This report published on Monday, April 6, 2020 10:43:32 PM PDT
This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
Safety
Poses a safety hazard
Major Defect
Correction likely involves a significant expense
Repair/Replace
Recommend repairing or replacing
Repair/Maintain
Recommend repair and/or maintenance
Maintain
Recommend ongoing maintenance
Evaluate
Recommend evaluation by a specialist
Monitor
Recommend monitoring in the future
Comment
For your information
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level, Moderate slope
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
1) The driveway sloped down towards the garage or house. This can result in water accumulating in the garage, around building foundations or underneath buildings, and is a condition conducive to attracting wood destroying organisms. Monitor these areas in the future, especially during and after periods of rain. If significant amounts of water are found to accumulate, then I recommend that a qualified paving contractor evaluate and repair as necessary. For example, by installing drain(s) or removing and installing new pavement.
2) The soil or grading sloped down towards building perimeters in some locations. This can result in water accumulating around building foundations or underneath buildings. At a minimum, monitor these areas, and areas under the structure in the future for accumulated water. If water does accumulate, I recommend grading soil so it slopes down and away from buildings with a slope of at least 1 inch per horizontal foot for a minimum 6 feet out from buildings.
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
3) The guardrail balusters (pickets) were noted with a 6" spacing. While this can be typical on homes of this age, modern building practices call for no less than 4" spacing on these balusters to inhibit the falling risk for toddlers and smaller children. Extra care should be taken whenever younger/smaller children are present.
4) The guardrail-to-house connection on the northeast corner of the deck was not completely and securely fastened to the house. This can reduce the integrity of the guardrail as well as allow moisture in between the guardrail and house exterior siding, increasing the risk of fall and lead to conditions conducive to rot and/or other wood-destroying organisms. I recommend properly and completely securing this guardrail to avoid such risks. Work to be completed by licensed general contractor or other qualified party.
5) The porch/ramp on the front entrance was noted with substandard building practices (i.e. lack of lag bolts/screws, lack of joist hangers/fasteners, wood-to-pavement contact, etc.). If the porch is to remain in place, I recommend further evaluation and necessary repairs to be completed by qualified licensed general contractor utilizing current best building practices.
6) The structural members of the rear (north-facing) deck were noted with excessive moss/biological growth. This can greatly reduce the useful lifespan of the structure and should be cleaned periodically. Work to be completed by qualified party.
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi-unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Attached garage
Type of door between garage and house: Solid core, Wood
Type of garage vehicle door: Sectional, Sliding
Number of vehicle doors: 1
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, I recommend that a professional review the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Traversed
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Hipped
Roof-attic ventilation system based on roof/exterior view: Ridge vent(s), Soffit vent(s)
Apparent number of layers of roof surface material: One
Gutter material: Aluminum
Downspout material: Aluminum
7) Significant amounts of debris have accumulated in gutters or downspouts. Gutters can overflow and cause water to come in contact with the building exterior, or water can accumulate around the foundation. This is a condition conducive to attracting wood destroying organisms. I recommend cleaning gutters and downspouts now and as necessary in the future. Work to be completed by a qualified gutter/downspout contractor.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Traversed
Roof structure type: Trusses
Ceiling structure: Ceiling joists
Ceiling insulation material: Fiberglass loose fill
Estimate of approximate insulation R value (may vary in some areas): R-49
Vermiculite insulation present: None visible
Roof-attic ventilation system(s) based on attic view: See "roof" section of report
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Primary service type: Underground
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
System grounding method: Ground electrode(s) in soil
Make of main panel(s): Westinghouse
Main disconnect rating (amps): 200
Location of main disconnect: Breaker at top of main service panel
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: Yes, but not tested
8) The functionality of, power source for, and placement of, smoke alarms was undetermined as part of this inspection. Smoke alarms should be installed in each bedroom, in hallways leading to bedrooms, and on every floor level. The devices have a limited lifespan and should be replaced every 10 years: Batteries should be changed when taking occupancy and annually in the future. In a related matter, per law, carbon monoxide alarms should be installed in close proximity to each sleeping area and on every floor level. Upon taking occupancy, or prior to, I recommend that clients verify functionality and sufficiency of smoke and CO alarms. Obviously, an insufficient number of working smoke alarms and/or CO alarms pose fire and life safety hazards.Any essential work such as installation or replacement of device(s) should be completed by a qualified person.
9) The electrical receptacles in the master bedroom and the receptacle to the west of the sliding glass door did not appear to be properly grounded. This can pose an electrical risk to devices plugged into these receptacles and, in turn, pose a risk to the user of said plugged-in devices. I recommend further evaluation and necessary repairs to be completed by qualified licensed electrical contractor.
10) The electrical receptacle located on the south wall of the master bedroom (wall common to master bathroom) was loose/wobbly. This can result in mechanical damage to the receptacle wiring and, in turn, pose an electrical hazard. I recommend a qualified licensed electrical contractor remove and reset or replace the receptacle to prevent such risks.
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
Heating system type(s): Furnace forced air
Location of main heating appliance: Garage
Source of combustion air: Intake duct
Forced air system capacity in BTUs or kilowatts: 80,000btuh
Make of heating appliance(s): Trane
Model number: TDS080A936A1
Last verifiable service date: 9/2019
Location of heating system filters: At top of air handler
General heating distribution type(s): Ducts with registers
Gas-fired device flue type: B-vent
Device operational at time of inspection: Yes
Energy source: Natural gas
Gas meter location: East side of house
Visible fuel storage systems onsite: None visible
Location of main fuel shut-off valve: At gas meter
11) The estimated useful life for most forced air furnaces is 15-20 years. This furnace appeared to be beyond its useful lifespan. It may need to be replaced or require significant repairs at any time. I recommend further evaluation, replacement as might be necessary, with work to be completed by a qualified HVAC professional.
I strongly recommend replacing/cleaning filters at time of real estate transaction, regardless of the last verified service date.
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Make of water heater(s): Rheem
Estimated age: 10/2019
Capacity (in gallons): 40
Type: Tank
Energy source: Natural gas
Device operational at time of inspection: Yes
Location of water heater: Garage
Water temperature (degrees Fahrenheit): 120f
Seismic straps installed at tank water heater: Yes
Temperature-pressure relief valve and drain line installed: Yes, valve and drain line are present
12) The temperature-pressure relief valve drain line was too short. This is a safety concern that contributes to the risk of scalding burns. This risk is less worrisome because of its location in the garage, but still to be taken seriously. If concerned, I recommend that a qualified and licensed plumbing or HVAC contractor repair/replace. For example, by extending the drain line to within 6 inches of the floor, or routing it to drain outside. For more information, visit: https://www.reporthost.com/?TPRVALVE
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Water service type: Public
Main system water pressure (psi): 130psi
Location of municipal/community connections/shutoffs and/or water meter (customarily located below grade): Not verified. Typically located at/below grade near the street or an alley
Location of "occupant accessible" main water shutoff valve: Not located, inspector only identified municipal or street shutoff. Occupant accessible shutoffs, when present, may be obscured from view or difficult to find. Consult with plumber, property owner or otherwise locate or install shutoff
Waste system type: Municipal sewer (underground pipes are excluded)
Sewage ejector pump installed: None visible
Location waste/drain system main cleanout(s): crawlspace
Plumbing vent stack or vent stacks present: Yes, more than one vent was noted. The inspector verifies that vents are present, but does not perform detailed analysis of the adequacy of stacks
13) The water supply pressure was greater than 80 pounds per square inch (PSI). Pressures above 80 PSI may void warranties for some appliances such as water heaters or washing machines. Flexible supply lines to washing machines are likely to burst with higher pressures. 40-80 PSI is considered the normal range for water pressure in a home, and most plumbers suggest 50-60 PSI. Typically, the pressure cannot be regulated at the water meter. I recommend that a qualified plumbing contractor evaluate and make modifications to reduce the pressure to below 80 PSI. Installing a pressure reducing valve on the main service pipe is a common solution to this problem. If one exists, then it should be adjusted, repaired or replaced as necessary to maintain lower pressures. Note that installing a pressure reducing valve creates a "closed system," which may require installing an expansion tank at the water heater if one is not already installed.
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.
The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Traversed
Apparent foundation type: Crawl space
Foundation wall/stem wall material: Poured in place concrete
Footing material (under foundation stem wall): Poured in place concrete
Foundation sill plate bolts: Sporadic, a few were seen, but would not conform to current standards. When present, bolts better attach a home to a foundation in the event of seismic activity
Pier or support post material: Wood
Beam material: Wood
Floor structure above: Solid wood joists
Insulation material underneath floor: Fiberglass roll or batt
Vapor barrier present: Yes
Ventilation type: Unconditioned space, with vents
14) Small amounts of standing water were noted at some crawl space locations. Minor seasonal water is sometimes seen. However, if significant amounts of crawl space water are present, structural and fungal damage may occur. Furthermore, crawl space water will evaporate up into interior space. In light of the small quantity of water noted, I suggest correcting any issues related to outside perimeter grading and/or roof drainage (see any other similar comments in this report). Also, review any disclosure statements available and ask the property owner about past accumulations of water. Then monitor the crawl space, especially after prolonged periods of rain. If this ends up being a bigger problem, as in significant amounts of crawl space water or flooding, consult with a drainage professional. Many procedures exist for controlling crawl space water:
Repairing, installing or improving underground footing and/or curtain drains
Applying waterproof coatings to foundation walls
Digging trenches in the crawl space to collect or divert water
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and are excluded from this inspection.
Range, cooktop, oven energy source: Electric
Ventilation kitchen/range: Hood or built into microwave over range or cooktop
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Locations/bathroom types: Full bath main floor, 3/4 bath main floor
Bathroom and laundry ventilation type: Spot exhaust fans, with individual ducts
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, I recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Exterior door(s) types/materials: See "exterior" report section
Exterior window(s) types/materials: See "exterior" report section
Interior wall type or covering: Drywall
Flooring type or covering(s): Carpet, Vinyl, linoleum or marmoleum
Ceiling type or covering: Drywall or plaster