReplaceRecommend repairing or replacing
Repair/MaintainRecommend repair and/or maintenance
MaintainRecommend ongoing maintenance
EvaluateRecommend evaluation by a specialist
MonitorRecommend monitoring in the future
CommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Crawl Space
Basement
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings

View summary

General Information
Table of contents
Time started: 10:00am
Present during inspection: Client, Realtor
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Warm
Type of building: Single family
Buildings inspected: One house, One detached garage
Age of main building: 72 years
Source for main building age: Municipal records or property listing
Main entrance faces: Southwest
Occupied: No
1) Safety, Comment - Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
http://www.reporthost.com/?EPA
http://www.reporthost.com/?CPSC
http://www.reporthost.com/?CDC
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Moderate slope
Condition of driveway: Appeared serviceable
Driveway material: Gravel
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Gravel
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
Condition of stairs, handrails and guardrails: Required repairs, replacement and/or evaluation (see comments below)
Exterior stair material: Concrete
2) Safety, Repair/Replace - Handrails at the flight of stairs leading to the main entrance were missing. This is a potential fall hazard. Recommend that a qualified contractor install handrails where missing and per standard building practices.
Photo
Photo 2-1 
3) Repair/Maintain - The gravel walkway showed signs of erosion near the patio area of the home. Recommend that a qualified person repair as necessary to prevent further erosion and undermining.
Photo
Photo 3-1 
Photo
Photo 3-2 
Exterior and Foundation
Table of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Wood
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Crawl space, Unfinished basement
Foundation/stem wall material: Concrete block
4) Maintain - Trees were in contact with or were close to the building at one or more locations. Damage to the building can occur, especially during high winds. Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.
Photo
Photo 4-1 
Photo
Photo 4-2 
Crawl Space
Table of contents
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Traversed
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Concrete block, Steel
Beam material: Built-up wood
Floor structure above: Wood joists
Condition of insulation underneath floor above: Appeared serviceable
Insulation material underneath floor above: Spray foam
Condition of vapor barrier: Appeared serviceable
5) Repair/Maintain - One or more joists were spliced with "sistered" lumber, and no support post was installed below. Sistering is a common repair practice where additional pieces of lumber are attached to spliced pieces. Such repairs result in a component that's weaker than the original joist and should be reinforced with a support post below. Recommend that a qualified contractor repair per standard building practices. For example, by installing support posts below.
Photo
Photo 5-1 
Photo
Photo 5-2 
6) Maintain, Comment - One or more crawl space vents were intentionally blocked/closed. This restricts ventilation in the crawl space and can result in increased levels of moisture inside. Such vents should be left open at all times except during freezing cold weather. Recommend opening vents as necessary.
Photo
Photo 6-1 
Photo
Photo 6-2 
Photo
Photo 6-3 
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Metal
7) Safety, Repair/Replace - Handrails were missing on the flight of stairs leading to the basement. This is a potential fall hazard. Recommend that a qualified contractor install handrails where missing and per standard building practices.
Photo
Photo 7-1 
8) Monitor - Evidence of prior water intrusion or high levels of moisture were found in one or more sections of the basement. For example, water stains or efflorescence on the foundation, etc. Recommend reviewing any disclosure statements available and ask the property owner about past accumulation of water in the basement. The basement should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, then recommend that a qualified contractor who specializes in drainage issues evaluate and repair as necessary. Typical repairs for preventing water from accumulating in basements include:
  • Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
  • Improving perimeter grading
  • Repairing, installing or improving underground footing and/or curtain drains
Ideally, water should not enter basements, but if water must be controlled after it enters the basement, then typical repairs include installing a sump pump.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Viewed from ground, Viewed from windows
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable
9) Repair/Maintain - Observed tree limbs overhanging the roof of the home and garage in areas. This can result in damage to roof in the event of severe weather. Recommend trimming or removal of tree limbs overhanging the roof by a qualified contractor.
Photo
Photo 9-1 
Photo
Photo 9-2 
Photo
Photo 9-3 
Photo
Photo 9-4 
Attic and Roof Structure
Table of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch(es)
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Spray polyurethane foam
Vermiculite insulation present: None visible
10) Safety, Repair/Replace - The attic access hatch was located or configured so that it posed a safety hazard for falling when attempting to enter the attic. Also, the attic access hatch was too small to allow easy access. Such hatches should be at least 22 x 30 inches in size, and in safely accessed areas. Recommend that a qualified person modify attic access points per standard building practices.
11) Comment - Attic observed.
Photo
Photo 11-1 
Photo
Photo 11-2 
Photo
Photo 11-3 
Photo
Photo 11-4 
Photo
Photo 11-5 
Photo
Photo 11-6 
Photo
Photo 11-7 
Garage or Carport
Table of contents
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Detached
Condition of garage vehicle door(s): Appeared serviceable
Number of vehicle doors: 1
Condition of automatic opener(s): Appeared serviceable
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: None visible
12) Repair/Maintain - Soil was in close proximity to the wood exterior of the garage. This is a conducive condition for fungal rot of wood. Recommend grading soil to prevent contact with wood by a qualified contractor.
Photo
Photo 12-1 
Photo
Photo 12-2 
13) Comment - Garage observed
Photo
Photo 13-1 
Photo
Photo 13-2 
Photo
Photo 13-3 
Photo
Photo 13-4 
Photo
Photo 13-5 
Photo
Photo 13-6 
Photo
Photo 13-7 
Photo
Photo 13-8 
Photo
Photo 13-9 
Photo
Photo 13-10 
Photo
Photo 13-11 
Photo
Photo 13-12 
Photo
Photo 13-13 
Photo
Photo 13-14 
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Primary service type: Overhead
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 200
System ground: Ground rod(s) in soil
Condition of main service panel: Appeared serviceable
Condition of sub-panel(s): Required repair, replacement and/or evaluation (see comments below)
Location of main service panel #A: First floor
Location of main service panel #B: Garage
Location of main disconnect: Breaker at bottom of main service panel
Branch circuit wiring type: non-metallic sheathed
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: Yes
Smoke alarms installed: Yes, but not tested
14) Safety, Repair/Replace, Evaluate - The electric receptacle at the laundry area had no visible ground fault circuit interrupter (GFCI) protection. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices.
For more information, visit:
http://www.reporthost.com/?GFCI
Photo
Photo 14-1 
Photo
Photo 14-2 
15) Safety, Repair/Maintain - No permanently installed carbon monoxide alarms were found. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed for new construction and/or for homes being sold. Recommend installing approved CO alarms outside of each separate sleeping area in the immediate vicinity of the bedrooms on each level and in accordance with the manufacturer's recommendations. For more information, visit:
http://www.reporthost.com/?COALRM
16) Evaluate, Comment - The functionality of, power source for and placement of smoke alarms is not determined as part of this inspection. Smoke alarms should be installed in each bedroom, in hallways leading to bedrooms, on each level and in attached garages. They have a limited lifespan and should be replaced every 10 years. For home buyers, batteries in smoke alarms should be changed when taking occupancy. Batteries should be replaced annually in the future. Carbon monoxide alarms should be installed in the vicinity of sleeping areas and on each level. For more information, visit:
http://www.reporthost.com/?SMKALRM
http://www.reporthost.com/?COALRM
17) - Electric service observed
Photo
Photo 17-1 
Photo
Photo 17-2 
Photo
Photo 17-3 
Photo
Photo 17-4 
Photo
Photo 17-5 
Photo
Photo 17-6 
Photo
Photo 17-7 
Photo
Photo 17-8 
Plumbing / Fuel Systems
Table of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Private well
Location of main water shut-off: Basement
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper, PEX plastic
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic, Cast iron
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: None visible
Sewage ejector pump installed: None visible
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: Above ground, propane tank
Location of main fuel shut-off valve: At propane tank
18) Safety, Repair/Maintain - The pressure regulator for the gas service was too close to an opening into the building (window). Small amounts of gas can vent from regulators from time to time, so regulators should be located at least 3 feet from building openings, although this distance varies depending on the municipality. This is a potential safety hazard. Recommend that a qualified contractor repair as necessary. For example, by installing a pipe extension onto the regulator.
Photo
Photo 18-1 
Photo
Photo 18-2 
Photo
Photo 18-3 
19) Safety, Comment - Copper water supply pipes were installed. Copper pipes installed prior to the late 1980s may be joined with solder that contains lead, which is a known health hazard especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained approximately 50% lead. The client should be aware of this, especially if children will be using this water supply system. Note that the inspector does not test for toxic materials such as lead. The client should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions include:
  • Flush water taps or faucets. Do not drink water that has been sitting in the plumbing lines for more than 6 hours
  • Install appropriate filters at points of use
  • Use only cold water for cooking and drinking, as hot water dissolves lead more quickly than cold water
  • Use bottled or distilled water
  • Treat well water to make it less corrosive
  • Have a qualified plumber replace supply pipes and/or plumbing components as necessary
For more information visit:
http://www.reporthost.com/?LEADDW
http://www.reporthost.com/?LEAD
Photo
Photo 19-1 
20) Repair/Replace, Evaluate - Water was discolored when bathtubs or sinks were filled, or when showers were operated. This can be caused by water stagnating in water supply pipes, rust accumulating in pipes or in the water heater, or sediment being present in the water supply. Recommend flushing the water supply piping and the water heater. If that fails to resolve the issue, then have a qualified plumber evaluate and repair as necessary.
21) Repair/Replace, Evaluate - Low flow was found at the shower head in the master bathroom shower (bathroom #3) Water supply pipes may be clogged or corroded, filters may be clogged or need new cartridges, or fixtures may be clogged. Recommend that a qualified plumber evaluate and repair as necessary.
Photo
Photo 21-1 
Photo
Photo 21-2 
22) Maintain, Evaluate - Based on visible components or information provided to the inspector, this property appeared to have a private sewage disposal (septic) system. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Generally, septic tanks should be pumped and inspected every 3 years. Depending on the type of system and municipal regulations, inspection and maintenance may be required more frequently, often annually. Recommend the following:
  • Consult with the property owner about this system's maintenance and repair history
  • Review any documentation available for this system
  • Review inspection and maintenance requirements for this system
  • That a qualified specialist evaluate, perform maintenance and make repairs if necessary
For more information, visit:
http://www.reporthost.com/?SEPTIC
23) Evaluate, Monitor - This property was unoccupied and the plumbing system has not been in continuous operation recently. It's possible for plumbing leaks to exist but not be apparent. Leaks can be small and take time to become visible. The inspector normally operates all accessible and operable plumbing fixtures, but this limited inspection may not reveal small leaks that only become visible after constant use of the plumbing system. After taking occupancy, monitor the plumbing system for leaks that may become apparent. Areas below the house should be evaluated after plumbing has been operated to check for leaks. Any problems that are found should be repaired by a qualified plumber.
24) Evaluate - Based on visible equipment, the water supply to this property is from a private well. Private well water supplies are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. The inspector does not test private well water for contamination or pollutants, determine if the supply and/or flow are adequate, or provide an estimate for remaining life of well pumps, pressure tanks or equipment. Only visible and accessible components are evaluated. Recommend the following:
  • That a qualified well contractor fully evaluate the well, including a pump/flow test
  • That the well water be tested per the client's concerns (coliforms, pH, contaminants, etc.)
  • Research the well's history (how/when constructed, how/when maintained or repaired, past performance, past health issues)
  • Document the current well capacity and water quality for future reference
For more information, visit:
http://www.reporthost.com/?WELL
25) Evaluate - A water filtration system was installed on the premises. These are specialty systems and are excluded from this inspection. Filter cartridges typically need replacing periodically. Cleaning and other maintenance may also be needed. Recommend consulting with the property owner about this system to determine its condition, required maintenance, age, expected remaining life, etc. For more information, visit:
http://www.reporthost.com/?WTRFLTR
Photo
Photo 25-1 
Photo
Photo 25-2 
26) Evaluate - Based on observation of older caste iron waste lines exiting the home to the septic, recommend that a qualified plumber or septic inspector, inspect the waste lines using a video scope device to determine if they need repair or replacement. Note that repairs are often expensive due to the need for excavation.
Photo
Photo 26-1 
27) Comment - Gas service observed
Photo
Photo 27-1 
Photo
Photo 27-2 
Photo
Photo 27-3 
Photo
Photo 27-4 
Photo
Photo 27-5 
Photo
Photo 27-6 
Water Heater
Table of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Type: Tankless, Integral with heating system, tankless
Energy source: Propane
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 113
28) Comment - see comments on boiler for information regarding water heater
Heating, Ventilation and Air Condition (HVAC)
Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Heat pump, Boiler (hydronic baseboards)
Last service date of primary heat source: NA
Condition of hydronic or steam heat system: Appeared serviceable
Type of hydronic or steam heat: Hydronic (hot water), Wall hung boiler
Hydronic or steam heat fuel type: Propane
Condition of venting system: Appeared serviceable
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location of heat pump or air conditioning unit: Building exterior
Type: Split system, Heat pump
Condition of controls: Appeared serviceable
29) Maintain, Evaluate - The last service date of the propane gas fired boiler was unable to be determined. Recommend conversation with current homeowner regarding service records and maintenance requirements. If the boiler has not been serviced within a year, recommend that a qualified HVAC technician further evaluate, clean, and service this system. For safety reasons, and because this system is fueled by gas, this servicing should be performed annually moving forward by a qualified technician.
Photo
Photo 29-1 
Photo
Photo 29-2 
30) Comment - SFC-199 NG 95% SUPERFLOW Intergas® Dual Fired Condensing Combi Boiler observed

Brand: IBC
Model #: SFC 199
Serial #: 024994-2010504493
Input capacity: 28,300 to 125,000 BTU/hr
Photo
Photo 30-1 
Photo
Photo 30-2 
Photo
Photo 30-3 
Photo
Photo 30-4 
Photo
Photo 30-5 
31) Comment - Lennox Heat Pump/Air Conditioning Split System observed:

Outdoor model #: MLA030S4M-1P
Serial #: 340C935800113050150160
Indoor/Upstairs model #: MWMA012S4-3P
Indoor/Downstairs model #: MWMA018S4-2P
Photo
Photo 31-1 
Photo
Photo 31-2 
Photo
Photo 31-3 
Photo
Photo 31-4 
Photo
Photo 31-5 
Photo
Photo 31-6 
Photo
Photo 31-7 
Photo
Photo 31-8 
Fireplaces, Stoves, Chimneys and Flues
Table of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Required repair, replacement and/or evaluation (see comments below)
Wood-burning fireplace type: Metal
32) Safety, Repair/Maintain, Evaluate - A solid fuel-burning fireplace was found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all solid fuel-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at:
http://www.reporthost.com/?CSIA
33) Safety, Repair/Maintain - The fireplace's firebox was significantly deteriorated with corrosion and the damper was not functional. Heat from the fireplace may penetrate the firebox due to gaps and missing mortar. This is a potential fire hazard. Recommend that a qualified contractor repair as necessary.
Photo
Photo 33-1 
Photo
Photo 33-2 
Photo
Photo 33-3 
Photo
Photo 33-4 
Photo
Photo 33-5 
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: N/A (none installed)
Condition of dishwasher: Appeared serviceable
Condition of ranges, cooktops and/or ovens: Appeared serviceable
Range, cooktop, oven type: Propane
Type of ventilation: Wall or ceiling mounted fan
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: Appeared serviceable
34) Comment - Kitchen observed
Photo
Photo 34-1 
Photo
Photo 34-2 
Photo
Photo 34-3 
Photo
Photo 34-4 
Photo
Photo 34-5 
Photo
Photo 34-6 
Photo
Photo 34-7 
Photo
Photo 34-8 
Bathrooms, Laundry and Sinks
Table of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath, first floor
Location #B: Full bath, second floor, hallway
Location #C: Full bath, Master bath, second floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Windows, Spot exhaust fans
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes
35) Safety, Repair/Replace - The clothes dryer was equipped with a vinyl or mylar, accordion-type, flexible exhaust duct. The U.S. Consumer Product Safety Commission considers these types of ducts to be unsafe, and a fire hazard. They can trap lint and are susceptible to kinks or crushing, which can greatly reduce the air flow and cause overheating. Recommend that such ducts be replaced with a rigid or corrugated semi-rigid metal duct, and by a qualified contractor if necessary. For more information, visit:
http://www.reporthost.com/?DRYER
Photo
Photo 35-1 
36) Repair/Replace, Evaluate - The water supply flow for the shower in the master bathroom was low at time of inspection. Recommend that a qualified plumber evaluate and repair as necessary.
Photo
Photo 36-1 
Photo
Photo 36-2 
37) Comment - Bathrooms and laundry area observed
Photo
Photo 37-1 
Photo
Photo 37-2 
Photo
Photo 37-3 
Photo
Photo 37-4 
Photo
Photo 37-5 
Photo
Photo 37-6 
Photo
Photo 37-7 
Photo
Photo 37-8 
Photo
Photo 37-9 
Photo
Photo 37-10 
Photo
Photo 37-11 
Photo
Photo 37-12 
Photo
Photo 37-13 
Photo
Photo 37-14 
Photo
Photo 37-15 
Photo
Photo 37-16 
Interior, Doors and Windows
Table of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood, Glass panel
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Metal, Casement
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Flooring type or covering: Wood or wood products
Condition of stairs, handrails and guardrails: Appeared serviceable
38) Comment - Screens were missing from many windows. These windows may not provide ventilation during months when insects are active.
Photo
Photo 38-1 
Photo
Photo 38-2 
Wood Destroying Organism Findings
Table of contents
Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: No
Visible evidence of past wood-destroying insects: No
Visible evidence of damage by wood-destroying insects: No


Photo
Photo X-1 
Photo
Photo X-2 
Photo
Photo X-3 
Photo
Photo X-4 
Photo
Photo X-5 
Photo
Photo X-6 
Photo
Photo X-7 
Photo
Photo X-8 
Photo
Photo X-9 
Photo
Photo X-10 
Photo
Photo X-11 
Photo
Photo X-12 
Photo
Photo X-13 
Photo
Photo X-14 
Photo
Photo X-15 
Photo
Photo X-16 
Photo
Photo X-17 
Photo
Photo X-18 
Photo
Photo X-19 
Photo
Photo X-20 
Photo
Photo X-21 
Photo
Photo X-22 
Photo
Photo X-23 
Photo
Photo X-24 
Photo
Photo X-25 
Photo
Photo X-26 
Photo
Photo X-27 
Photo
Photo X-28 
Photo
Photo X-29 
Photo
Photo X-30 
Photo
Photo X-31 
Photo
Photo X-32 
Photo
Photo X-33 
Photo
Photo X-34 
Photo
Photo X-35 
Photo
Photo X-36 
Photo
Photo X-37 
Photo
Photo X-38 
Photo
Photo X-39 
Photo
Photo X-40 
Photo
Photo X-41 
Photo
Photo X-42 
Photo
Photo X-43 
Photo
Photo X-44 
Photo
Photo X-45 
Photo
Photo X-46 
Photo
Photo X-47 
Photo
Photo X-48 
Photo
Photo X-49 
Photo
Photo X-50 
Photo
Photo X-51 
Photo
Photo X-52 
Photo
Photo X-53 
Photo
Photo X-54 
Photo
Photo X-55 
Photo
Photo X-56 
Photo
Photo X-57 
Photo
Photo X-58 
Photo
Photo X-59 
Photo
Photo X-60 
Photo
Photo X-61 
Photo
Photo X-62 
Photo
Photo X-63 
Photo
Photo X-64 
Photo
Photo X-65 
Photo
Photo X-66 
Photo
Photo X-67 
Photo
Photo X-68 
Photo
Photo X-69 
Photo
Photo X-70 
Photo
Photo X-71 
Photo
Photo X-72 
Photo
Photo X-73 
Photo
Photo X-74 
Photo
Photo X-75 
Photo
Photo X-76 
Photo
Photo X-77 
Photo
Photo X-78 
Photo
Photo X-79 
Photo
Photo X-80 
Photo
Photo X-81 
Photo
Photo X-82 
Photo
Photo X-83 
Photo
Photo X-84 
Photo
Photo X-85 
Photo
Photo X-86 
Photo
Photo X-87 
Photo
Photo X-88 
Photo
Photo X-89 
Photo
Photo X-90 
Photo
Photo X-91 
Photo
Photo X-92 
Photo
Photo X-93 
Photo
Photo X-94 
Photo
Photo X-95 
Photo
Photo X-96 
Photo
Photo X-97 
Photo
Photo X-98 
Photo
Photo X-99 
Photo
Photo X-100 
Photo
Photo X-101 
Photo
Photo X-102 
Photo
Photo X-103 
Photo
Photo X-104 
Photo
Photo X-105 
Photo
Photo X-106 
Photo
Photo X-107 
Photo
Photo X-108 
Photo
Photo X-109 
Photo
Photo X-110 
Photo
Photo X-111 
Photo
Photo X-112 
Photo
Photo X-113 
Photo
Photo X-114 
Photo
Photo X-115 
Photo
Photo X-116 
Photo
Photo X-117 
Photo
Photo X-118 
Photo
Photo X-119 
Photo
Photo X-120 
Photo
Photo X-121 
Photo
Photo X-122 
Photo
Photo X-123 
Photo
Photo X-124 
Photo
Photo X-125 
Photo
Photo X-126 
Photo
Photo X-127 
Photo
Photo X-128 
Photo
Photo X-129 
Photo
Photo X-130 
Photo
Photo X-131 
Photo
Photo X-132 
Photo
Photo X-133 
Photo
Photo X-134 
Photo
Photo X-135 
Photo
Photo X-136 
Photo
Photo X-137 
Photo
Photo X-138 
Photo
Photo X-139 
Photo
Photo X-140 
Photo
Photo X-141 
Photo
Photo X-142 
Photo
Photo X-143 
Photo
Photo X-144 
Photo
Photo X-145 
Photo
Photo X-146 
Photo
Photo X-147 
Photo
Photo X-148 
Photo
Photo X-149 
Photo
Photo X-150 
Photo
Photo X-151 
Photo
Photo X-152 
Photo
Photo X-153 
Photo
Photo X-154 
Photo
Photo X-155 
Photo
Photo X-156 
Photo
Photo X-157 
Photo
Photo X-158 
Photo
Photo X-159 
Photo
Photo X-160 
Photo
Photo X-161 
Photo
Photo X-162 
Photo
Photo X-163 
Photo
Photo X-164 
Photo
Photo X-165 
Photo
Photo X-166 
Photo
Photo X-167 
Photo
Photo X-168 
Photo
Photo X-169 
Photo
Photo X-170 
Photo
Photo X-171 
Photo
Photo X-172 
Photo
Photo X-173 
Photo
Photo X-174 