1731 Howe Ave # 131 
Sacramento CA 95825-2209
Inspector: James Mecorney

Property Inspection Report

Client(s):  Nicholas and Tina Soberanis/Marelise Navarro (agent)
Property address:  879 Corcoran Ct
Benicia CA 94510-3612
Inspection date:  Saturday, October 12, 2019

This report published on Sunday, October 13, 2019 5:22:18 AM PDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings

View summary

General InformationTable of contents
Report number: SOL0138
Time started: 945
Client present for discussion at end of inspection: No
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Cool
Ground condition: Dry
Recent weather: Dry (no rain)
Overnight temperature: Cool
Inspection fee: 400
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: 1982
Source for main building age: Municipal records or property listing
Front of building faces: South
Main entrance faces: South
Occupied: No
1) Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
https://www.reporthost.com/?EPA
https://www.reporthost.com/?CPSC
https://www.reporthost.com/?CDC
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Condition of fences and gates: Appeared serviceable
Fence and gate material: Wood, Chain link, Wrought iron
Condition of retaining walls: Appeared serviceable
Retaining wall material: Wood
Site profile: Level, Steep slope
Condition of driveway: Appeared serviceable
Driveway material: Brick
Condition of sidewalks and/or patios: Required repairs, replacement and/or evaluation (see comments below)
Sidewalk material: Poured in place concrete, Brick
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
2) Cracks, holes, settlement, heaving and/or deterioration resulting in trip hazards were found in the sidewalks or patios. For safety reasons, recommend that a qualified contractor repair as necessary to eliminate trip hazards.
Photo
Photo 2-1 
3) Some wooden timbers in retaining walls were rotten. The retaining walls appeared to be serviceable, but recommend monitoring them in the future. Further rot and/or deterioration may occur and retaining walls may need significant repairs or replacement at some point. Note that such repairs are often expensive.
Photo
Photo 3-1 
Exterior and FoundationTable of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Required repairs, replacement and/or evaluation (see comments below)
Apparent wall structure: Wood frame
Wall covering: Wood, Stucco
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Concrete slab on grade, Concrete garage slab
Foundation/stem wall material: Poured in place concrete, Concrete slab on grade
Footing material (under foundation stem wall): Concrete slab
4) Some sections of siding and/or trim were warped. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo
Photo 4-1 
5) Fungal rot was found at one or more sections of siding or trim. Conducive conditions for rot should be corrected (e.g. wood-soil contact, reverse perimeter slope). Recommend that a qualified contractor repair as necessary. All rotten wood should be replaced.
Photo
Photo 5-1 There was an area of concern in the wood siding at this location.
Photo
Photo 5-2 
Photo
Photo 5-3 
Photo
Photo 5-4 
Photo
Photo 5-5 The noted fungal rot may be associated with the gutter at this location.
Photo
Photo 5-6 Fungal rot was noted at the garage door opening.
Photo
Photo 5-7 Detail of previous photo.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Age of roof surface(s): 2000 (estimate)
Roof inspection method: Viewed from eaves on ladder, Viewed from ground with binoculars, Viewed from windows
Condition of roof surface material: Required repair, replacement and/or evaluation (see comments below)
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Required repair, replacement and/or evaluation (see comments below)
Condition of gutters, downspouts and extensions: Appeared serviceable
Gutter and downspout material: Metal
Gutter and downspout installation: Full
6) Fungal rot or significant water damage was found at one or more roof areas at barge boards. Recommend that a qualified contractor repair as necessary. For example, by replacing all rotten wood, priming and painting new wood and installing flashing.
Photo
Photo 6-1 
Photo
Photo 6-2 Detail of previous photo.
Photo
Photo 6-3 
Photo
Photo 6-4 
Photo
Photo 6-5 
Photo
Photo 6-6 
7) One or more roof flashings were substandard. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.
Photo
Photo 7-1 The flashing on this exposed barge board was substandard.
8) Moss was growing on the roof. As a result, shingles can lift or be damaged. Leaks can result and/or the roof surface can fail prematurely. Efforts should be made to kill the moss during its growing season (wet months). Typically, zinc or phosphate-based chemicals are used for this and must be applied periodically. For information on various moss treatment products and their pros and cons, visit:
https://www.reporthost.com/?MOSS
Photo
Photo 8-1 
9) Stains were found on one or more gutters that indicate past leaks have occurred. However, the inspector was unable to verify that the gutters do or don't leak because of lack of recent rainfall. Monitor the gutters in the future while it's raining to determine if gutters leak. If they do, then recommend that a qualified person repair as necessary to prevent water from coming in contact with the building or accumulating around the building foundation.
Photo
Photo 9-1 
Attic and Roof StructureTable of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Partially traversed
Location of attic access point #A: Master bedroom closet
Attic access points that were opened and viewed, traversed or partially traversed: A
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass roll or batt
Approximate attic insulation R value (may vary in areas): R-30
Vapor retarder: None visible
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Box vents (roof jacks), Open soffit vents
Attic exhaust fan condition: Appeared serviceable
10) One or more exhaust ducts (e.g. bathroom fan, clothes dryer) in the attic have come apart, were loose or have fallen down. This can result in increased moisture levels inside the structure and is a conducive condition for wood-destroying organisms. Recommend that a qualified person make permanent repairs as necessary.
Photo
Photo 10-1 
Garage or CarportTable of contents
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Attached, Garage
Condition of door between garage and house: Required repair, replacement and/or evaluation (see comments below)
Type of door between garage and house: Solid core, Wood
Condition of exterior entry doors: Required repair, replacement and/or evaluation (see comments below)
Exterior door material: Metal
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors:
Condition of automatic opener(s): Appeared serviceable
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: Exists
11) One or more exterior doors were difficult to open or close. Recommend that a qualified person repair as necessary.
Photo
Photo 11-1 
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: 2
Service voltage (volts): 120-240
Estimated service amperage: 125
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded copper
Main disconnect rating (amps): 125
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Building exterior
Location of main disconnect: Center
Condition of branch circuit wiring: Required repair, replacement and/or evaluation (see comments below)
Branch circuit wiring type: non-metallic sheathed
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: Yes
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: Yes, but not tested
Carbon monoxide alarms installed: No, recommend install
Smoke alarm power source(s): Battery
12) One or more ground fault circuit interrupter (GFCI) devices protecting receptacles at the exterior wouldn't trip when tested. This is a potential shock hazard. Recommend that a qualified electrician evaluate and repair as necessary.
Photo
Photo 12-1 
Photo
Photo 12-2 This GFCI did not trip when tested.
13) The electric service to this property appeared to be rated at substantially less than 200 amps and may be inadequate. Depending on the client's needs, recommend consulting with a qualified electrician about upgrading to a 200 amp service. Note that the electric service's rating is based on the lowest rating for the meter base, the service conductors, the main service panel and the main disconnect switch. One or more of these components may need replacing to upgrade.
Plumbing / Fuel SystemsTable of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Water pressure (psi): 70 psi
Location of main water meter: By sidewalk in front of house
Location of main water shut-off: Building exterior
Service pipe material: Copper
Condition of supply lines: Required repair, replacement and/or evaluation (see comments below)
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Location(s) of plumbing clean-outs: Building exterior
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: No
Sewage ejector pump installed: No
Type of irrigation system supply source: Public
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: None visible
Location of main fuel shut-off valve: At gas meter
14) No sediment trap was installed in the gas supply line at the furnace and/or water heater. Sediment traps prevent damage to gas-fired appliances by trapping oil, scale, water condensation and/or debris. Recommend that a qualified contractor install a sediment trap per standard building practices.
Photo
Photo 14-1 
15) Significant corrosion or rust was found at one or more water supply valves. This can indicate past leaks, or that leaks are likely to occur in the future. Recommend that a qualified plumber repair as necessary. For example, by replacing valves or fittings.
Photo
Photo 15-1 
16) One or more hose bibs leaked when tested. When hose bibs leak while turned off, it's often caused by a worn valve seat or a loose bonnet. When hose bibs leak while turned on, it may be due to worn "packing" around the stem or a defective backflow prevention device. Recommend that a qualified plumber repair as necessary.
Photo
Photo 16-1 
Water HeaterTable of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable, Near, at or beyond service life
Type: Tank
Energy source: Natural gas
Estimated age: 1995
Capacity (in gallons): 50, Estimate
Temperature-pressure relief valve installed: Yes
Manufacturer: A.O. Smith
Location of water heater: Garage
Condition of burners: Appeared serviceable
Condition of venting system: Required repair, replacement and/or evaluation (see comments below)
Condition of combustion air supply: Appeared serviceable
17) The draft hood for the water heater flue was loose. This is a potential safety hazard due to the risk of exhaust gases entering living spaces. A qualified person should permanently secure the draft hood with appropriate fasteners per standard building practices.
Photo
Photo 17-1 
18) A permanently installed insulated jacket was installed on the water heater. It obscured the manufacturer's information label and/or most of the water heater. The inspector was unable to fully evaluate the water heater.
Photo
Photo 18-1 
19) The estimated useful life for most water heaters is 8-12 years. This water heater appeared to be beyond this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.

Inspector was unable to determine manufacture date with certainty, but estimate 1995.
Heating, Ventilation and Air Condition (HVAC)Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Furnace
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: 2014
Forced air heating system manufacturer: Bryant
Location of forced air furnace: Closet
Forced air system capacity in BTUs or kilowatts: 110,000
Condition of furnace filters: N/A (none visible)
Location for forced air filter(s): Behind return air grill(s)
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable
Type of combustion air supply: Vent(s) to exterior
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location of heat pump or air conditioning unit: Building exterior
Type: Split system
Estimated age of heat pump or air conditioning unit: 2014
Approximate tonnage: 3
Manufacturer of cooling system and/or heat pump: Bryant
Condition of controls: Appeared serviceable
20) Air filters for the heating and/or cooling system were missing at one or more locations where they should have been installed. Indoor air quality will be reduced as a result. Recommend installing good quality filters at intended locations (e.g. in or at the air handler, behind return air grills). Filters should be sized correctly to minimize air gaps. Many types of filters are available. Recommend installing pleated filters or better rather than the cheapest disposable kind. For more information, visit:
https://www.reporthost.com/?FLTRTPS
Photo
Photo 20-1 
Fireplaces, Stoves, Chimneys and FluesTable of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of gas-fired fireplaces or stoves: Required repair, replacement and/or evaluation (see comments below)
Gas fireplace or stove type: Metal pre-fab fireplace
Fan or blower installed in gas-fired fireplace or stove: None visible
Condition of chimneys and flues: Appeared serviceable
Wood-burning chimney type: Metal, with wood enclosure
Gas-fired flue type: B-vent
21) The glass front on the gas fireplace had a hazy film. This is typically a mineral residue left from water vapor as the gas burns. It may be possible to clean this fogging by removing the glass from the fireplace and using a gas appliance ceramic glass cleaner, available through gas fireplace and stove distributors and installers. Ammonia-based products, such as common glass cleaners, should not be used since they can cause damage or etching to the glass, or make the haze permanent. It may be possible for a homeowner to remove the glass for cleaning, if the instructions for the fireplace are available and if the homeowner is experienced in such repairs. Consult with a qualified specialist for more information, or to have them do the cleaning.
Photo
Photo 21-1 
22) One or more gas fireplaces or stoves did not respond to normal controls (e.g. on/off switch, thermostat, remote control) and were not fully evaluated as a result. The pilot light or gas supply may have been turned off, or some other condition may have prevented operation. The inspector only operates normal controls and does not light pilot lights or operate gas shut-off valves. Consult with the property owner, review all documentation for such gas appliances, and become familiar with the lighting procedure. If necessary, a qualified specialist should assist in lighting such appliances, and make any needed repairs.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Permanently installed kitchen appliances present during inspection: Range, Dishwasher, Refrigerator, Under-sink food disposal, Microwave oven, Hot water dispenser
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Required repair, replacement and/or evaluation (see comments below)
Condition of dishwasher: Appeared serviceable
Condition of ranges, cooktops and/or ovens: Appeared serviceable
Range, cooktop, oven type: Natural gas
Type of ventilation: Hood or built into microwave over range or cooktop, ducted to exterior
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: Appeared serviceable
Condition of hot water dispenser: Appeared serviceable
Condition of trash compactor: N/A (none installed)
23) The under-sink food disposal was jammed. Recommend that a qualified contractor repair or replace as necessary.
Photo
Photo 23-1 
Bathrooms, Laundry and SinksTable of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath, Master bath, second floor
Location #B: 3/4 bath, first floor, Hall
Location #C: 3/4 bath, first floor, Bed 2
Location #D: Laundry room/area, first floor
Location #E: Bar sink, second floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of toilets: Required repair, replacement and/or evaluation (see comments below)
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Windows, Spot exhaust fans, with individual ducts
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes
24) The clothes dryer exhaust duct was kinked, crushed or damaged. Air flow will be restricted as a result and the clothes dryer may overheat. This is a safety hazard due to the risk of fire. Recommend that a qualified person replace or repair the duct as necessary. For more information, visit:
https://www.reporthost.com/?DRYER
Photo
Photo 24-1 
25) The toilet at location(s) #B was loose where it attached to the floor. Leaks can occur. Flooring, the sub-floor or areas below may get damaged. Sewer gases can enter living spaces. Recommend that a qualified contractor remove the toilet(s) for further evaluation and repair if necessary. A new wax ring should be installed and toilet(s) should be securely anchored to the floor to prevent movement and leaking.
Photo
Photo 25-1 
26) The sink at location(s) #A drained slowly. Recommend clearing drain and/or having a qualified plumber repair if necessary.
Photo
Photo 26-1 
27) The sink drain stopper mechanism at location(s) #A was inoperable. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 27-1 
28) Water was leaking at the sink faucet base or handles at location(s) #E. Recommend that a qualified plumber repair as necessary.
Photo
Photo 28-1 
29) One or more sink drains were leaking at location(s) #A and B. A qualified person should repair as necessary.
Photo
Photo 29-1 
Photo
Photo 29-2 
Photo
Photo 29-3 
Photo
Photo 29-4 
30) Caulk around the base of the toilet at location(s) #B and C was missing, substandard and/or deteriorated. Modern standards require caulk to be installed around the entire toilet base where it meets the floor for sanitary reasons. Without it, soiled water can soak into flooring and sub-floor materials if the toilet overflows. Condensation from the toilet can also soak into the flooring. Recommend that a qualified person caulk around toilet bases per standard building practices.
Photo
Photo 30-1 
Photo
Photo 30-2 
31) There was a floor heating system installed in the master bathroom. Inspector was unable to activate the floor heating system as the controls had no response. Consult with property owner regarding correct operation of floor heating system, and inquire as to any defects may exist in the system.
Photo
Photo 31-1 
Interior, Doors and WindowsTable of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Fiberglass or vinyl, Sliding glass
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Vinyl, Metal, Multi-pane, Sliding, Fixed
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Condition of concrete slab floor(s): Appeared serviceable
Flooring type or covering: Carpet, Vinyl, linoleum or marmoleum, Tile
Condition of stairs, handrails and guardrails: Appeared serviceable
32) Vinyl floor tiles were installed in one or more "wet" areas (e.g. kitchen, mud room, bathroom, laundry room). Spilled water can penetrate seams and damage the sub-floor. Recommend that a qualified contractor install continuous waterproof flooring in wet areas as necessary.
Photo
Photo 32-1 
Wood Destroying Organism FindingsTable of contents
Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: No
Visible evidence of active wood decay fungi: No
Visible evidence of past wood-destroying insects: No
Visible evidence of past wood decay fungi: Yes, See notes
Visible evidence of damage by wood-destroying insects: No
Visible evidence of damage by wood decay fungi: Yes, See notes
Visible evidence of conditions conducive to wood-destroying organisms: No
Evidence of prior treatment of wood-destroying insects: Posted inspection notice, 05/2019

The Parties Understood and Agreed as follows:

1. INSPECTOR GUARANTEES to perform a visual inspection of the home and to provide CLIENT with a written inspection report identifying the defects that INSPECTOR both observed and deemed material. INSPECTOR may offer comments as a courtesy, but these comments will not comprise the bargained-for report. The report is only supplementary to the sellers disclosure.

2. INSPECTOR agrees to perform the inspection in accordance to the current Standards of Practice of the National Association of Certified Home Inspectors posted at http://www.nachi.org/sop.htm.

3. CLIENT understands that the inspection will be performed in accordance to the aforementioned Standards, which contain certain limitations, exceptions, and exclusions.

4. The inspection and report are performed and prepared for the use of CLIENT, who gives INSPECTOR permission to discuss observations with real estate agents, owners, repair persons and other interested parties. INSPECTOR accepts no responsibility for use or misinterpretation by third parties.

5. INSPECTOR does not perform engineering, architectural, plumbing, or any other job function requiring an occupational license in the jurisdiction where the inspection is taking place, unless the inspector holds a valid occupational license, in which case he/she may inform the CLIENT that he/she is so licensed, and is therefore qualified to go beyond this basic home inspection, and for additional fee, perform additional inspections beyond those within the scope of the basic home inspection.

6. In the event of a claim against INSPECTOR, CLIENT agrees to supply INSPECTOR with the following: (1) Written notification of adverse conditions within 14 days of discovery, and (2) Access to the premises. Failure to comply with the above conditions will release INSPECTOR and its agents from any and all obligations.

7. HOLD HARMLESS AGREEMENT: CLIENT agrees to hold any and all real estate agents involved in the purchase of the property to be inspected harmless and keep them exonerated from all loss, damage, liability or expense occasioned or claimed by reasons of acts or neglects of the INSPECTOR or his employees or visitors or of independent contractors engaged or paid by INSPECTOR for the purpose of inspecting the subject home.

8. In the event that CLIENT fails to prove any adverse claims against INSPECTOR in a court of law, then the CLIENT will pay all legal costs, expenses and fees of INSPECTOR in defending said claims.

9. If any provision of this Agreement is declared invalid or unenforceable by any court, the remaining provisions will remain in effect. This agreement represents the entire agreement between the parties. No change or modification shall be enforceable against any party unless such change or modification is in writing and signed by the parties. This Agreement shall be binding upon and enforceable by the parties and their heirs, executors, administrators, successors and assigns. CLIENT shall have no cause of action against INSPECTOR after one year after from the date of the inspection.

10. Payment, by CLIENT or CLIENTs representative, is due in full at the inspection site, upon completion of the on-site inspection. The CLIENT will pay all legal and time expenses incurred in collecting due payments.




"A Home Inspection is a Non-Invasive Visual Examination of a Residential Dwelling. Components may include any combination of mechanical, structural, electrical, plumbing, or other essential systems or portions of the home, as identified and agreed to by the Client and Inspector, such as: Roof ~ Exterior ~ Basement / Foundation ~ Heating Cooling ~ Plumbing ~ Electrical ~ Fireplace ~ Attic & Insulation ~ Doors, Windows & Interior."
From NACHI Standards of Practice


"There are conditions that require the removal of some part of the building to observe, measure, or test otherwise concealed construction. Such intrusive inspections require some demolition and should be performed only with the permission of the owner and by experienced, qualified mechanics."
-From the U.S. Department of Housing and Urban Development's
Residential Rehabilitation Inspection Guide, 2000


- HOMES BEING INSPECTED DO NOT "PASS" OR "FAIL" -
A home inspector merely discloses his or her findings and reports those findings to the client. Everyone involved graduates to a state of higher learning, and the client can now make better informed decisions about the purchase of a home and its future needs of upkeep and repair.

Four key areas of most home/building inspections cover the exterior, the basement or crawlspace areas, the attic or crawlspace areas and the living areas. Inspectors typically will spend sufficient time in all of these areas to visually look for a host of red flags, tell-tale clues and signs or defects and deficiencies.

The inspected areas of a home/building will consist of all of the major visible and accessible electro-mechanical systems as well as the major visible and accessible structural systems and components of a building as they appeared and functioned at the time and date of the inspection.

Inspectors typically do not provide warranties or guaranties with their inspections and reports. Buyers should therefore not rely on the inspection as any form of insurance policy against any latent, hidden, concealed or future defects and deficiencies.

The following are also some key items that buyers should remember and consider when reviewing their inspection reports:
* Inspections are not code compliance evaluations.
* Inspection reports are not structural engineering reports.
* Systems and components that are off during the inspection are not tested or reactivated.
* Buyers should consult with and ask questions of owners and their representatives.
* Roof inspections and their components are typically done from eaves or street level with binoculars.
* Reports are confidential and are meant exclusively for buyers, and not brokers or owners.
* Inspectors typically will not find each and every defect in a building, hence buyers should anticipate future typical defects and deficiencies.
* Further evaluation by specialists is recommended for any areas showing defects/deficiencies.
* A final walk-through inspection should be carried out the day before closing by the new owners to double check the condition of the building.



Limitations:
I. An inspection is not technically exhaustive.
II. An inspection will not identify concealed or latent defects.
III. An inspection will not deal with aesthetic concerns or what could be deemed matters of taste, cosmetic, etc.
IV. An inspection will not determine the suitability of the property for any use.
V. An inspection does not determine the market value of the property or its marketability.
VI. An inspection does not determine the advisability or inadvisability of the purchase of the inspected property.
VII. An inspection does not determine the life expectancy of the property or any components or systems therein.
VIII. An inspection does not include items not permanently installed.
IX. These Standards of Practice apply only to homes with four or fewer dwelling units.

Exclusions:
I. The inspectors are not required to determine:
A. Property boundary lines or encroachments.
B. The condition of any component or system that is not readily accessible.
C. The service life expectancy of any component or system.
D. The size, capacity, BTU, performance, or efficiency of any component or system.
E. The cause or reason of any condition.
F. The cause for the need of repair or replacement of any system or component.
G. Future conditions.
H. The compliance with codes or regulations.
I. The presence of evidence of rodents, animals or insects.
J. The presence of mold, mildew or fungus.
K. The presence of air-borne hazards.
L. The presence of birds.
M. The presence of other flora or fauna.
N. The air quality.
O. The existence of asbestos.
P. The existence of environmental hazards.
Q. The existence of electro-magnetic fields.
R. The presence of hazardous materials including, but not limited to, the presence of lead in paint.
S. Any hazardous waste conditions.
T. Any manufacturer recalls or conformance with manufacturer installation or any information included in the consumer protection bulletin.
U. Operating costs of systems.
V. Replacement or repair cost estimates.
W. The acoustical properties of any systems.
X. Estimates of how much it will cost to run any given system.

II. The inspectors are not required to operate:
A. Any system that is shut down.
B. Any system that does not function properly.
C. Or evaluate low voltage electrical systems such as, but not limited to:
1. Phone lines.
2. Cable lines.
3. Antennae.
4. Lights.
5. Remote controls.
D. Any system that does not turn on with the use of normal operating controls.
E. Any shut off valve.
F. Any electrical disconnect or over current protection devices.
G. Any alarm systems.
H. Moisture meters, gas detectors or similar equipment.



III. The inspectors are not required to:

A. Move any personal items or other obstructions,
such as, but not limited to:

1. Throw rugs.
2. Furniture.
3. Floor or wall coverings.
4. Ceiling tiles
5. Window coverings.
6. Equipment.
7. Plants.
8. Ice.
9. Debris.
10. Snow.
11. Water.
12. Dirt.
13. Foliage.
14. Pets

B. Dismantle, open, or uncover any system or component.
C. Enter or access any area which may, in the opinion of the inspector, to be unsafe or risk personal safety.
D. Enter crawlspaces or other areas that are unsafe or not readily accessible.
E. Inspect underground items such as, but not limited to, underground storage tanks or other indications of their presence, whether abandoned or actively used.
F. Do anything which, in the inspector's opinion, is likely to be unsafe or dangerous to the inspector or others or damage property, such as, but not limited to, walking on roof surfaces, climbing ladders, entering attic spaces or negotiating with dogs.
G. Inspect decorative items.
H. Inspect common elements or areas in multi-unit housing.
I. Inspect intercoms, speaker systems, radio-controlled, security devices or lawn irrigation systems.
J. Offer guarantees or warranties.
K. Offer or perform any engineering services.
L. Offer or perform any trade or professional service other than home inspection.
M. Research the history of the property, report on its potential for alteration, modification, extendibility, or its suitability for a specific or proposed use for occupancy.
N. Determine the age of construction or installation of any system structure, or component of a building, or differentiate between original construction or subsequent additions, improvements, renovations or replacements thereto.
O. Determine the insurability of a property.