Cedar Valley Inspections, LLC

819 Haines St 
Sedro Woolley WA 98284-1113
Inspector: Jason Matheny

Cochran20200322

Client(s):  Christopher and Christina Cochran
Property address:  2126 Hearthstone St
Ferndale WA 98248-8023
Inspection date:  Sunday, March 22, 2020

This report published on Monday, March 23, 2020 1:29:35 AM PDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Site and Grounds
Exterior
Garage and/or Carport
Roof
Attic Space and Roof Structure
Electric System
HVAC (Heating, Ventilation and Air Conditioning)
Fireplaces, Inserts, Stoves, Chimneys and Flues
Water Heater(s)
Plumbing System
Crawl Space(s) (Foundation)
Kitchen
Bathrooms and Laundry Areas
Interior Areas

View summary

General Information
Table of contents
Time started: 3:30pm
Time finished: 5:30pm
Present during inspection: Realtor
Client present for discussion at end of inspection: No
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Cool
Type of building inspected: Single family and attached or built-in garage
Buildings inspected: House and attached/built-in garage
Year Built: 2020
Source for main building age: Public records/assessor data
Front of building faces: South
Main entrance faces: South
Occupied: No
1) The client should be aware that a break-in period occurs during the first year or two after a building is constructed. Some amount of settlement and shrinkage is inevitable as temperature and humidity varies during the seasons. Systems may need adjustment or repair after experiencing constant, prolonged and/or heavy usage. Overall performance of the building exterior has not yet been tested by a wide variety of weather conditions. It is beyond the scope of this inspection to determine if all permits have been approved or signed off. Consult with the builder and/or municipality to determine if all necessary permits have been approved.
Site and Grounds
Table of contents
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Apparent wall structure: Wood frame
Wall covering: Cement fiber
Exterior door(s) types/materials: Solid wood hinged, Glass panel hinged
Exterior window(s) types/materials: Double pane synthetic (vinyl, composite and/or fiberglass) sashes/frames
Deck, patio, porch cover material and type: Open
Deck, porch and/or balcony material: Wood
Exterior stair material: Wood
2) Clearances between the cement fiber siding and surfaces below were insufficient. Conditions conducive to moisture entry can penetrate and damage the siding, and the manufacturer's warranty might be voided. Normally, minimum clearances below the bottom of cement fiber siding and trim include:
  • 6 inches to the finished grade below
  • 2 inches to paths, steps, driveways or deck surfaces below
  • 2 inches to roof surfaces below
  • 1/4 inch to horizontal flashing below, with no caulk applied
Recommend that a qualified general contractor repair per the siding/trim manufacturer's specifications.
Photo
Photo 2-1 A 1"-2" gap wherever siding meets other surfaces allows for proper water-shedding qualities. Water trapped or held in place by inadequate clearances can infiltrate siding and undermine its efficacy.
3) The wood siding on parts of the home's exterior will require occasional maintenance to guard against elemental wear of its sealant/protective exterior coating. This is important to prevent moisture-related deterioration of exterior cladding. I recommend consulting with seller and/or qualified licensed siding contractor for further tips on ongoing maintenance of wood exterior cladding products.
Photo
Photo 3-1 
Photo
Photo 3-2 
Photo
Photo 3-3 
4) Some crawlspace vents were at grade level. These can become filled with debris, diminishing their efficacy. I recommend occasional monitoring by occupant/homeowner to maintain proper ventilation properties.
Photo
Photo 4-1 
Photo
Photo 4-2 
Garage and/or Carport
Table of contents
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi-unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Attached garage
Type of door between garage and house: Hollow core, Wood
Type of garage vehicle door: Sectional, Sliding
Number of vehicle doors: 1
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
5) The door between the garage and the house did not appear to be fire-resistant, or the inspector was unable to verify that it was via a label. This is a potential safety hazard. House to garage doors, to prevent fire and fumes from spreading from the garage into interior living space, should be constructed of fire-resistant materials. Doors, generally considered to be suitable for the purpose, are solid core wood, steel, honeycomb steel or a door that has been factory labeled as acceptable. I recommend that a qualified general contractor replace or repair the door and, at that time, make any other corrections that might be required to provide suitable fire-resistance between the garage and the dwelling per standard guidelines.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, I recommend that a professional review the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Partially traversed, Viewed from eaves on ladder, Viewed from ground, Viewed from windows
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Hipped
Roof-attic ventilation system based on roof/exterior view: Roof box vent(s), Soffit vent(s)
Apparent number of layers of roof surface material: One
Gutter material: Aluminum
Downspout material: Aluminum
Attic Space and Roof Structure
Table of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Partially traversed
Roof structure type: Trusses
Ceiling structure: Ceiling joists
Ceiling insulation material: Fiberglass loose fill
Estimate of approximate insulation R value (may vary in some areas): approx. R-45 to R-49
Roof-attic ventilation system(s) based on attic view: See "roof" section of report
Electric System
Table of contents
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Primary service type: Underground
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
System grounding method: Ground electrode(s) in soil
Make of main panel(s): Siemens
Main disconnect rating (amps): 200
Location of main disconnect: Breaker at top of main service panel
Location of main service panel #1: Garage
Branch circuit wiring type: copper
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: Yes
Arc fault circuit interrupter (AFCI) protection present: Yes
Smoke alarms installed: Yes, but not tested
Carbon monoxide alarms installed: Yes, but not tested
HVAC (Heating, Ventilation and Air Conditioning)
Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
Heating system type(s): Furnace forced air
Location of main heating appliance: Garage
Source of combustion air: Intake duct
Forced air system capacity in BTUs or kilowatts: 60,000 btuh
Make of heating appliance(s): Goodman Company
Model number: GCES960603BNAA
Last verifiable service date: New Install
Location of heating system filters: Behind return air grill(s)
General heating distribution type(s): Ducts with registers
Gas-fired device flue type: B-vent
Device operational at time of inspection: Yes
Energy source: Natural gas
Gas meter location: East side of house
Location of main fuel shut-off valve: At gas meter
Fireplaces, Inserts, Stoves, Chimneys and Flues
Table of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Gas fireplace/stove(s) type: Insert
Brand of gas fireplace/stove(s)/log lighter: Missing Product Data Plate
Energy source: Natural gas
Gas-fired device flue type: Direct vent
Device operational at time of inspection: Excluded from inspection, undetermined status due to circumstances
6) I recommend that the client review all available documentation for gas-fired fireplaces and stoves. Depending on how they are operated (for routine heating versus ambiance), such appliances may require annual service or service every few years. Consult with the property owner and/or a qualified heating contractor to determine if service is needed at this time. Product data plate could not be located.
Photo
Photo 6-1 The gas shut-off valve for the fireplace is located behind the removable cover approximately within the green circled area.
Photo
Photo 6-2 View of gas shut off valve. This is typically where a metal product data plate can be found attached to a thin-gauge wire. The wire was found, but without its tag/data plate.
Water Heater(s)
Table of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Make of water heater(s): Navien
Estimated age: New Install
Capacity (in gallons): Not applicable
Type: Tankless
Energy source: Natural gas
Device operational at time of inspection: Yes
Location of water heater: Garage
Water temperature (degrees Fahrenheit): 115F
Temperature-pressure relief valve and drain line installed: Valve present, but missing or defective drain line
7) The drain line assembly for the water heater's temperature-pressure relief valve appeared to be made from PVC plastic. This material is not rated for high temperature and pressure and poses a safety hazard. Also, these lines are not to be trapped. However, this line was run to a "receiver" (along with the condensate drain line) which was installed with a drain trap, effectively trapping the TPRV drain line. A qualified plumber should repair per standard guidelines. For example, by replacing the PVC components with copper or CPVC plastic components.
Photo
Photo 7-1 
Photo
Photo 7-2 TPRV drain lines are not to be trapped. When the TPRV drain line is in use, it can be very hot and forceful. Traps inhibit the safe exiting of very hot water in such emergency situations.
Photo
Photo 7-3 This drain line should be plumbed with CPVC, Galvanized Steel, Copper, or another approved material. PVC is not rated for high enough temperatures to be safe for use in TPRV drain lines.
Plumbing System
Table of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Water service type: Public
Main system water pressure (psi): 60psi
Location of municipal/community connections/shutoffs and/or water meter (customarily located below grade): Not verified. Typically located at/below grade near the street or an alley
Location of "occupant accessible" main water shutoff valve: Not located, inspector only identified municipal or street shutoff. Occupant accessible shutoffs, when present, may be obscured from view or difficult to find. Consult with plumber, property owner or otherwise locate or install shutoff
Waste system type: Municipal sewer (underground pipes are excluded)
Sewage ejector pump installed: None visible
Location waste/drain system main cleanout(s): Crawlspace
Plumbing vent stack or vent stacks present: Yes, more than one vent was noted. The inspector verifies that vents are present, but does not perform detailed analysis of the adequacy of stacks
Service pipe material: Below ground, undetermined
Supply pipe material: PEX plastic
Drain/waste pipe material: ABS plastic
Vent pipe material: ABS plastic
8) Some drain line traps were substandard (e.g. "S", "U" or drum traps). Traps can siphon or run dry and cause sewer gases to enter living spaces. I recommend that a qualified plumbing contractor repair per standard guidelines. For example, by replacing with modern "P" traps.
Photo
Photo 8-1 This drain setup is effectively an "s" type trap. According to currently accepted plumbing practices, a "p" style trap is called for.
Photo
Photo 8-2 
Photo
Photo 8-3 
Photo
Photo 8-4 
Crawl Space(s) (Foundation)
Table of contents
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Traversed
Apparent foundation type: Crawl space
Foundation wall/stem wall material: Poured in place concrete
Footing material (under foundation stem wall): Poured in place concrete
Foundation sill plate bolts: Yes, newer home typical. When present, bolts better attach a home to a foundation in the event of seismic activity
Pier or support post material: Wood
Beam material: Wood
Floor structure above: Solid wood joists
Insulation material underneath floor: Fiberglass roll or batt
Vapor barrier present: Yes
Ventilation type: Unconditioned space, with vents
9) Small amounts of standing water were noted at some crawl space locations. Minor seasonal water is sometimes seen. However, if significant amounts of crawl space water are present, structural and fungal damage may occur. Furthermore, crawl space water will evaporate up into interior space. In light of the small quantity of water noted, I suggest correcting any issues related to outside perimeter grading and/or roof drainage (see any other similar comments in this report). Also, review any disclosure statements available and ask the property owner about past accumulations of water. Then monitor the crawl space, especially after prolonged periods of rain. If this ends up being a bigger problem, as in significant amounts of crawl space water or flooding, consult with a drainage professional. Many procedures exist for controlling crawl space water:
  • Repairing, installing or improving underground footing and/or curtain drains
  • Applying waterproof coatings to foundation walls
  • Digging trenches in the crawl space to collect or divert water
  • Installing sump pumps
Photo
Photo 9-1 View of crawlspace grade change. In this larger section of the crawlspace, drainage rock/gravel was noted on the lower section, underneath the vapor barrier. This promotes better drainage of moisture.
Photo
Photo 9-2 Picture of grade height transition with drainage gravel installed on lower section.
Photo
Photo 9-3 Lower grade section of smaller portion of crawlspace noted without drainage gravel and with standing water. If this were dug down deeper with installation of drainage gravel, this standing water would likely not accumulate, outside of times with heavy rainfall. At the time of inspection, no significant rain had fallen for the week prior to inspection.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and are excluded from this inspection.
Range, cooktop, oven energy source: Natural gas
Ventilation kitchen/range: Hood or built into microwave over range or cooktop, ducted to exterior
10) The garbage disposal installed on the kitchen sink did not appear to be electrically connected. This was, therefore, not inspected/tested. The oven and the dishwasher were also not tested, as each was newly installed and had not yet been started/initially setup. Client should confer with seller as to operational status of newly installed appliances.
Photo
Photo 10-1 This garbage disposal has no electrical cord/plug installed.
Photo
Photo 10-2 All drain and supply plumbing leading from dishwasher to plumbing under kitchen sink was found to be in normal/acceptable installation condition. Dishwasher was not tested/run.
Photo
Photo 10-3 Oven control panel. Inspector does not initialize newly installed appliances. Confer with seller/installer and/or user manual with any questions regarding this equipment's operation.
Photo
Photo 10-4 Newly installed oven with product data/manual
11) The corner cabinet door between the sink and stovetop was noted as rubbing/catching with adjacent drawer. This is a nuisance concern of no great consequence. Care should be taken when operating to avoid mechanical damage.
Photo
Photo 11-1 
Photo
Photo 11-2 
Photo
Photo 11-3 
12) The cabinet below the stovetop contains the gas supply line and gas shutoff valve for the stovetop. Care should be taken whenever items are to be stored in this cabinet to avoid mechanical damage to the gas line. Also, awareness of the gas shutoff valve can be vital.
Photo
Photo 12-1 
Photo
Photo 12-2 Gas shutoff valve located under stovetop.
Bathrooms and Laundry Areas
Table of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Locations/bathroom types: Full bath main floor, Half bath main floor, Full bath upper floor, Master bath upper floor
Bathroom and laundry ventilation type: Windows, Spot exhaust fans, with individual ducts
Gas supply present for dryer: Yes
240 volt receptacle present for dryer: Yes
13) Many cabinet doors in the bathrooms were able to strike nearby walls. This can cause cosmetic damage to the walls' paint surfaces. I recommend awareness and care to be taken when in use.
Photo
Photo 13-1 
Photo
Photo 13-2 Master bath cabinetry adjacent to water closet
14) The glass door on the master bath shower stall enclosure had no sort of doorstop installed and was able to strike both the towel bar and the shower head. I recommend awareness and care taken when in use.
Photo
Photo 14-1 
Photo
Photo 14-2 Master bath shower stall door can strike towel bar. Care should be taken.
Photo
Photo 14-3 Shower stall door can also strike shower head. This is likely to cause more damage to shower head than door. Care should be taken when operating.
Photo
Photo 14-4 
Interior Areas
Table of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, I recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Exterior door(s) types/materials: See "exterior" report section
Exterior window(s) types/materials: See "exterior" report section
Interior wall type or covering: Drywall
Flooring type or covering(s): Carpet, Wood or wood products, Laminate
Ceiling type or covering: Drywall or plaster
15) The cable lines run horizontally below guardrail/handrail on the stairs and upstairs hallway are not aligned with current building safety standards. While the spacing between is within current standards, the horizontal installation allows for these to be climbable and dangerous to toddlers and adventurous children. I recommend, at the very least, extra care taken whenever young children are present. If concerned, I recommend further evaluation and repairs to be completed by qualified licensed general contractor.
Photo
Photo 15-1 
Photo
Photo 15-2 
Photo
Photo 15-3 
Photo
Photo 15-4 
Photo
Photo 15-5 Just a 42" climb...
Photo
Photo 15-6 Can result in a 13.5ft fall!
16) Some exterior door hardware, including deadbolts and/or latches were difficult to operate. This is a matter of security and an issue of convenience. I recommend that a qualified person or contractor evaluate and repair/ replace as necessary.

This was most notable on the front (main entrance) door.
Photo
Photo 16-1 Front door requires extra force applied to operate deadbolt and/or to get the door to properly latch shut.
Photo
Photo 16-2 Strike plates should be adjusted to allow for easier operation of door latch and deadbolt.
17) The closet door in the first floor bedroom was noted as installed in a way to allow it to collide with the bedroom door, when both open. This can allow for mechanical damage to either/both doors. I recommend care taken when operating.
Photo
Photo 17-1 First floor bedroom closet.
18) I've attached extra photos of closets and storage areas per conversation with client.
Photo
Photo 18-1 First floor bedroom closet.
Photo
Photo 18-2 First floor bedroom closet.
Photo
Photo 18-3 First floor bedroom closet.
Photo
Photo 18-4 Kitchen Pantry
Photo
Photo 18-5 The light switch for the pantry located to the left of the pantry door.
Photo
Photo 18-6 Kitchen Pantry
Photo
Photo 18-7 Kitchen Pantry
Photo
Photo 18-8 Kitchen Pantry
Photo
Photo 18-9 Kitchen Pantry
Photo
Photo 18-10 Kitchen Pantry
Photo
Photo 18-11 Kitchen Pantry
Photo
Photo 18-12 Kitchen Pantry
Photo
Photo 18-13 Kitchen Pantry
Photo
Photo 18-14 Kitchen Pantry
Photo
Photo 18-15 Under-stair storage closet
Photo
Photo 18-16 Under-stair storage closet
Photo
Photo 18-17 Under-stair storage closet
Photo
Photo 18-18 Upstairs hall linen closet
Photo
Photo 18-19 Upstairs hall linen closet
Photo
Photo 18-20 Upstairs SW bedroom closet
Photo
Photo 18-21 Upstairs SW bedroom closet
Photo
Photo 18-22 Upstairs SW bedroom closet
Photo
Photo 18-23 Upstairs SW bedroom closet
Photo
Photo 18-24 Upstairs NE Bedroom Closet
Photo
Photo 18-25 Upstairs NE Bedroom Closet
Photo
Photo 18-26 Upstairs NE Bedroom Closet
Photo
Photo 18-27 Upstairs NE Bedroom Closet
Photo
Photo 18-28 Master Bedroom Closet
Photo
Photo 18-29 Master Bedroom Closet
Photo
Photo 18-30 Master Bedroom Closet
Photo
Photo 18-31 
Photo
Photo 18-32 Master Bedroom Closet
Photo
Photo 18-33 Master Bedroom Closet
Photo
Photo 18-34 Master Bedroom Closet
Photo
Photo 18-35 Low-voltage panel box with cover plate installed in Master Bedroom Closet
Photo
Photo 18-36 This is for a control panel/security system.