This report published on Wednesday, July 3, 2019 6:34:33 PM PDT
This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
Safety
Poses a safety hazard
Repair/Replace
Recommend repairing or replacing
Repair/Maintain
Recommend repair and/or maintenance
Maintain
Recommend ongoing maintenance
Evaluate
Recommend evaluation by a specialist
Monitor
Recommend monitoring in the future
Comment
For your information
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain), Overcast
Temperature during inspection: Cool
Type of building inspected: Single family, Detached garage
Buildings inspected: House only, Detached garage, Gazebo
Year Built: 1935
Source for main building age: Public records/assessor data
Front of building faces: West
Main entrance faces: West
Occupied: Yes
1) Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation.
2) Some areas and items at this property were obscured by furniture and/or stored items. This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level
Driveway material: Gravel
Sidewalk material: Poured in place concrete
3) Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a condition conducive to attracting wood-destroying organisms. I recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
Deck, porch and/or balcony material: Wood
Exterior stair material: Wood
4) Soil was in contact with or less than 6 inches from siding or trim. Regardless of what material is used for siding, it should not be in contact with the soil. If made of wood, siding or trim will eventually rot. For other materials, ground or surface water can infiltrate siding or trim and cause damage to the wall structure. Wood destroying insects are likely to infest and damage the wall structure. This is a condition conducive to attracting wood destroying organisms. I recommend grading or removing soil as necessary to maintain a 6-inch clearance. Note that damage from fungal rot and/or insects may be found when soil is removed, and repairs may be necessary.
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi-unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Detached garage
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
5) A small squared hole was noted on the north side exterior of the detached garage. It appeared as if something were removed from this spot (perhaps an electrical receptacle of some sort.) This should be covered to help prevent intrusion from elements, moisture, and/or pests such as rodents, insects, or other wood-destroying organisms. Work to be completed by licensed general contractor or other qualified party.
6) The skylight in the garage is cracked/stressed in several locations. Evidence of leaks can be seen on the wood structure/trim of the skylight well. Moisture intrusion can create conditions conducive to rot and/or other wood-destroying organisms. I recommend repair or removal of the skylight in question to prevent said conditions. Work to be completed by licensed general contractor or other qualified party.
7) At least one exterior light fixture on the detached garage showed signs of corrosion/oxidation. Extensive deterioration of exterior light fixtures can allow moisture intrusion, electrical short, and/or failure of the fixture itself. I recommend replacing corroded/deteriorated fixtures. Work to be completed by licensed electrical contractor or other qualified party.
8) Firewood has been stacked inside the garage against the north wall. Wood piles can hold moisture against walls, creating conditions conducive to rot and/or other wood-destroying organisms. Wood piles can also themselves be perfect breeding/feeding grounds for rot and/or other wood-destoying organisms. I recommend moving the wood pile outside the garage and away from wood structures. Work to be completed by qualified individual.
9) See "Electric System" section of report for electrical concerns in the detached garage.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, I recommend that a professional review the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Traversed
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable, Hipped
Roof-attic ventilation system based on roof/exterior view: Ridge vent(s), Enclosed vented soffit
Apparent number of layers of roof surface material: One
Gutter material: Plastic
Downspout material: Plastic
10) The "solar tube"/skylight was noted with a crack around one of the fasteners. This may allow moisture intrusion and other pertinant concerns/issues. I recommend evaluation and/or replacement of the tube's bowl/globe. Work to be completed by licensed roofing contractor or other qualified party.
11) Nail heads were exposed at some of the shingles. More than just a few exposed nail heads may indicate a substandard roof installation. I recommend applying an approved sealant over exposed nail heads now and as necessary in the future to prevent leaks. Some areas had missing/torn shingles (likely the work of wind storms). Areas of the ridge vent also had exposed nail heads and bent/cut flashing. I recommend appropriate repairs be made to ensure proper shedding of rain and/or other precipitation and moisture. Work and further evaluation to be completed by a qualified roofing contractor.
12) Significant amounts of debris have accumulated in gutters or downspouts. Gutters can overflow and cause water to come in contact with the building exterior, or water can accumulate around the foundation. This is a condition conducive to attracting wood destroying organisms. I recommend cleaning gutters and downspouts now and as necessary in the future. Work to be completed by a qualified gutter/downspout contractor.
13) An area on the east side of the detached garage roofing surface showed signs of wear/deterioration at a higher rate than the rest of the roof. Cause of this advanced deterioration was not readily apparent at the time of inspection. I recommend awareness of the concern and ongiong monitoring of the area in question for signs of further deterioration. Consult with qualified roofing contractor if concerned or signs of further deterioration become apparent.
14) A tv satellite dish was noted on the edge of the east side of the roof. However, the cable and internet appeared to be supplied by cable. If the dish is not going to be in use, I recommend removal of the dish and repair of the area from which it is removed. This will eliminate any chance of leak or issue due to the presence/installation of said satellite dish. Work to be completed by qualified general contractor, satellite provider contractor, or other qualified party.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch(es), Partially traversed
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Ceiling insulation material: Fiberglass loose fill, Fiberglass roll or batt
Estimate of approximate insulation R value (may vary in some areas): R-38, estimated
Vermiculite insulation present: None visible
Roof-attic ventilation system(s) based on attic view: See "roof" section of report
15) Some locations in the attic showed signs of a previous fire. This was confirmed by the disclosure information per the client's agent. Wood that has been previously burned is affected by a process called "pyrophoric carbonization". This effectively lowers the temperature at which the wood will ignite. This can be hazardous if the affected area is exposed to elevated temperatures for long amounts of time. I recommend awareness of this condition and great caution be taken by the homeowner and/or occupants to avoid exposing this area to elevated temperatures, especially for long amounts of time.
16) For electrical concerns in the attic, see "Electric System" section of report.
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Primary service type: Overhead
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 100
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
System grounding method: unseen/unverified
Make of main panel(s): Square D
Main disconnect rating (amps): 100
Location of main disconnect: Breaker at bottom of main service panel
Location of main service panel #1: Top of Stairs to Basement
Make of sub/remote distribution panel(s): Square D
Location of sub/remote distribution-panel #1: Garage
Ground fault circuit interrupter (GFCI) protection present: No
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: Yes, but not tested
Carbon monoxide alarms installed: Yes, but not tested
17) Substandard wiring was found at the attic and/or garage. For example, exposed wiring, loose wiring, exposed splices, missing or broken cover plates, loose boxes and/or extension or lamp cord used as permanent wiring.This condition poses a fire and safety concern. I recommend that a qualified electrical contractor evaluate and repair/replace as necessary.
18) At least one electric receptacle at the kitchen, bathroom(s), garage, exterior and/or basement had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. Proper GFCI protection reduces the risk of electrical shock at specific areas of the home. I recommend that a qualified electrical contractor evaluate and, as necessary, install GFCI protection. At the present time, GFCI protection is required at multiple 120 volt branch circuits. If wiring is modified in the future, depending on the scope of the project, the permitting process may trigger mandatory upgrades. State law compels an inspector to suggest updating GFCI protection to meet with current guidelines. A diagram, illustrative of current placement for GFCI and AFCI (arc fault) protection, is available at this link: https://goo.gl/f62RMB
19) At least one electric receptacle(s) at the bedroom(s), kitchen, dining room and/or living room had no visible arc fault circuit interrupter (AFCI) protection, or the inspector was unable to determine if AFCI protection was present. AFCI protection reduces the risk of fire by guarding against circuits that are overheating or arching. I recommend that a qualified electrical contractor evaluate and, as necessary, install AFCI protection per standard safety guidelines. At the present time, AFCI protection guidelines require the devices at most 120 volt household branch circuits. Rule changes over the years are typically not retroactive but, depending on the scope of the project, if wiring is modified in the future, the permitting process could trigger compulsory upgrades. A diagram, illustrative of the recommended placement for AFCI and GFCI (ground fault) protection, is available at this link: https://goo.gl/f62RMB
20) At least one modern 3-slot electric receptacles, with a missing or open ground, was identified on the premises. Three-slot receptacles should have a hot, a neutral and an equipment ground wire connected. Homeowners often install new 3-slot receptacles on older 2-wire circuits that only accommodate hot and neutral wires. Any such receptacles do not have equipment ground(s), when present equipment grounds enhance occupant safety, and are considered antiquated wiring by today's standards. Any tools, appliances and equipment that is designed to be grounded should not be plugged into receptacles that are lacking equipment grounds. I recommend that a qualified electrical contractor evaluate and upgrade/repair/replace wiring and system as necessary. Upgrading to grounded receptacles typically requires installing new wiring from the main service panel or sub-panel to the receptacle(s), in addition to replacing the receptacle(s). If rewiring is not an option, due to financial considerations, often 3-slot ungrounded receptacles will be replaced with 2-slot receptacles.
21) Branch circuit wiring installed in buildings built prior to the mid 1980s is typically rated for a maximum temperature of only 60 degrees Celsius. This includes non-metallic sheathed (Romex) wiring, and both BX and AC metal-clad flexible wiring. Knob and tube wiring, typically installed in homes built prior to 1950, may be rated for even lower maximum temperatures. Newer electric fixtures including lighting and fans typically require wiring rated for 90 degrees Celsius. Connecting newer fixtures to older, 60-degree-rated wiring is a potential fire hazard. Repairs for such conditions may involve replacing the last few feet of wiring to newer fixtures with new 90-degree-rated wire, and installing a junction box to join the old and new wiring.
It is beyond the scope of this inspection to determine if such incompatible components are installed, or to determine the extent to which they're installed. Based on the age of this building, the client should be aware of this safety hazard, both for existing fixtures and when planning to upgrade with newer fixtures. I recommend that a qualified electrical contractor evaluate and repair/replace as necessary.
22) The service drop wires were less than 12 feet above the ground through the east yard (over the greenhouse.) While current code/building standards mandate a minimum of 10ft clearance, service drop wires with 11ft of clearance can be problematic still. I recommend awareness of this concern by the homeowner and/or occupants and caution be taken whenever participating in activities overhead and/or when moving or working with long/tall/large items or materials.
23) An electrical switch in the garage was noted as having been taped over. If a switch is controlling some electrical device or receptacle that needs to stay in a certain position (on or off) except in certain situations, it is best practice to install a switch with a cover or a sub-panel for the concerned receptacle/device. I recommend evaluation and appropriate repairs to be performed by a qualified electrical contractor.
24) The electric service appears to be rated at substantially less than 200 amps and may be inadequate. Depending on the client's needs, I recommend consulting with a qualified electrical contractor about upgrading to a 200 amp service. Note that the electric service's rating is based on the lowest rating for the meter base, the service conductors, the main service panel and the main disconnect switch. System components may require replacement or upgrade.
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
Heating system type(s): Furnace forced air
Location of main heating appliance: Basement
Source of combustion air: Intake duct, Vent(s) to exterior
Forced air system capacity in BTUs or kilowatts: 60,000
Make of heating appliance(s): Coleman
Model number: TG9S060B12MP11B
Last verifiable service date: 03/2018
Location of heating system filters: Inside air handler
General heating distribution type(s): Ducts with registers
Gas-fired device flue type: B-vent
Device operational at time of inspection: Yes
Energy source: Natural gas
Gas meter location: South side of house
Visible fuel storage systems onsite: None visible
Location of main fuel shut-off valve: At gas meter
25) The last service date of the gas or oil-fired forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the specific date, or if service was more than 1 year ago, I recommend that a qualified HVAC professional inspect, clean, service this system, and make repairs if necessary. To assure safety and optimal performance, schedule service on an annual basis in the future. Bring any issues noted in this report to the attention of the HVAC technician when the unit is serviced.
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Gas fireplace/stove(s) type: Freestanding stove
Brand of gas fireplace/stove(s)/log lighter: Unverifiable
Model number: n/a
Energy source: Natural gas
Gas-fired device flue type: B-vent
Device operational at time of inspection: Excluded from inspection, undetermined status due to circumstances
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Make of water heater(s): Rheem
Estimated age: 03/2017
Capacity (in gallons): 40
Type: Tank
Energy source: Natural gas
Device operational at time of inspection: Yes
Location of water heater: Basement
Water temperature (degrees Fahrenheit): 117F
Seismic straps installed at tank water heater: Yes
Temperature-pressure relief valve and drain line installed: Yes, valve and drain line are present
Catch pan/drain line present under tank at finished interior space: No, missing pan and drain line
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Water service type: Public
Main system water pressure (psi): 70psi
Location of municipal/community connections/shutoffs and/or water meter (customarily located below grade): Not verified. Typically located at/below grade near the street or an alley
Location of "occupant accessible" main water shutoff valve: Basement, in SW corner of basement behind wall "patch"
Waste system type: Municipal sewer (underground pipes are excluded)
Sewage ejector pump installed: Yes
Location waste/drain system main cleanout(s): East side of building exterior
Plumbing vent stack or vent stacks present: Yes, more than one vent was noted. The inspector verifies that vents are present, but does not perform detailed analysis of the adequacy of stacks
26) Some drain line traps were substandard (e.g. "S", "U" or drum traps). Traps can siphon or run dry and cause sewer gases to enter living spaces. I recommend that a qualified plumbing contractor repair per standard guidelines. For example, by replacing with modern "P" traps.
27) Some hose bibs leaked when tested. When hose bibs leak, it's often caused by worn washers, missing packing at valve stems or loose bonnets. I recommend, to avoid wasting water, that a qualified plumbing contractor evaluate and replace/repair components as necessary.
This was noted at the NW corner of the house exterior. When opened fully, water leaked from the valve handle.
28) A sewage ejector pump was installed on the premises. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified ejector pump specialist. These systems are typically sealed and involve moving parts. They are subject to clogging and/or damage from disposal of items such as disposable diapers and sanitary napkins. I recommend that this pump and related equipment (piping, valves, etc.) be evaluated by a qualified plumbing contractor and repaired if necessary. This should be done per the manufacturer's recommendations in the future, or annually if unable to verify the manufacturer's specifications. Typically, these pumps have a lifespan of 7-10 years.
29) A sump pump was installed in the basement. These are specialty systems and only a limited evaluation was performed as part of this inspection. The inspector does not determine the adequacy of sump pumps and their associated drainage systems. The presence of a sump pump may indicate that water routinely accumulates below or inside the structure. I recommend asking the property owner how often the sump pump operates and for how long at different times of the year. The client should be aware that the service life of most sump pumps is 5-7 years, and that the pump will require replacement at an undetermined time in the future.
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing. The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Apparent foundation type: Finished basement
Foundation wall/stem wall material: Poured in place concrete
Footing material (under foundation stem wall): Not visible
Foundation sill plate bolts: No, older home typical. When present, bolts better attach a home to a foundation in the event of seismic activity, None seen where checked. When present, bolts better attach a home to a foundation in the event of seismic activity
Pier or support post material: Wood
Beam material: Wood
Floor structure above: Solid wood joists
Insulation material underneath floor: Fiberglass roll or batt
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and are excluded from this inspection.
Range, cooktop, oven energy source: Natural gas
Ventilation kitchen/range: Hood or built into microwave over range or cooktop
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Locations/bathroom types: Full bath main floor, Basement bath
Bathroom and laundry ventilation type: Windows, Spot exhaust fans, with individual ducts
Gas supply present for dryer: Yes
30) The inspector was unable to verify that the glass used in at least one doors and/or enclosure walls by the shower was approved safety glass. A safety hazard exists if untempered glass is located in areas where glazing is subject to human impact. Standard guidelines require that approved safety glass be employed in enclosures for bathtubs, showers, spas, saunas and steam rooms, and in windows where the bottom edge of the window is less than 60 inches above the drain inlet or standing surface. I recommend that a qualified person such as a window and door installation contractor evaluate and determine if glazing is approved safety glass. If not, contractor to replace with proper glazing.
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, I recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Exterior door(s) types/materials: See "exterior" report section
Exterior window(s) types/materials: See "exterior" report section
Interior wall type or covering: Drywall or plaster
Flooring type or covering(s): Carpet, Wood or wood products
Ceiling type or covering: Drywall or plaster