How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
Safety
Poses a safety hazard
Major Defect
Correction likely involves a significant expense
Repair/Replace
Recommend repairing or replacing
Repair/Maintain
Recommend repair and/or maintenance
Maintain
Recommend ongoing maintenance
Evaluate
Recommend evaluation by a specialist
Monitor
Recommend monitoring in the future
Comment
For your information
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Warm
Payment method: Credit card, 409.00
Type of building: Single family
Buildings inspected: One house, 4788 sq ft
Number of residential units inspected: 1
Age of main building: Built 1992
Source for main building age: Municipal records or property listing
Front of building faces: North
Main entrance faces: North
Occupied: Yes
1) Many areas and items at this property were obscured by . This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Minor slope
Condition of driveway: Required repair, replacement and/or evaluation (see comments below)
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Required repairs, replacement and/or evaluation (see comments below)
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Open, Covered (Refer to Roof section)
Condition of decks, porches and/or balconies: Required repairs, replacement and/or evaluation (see comments below)
Deck, porch and/or balcony material: Wood
Condition of stairs, handrails and guardrails: Required repairs, replacement and/or evaluation (see comments below)
Exterior stair material: Wood
2) One or more decks or porches were unstable due to missing or substandard bracing, or lack of attachment to main structure. This is a safety hazard since severe movement may cause the decks or porches to collapse. A qualified contractor should repair as necessary.
Photo 2-1 Photo 2-2
Photo 2-3 Photo 2-4
Photo 2-5 Photo 2-6
Photo 2-7 Photo 2-8
Photo 2-9 Photo 2-10
Photo 2-11 Photo 2-12
Photo 2-13 Photo 2-14
Photo 2-15 Photo 2-16
Photo 2-17 Photo 2-18
Photo 2-19 Photo 2-20
Photo 2-21 Photo 2-22
Photo 2-23 Photo 2-24
Photo 2-25 Photo 2-26
Photo 2-27 Photo 2-28
Photo 2-29 Photo 2-30
Photo 2-31 Photo 2-32
Photo 2-33 Photo 2-34
Photo 2-35 Photo 2-36
Photo 2-37 Photo 2-38
Photo 2-39 Photo 2-40
Photo 2-41 Photo 2-42
Photo 2-43 Photo 2-44
Photo 2-45 Photo 2-46
Photo 2-47 Photo 2-48
Photo 2-49 Photo 2-50
Photo 2-51
3) Ledger boards for one or more decks, balconies or porches appeared to be attached with nails only. This method of attachment is substandard and may result in such structures separating from the main building. This is a potential safety hazard. Modern standards call for ledger boards to be installed with 1/2 inch lag screws or bolts into solid backing, and brackets such as Simpson Strong Tie DTT2 brackets and threaded rod, connecting interior and exterior joists. Recommend that a qualified contractor repair per standard building practices. For more information, visit: https://www.reporthost.com/?LB https://www.reporthost.com/?SD
4) Flashing appeared to be missing from above one or more deck or porch ledger boards, or could not be verified. Missing flashing at this location can cause moisture to accumulate between the ledger boards and the building. Fungal rot may occur in this area and cause the ledger board fasteners to fail. The deck may separate from the building in this event. This is a potential safety hazard. Recommend that a qualified contractor install flashing above ledger boards per standard building practices. For more information, visit: https://www.reporthost.com/?LB https://www.reporthost.com/?SD
Photo 4-1 Photo 4-2
Photo 4-3 Photo 4-4
Photo 4-5 Photo 4-6
Photo 4-7 Photo 4-8
Photo 4-9 Photo 4-10
Photo 4-11 Photo 4-12
Photo 4-13 Photo 4-14
Photo 4-15 Photo 4-16
Photo 4-17
5) One or more sets of stairs were unstable and/or wobbly. A qualified contractor should repair as necessary. For example, by installing additional bracing or supports.
Photo 5-1 Photo 5-2
Photo 5-3 Photo 5-4
Photo 5-5 Photo 5-6
Photo 5-7
6) One or more deck, patio and/or porch covers were unstable due to substandard bracing, lack of diagonal bracing, or lack of attachment to the main building. This is a safety hazard since severe movement may cause the cover to collapse. A qualified contractor should repair as necessary.
Photo 6-1 Photo 6-2
Photo 6-3 Photo 6-4
Photo 6-5 Photo 6-6
Photo 6-7 Photo 6-8
Photo 6-9 Photo 6-10
Photo 6-11 Photo 6-12
Photo 6-13 Photo 6-14
Photo 6-15 Photo 6-16
Photo 6-17 Photo 6-18
Photo 6-19 Photo 6-20
Photo 6-21 Photo 6-22
Photo 6-23 Photo 6-24
Photo 6-25 Photo 6-26
Photo 6-27 Photo 6-28
Photo 6-29 Photo 6-30
Photo 6-31 Photo 6-32
Photo 6-33 Photo 6-34
Photo 6-35 Photo 6-36
Photo 6-37 Photo 6-38
Photo 6-39 Photo 6-40
7) Handrails at one or more flights of stairs were wobbly. This is a safety hazard. Recommend that a qualified person repair as necessary.
Photo 7-1 Photo 7-2
Photo 7-3 Photo 7-4
Photo 7-5
8) Fasteners for the deck, porch or balcony joist hangers were missing. Approved fasteners such as Teco nails should be installed in every nail hole in such hardware. Recommend that a qualified person install approved fasteners where necessary.
Photo 8-1 Photo 8-2
Photo 8-3 Photo 8-4
Photo 8-5 Photo 8-6
Photo 8-7 Photo 8-8
Photo 8-9 Photo 8-10
Photo 8-11 Photo 8-12
Photo 8-13 Photo 8-14
Photo 8-15 Photo 8-16
Photo 8-17 Photo 8-18
Photo 8-19 Photo 8-20
Photo 8-21 Photo 8-22
Photo 8-23 Photo 8-24
Photo 8-25 Photo 8-26
Photo 8-27 Photo 8-28
Photo 8-29 Photo 8-30
Photo 8-31 Photo 8-32
Photo 8-33 Photo 8-34
Photo 8-35 Photo 8-36
Photo 8-37
9) Cracks, holes, settlement, heaving and/or deterioration were found in the driveway. Recommend that qualified contractor repair as necessary.
Photo 9-1 Photo 9-2
Photo 9-3 Photo 9-4
Photo 9-5 Photo 9-6
Photo 9-7 Photo 9-8
Photo 9-9 Photo 9-10
Photo 9-11 Photo 9-12
Photo 9-13 Photo 9-14
Photo 9-15 Photo 9-16
Photo 9-17 Photo 9-18
Photo 9-19 Photo 9-20
Photo 9-21 Photo 9-22
Photo 9-23 Photo 9-24
Photo 9-25 Photo 9-26
Photo 9-27
10) The soil or grading sloped down towards building perimeters in one or more areas. This can result in water accumulating around building foundations or underneath buildings. At a minimum, monitor these areas, and areas under the structure in the future for accumulated water. If water does accumulate, recommend grading soil so it slopes down and away from buildings with a slope of at least 1 inch per horizontal foot for at least 6 feet out from buildings.
Photo 10-1 Photo 10-2
Photo 10-3 Photo 10-4
Photo 10-5 Photo 10-6
Photo 10-7 Photo 10-8
Photo 10-9 Photo 10-10
Photo 10-11 Photo 10-12
Photo 10-13 Photo 10-14
Photo 10-15 Photo 10-16
Photo 10-17 Photo 10-18
Photo 10-19 Photo 10-20
Photo 10-21 Photo 10-22
Photo 10-23 Photo 10-24
Photo 10-25 Photo 10-26
Photo 10-27 Photo 10-28
Photo 10-29 Photo 10-30
11) Pavement sloped down towards building perimeters in one or more areas. This may result in water accumulating around building foundations or underneath buildings. Monitor these areas in the future, especially during and after periods of rain. If significant amounts of water are found to accumulate, then recommend that a qualified contractor evaluate and repair as necessary. For example, by installing drain(s) or removing old pavement and installing new.
Photo 11-1 Photo 11-2
Photo 11-3 Photo 11-4
Photo 11-5 Photo 11-6
Photo 11-7 Photo 11-8
Photo 11-9 Photo 11-10
Photo 11-11 Photo 11-12
Photo 11-13 Photo 11-14
Photo 11-15 Photo 11-16
Photo 11-17 Photo 11-18
Photo 11-19 Photo 11-20
Photo 11-21 Photo 11-22
Photo 11-23 Photo 11-24
Photo 11-25 Photo 11-26
Photo 11-27 Photo 11-28
Photo 11-29 Photo 11-30
Photo 11-31 Photo 11-32
12) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in sidewalks or patios, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Wood fiber
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Unfinished basement, Finished basement
13) Some sections of siding and/or trim were deteriorated and/or damaged. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo 13-1 Photo 13-2
Photo 13-3 Photo 13-4
Photo 13-5 Photo 13-6
Photo 13-7 Photo 13-8
Photo 13-9 Photo 13-10
Photo 13-11 Photo 13-12
Photo 13-13 Photo 13-14
Photo 13-15 Photo 13-16
Photo 13-17
14) The masonry (brick or stone) veneer was deteriorated or damaged in some areas. Where cracks or openings are exposed, water can enter the wall structure causing mold, fungal growth and structural damage. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor repair as necessary. For example, by repointing mortar or replacing broken or missing masonry.
Photo 14-1 Photo 14-2
Photo 14-3 Photo 14-4
Photo 14-5 Photo 14-6
Photo 14-7 Photo 14-8
Photo 14-9 Photo 14-10
15) Untreated wood siding and/or trim was in contact with concrete or masonry at the exterior. Moisture collected between the two materials or wicking up into the wood is a conducive condition for wood-destroying organisms. Wood siding or trim should be installed with a minimum clearance of 1-2 inches between it and concrete or masonry below it at building exteriors. Monitor these areas for rot or infestation in the future and repair if needed. Recommend that a qualified person repair per standard building practices. For example, by trimming siding or trim as needed.
Photo 15-1 Photo 15-2
Photo 15-3 Photo 15-4
Photo 15-5 Photo 15-6
Photo 15-7 Photo 15-8
Photo 15-9 Photo 15-10
Photo 15-11 Photo 15-12
Photo 15-13 Photo 15-14
Photo 15-15 Photo 15-16
Photo 15-17 Photo 15-18
Photo 15-19 Photo 15-20
16) Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo 16-1 Photo 16-2
Photo 16-3 Photo 16-4
Photo 16-5 Photo 16-6
Photo 16-7 Photo 16-8
Photo 16-9 Photo 16-10
Photo 16-11 Photo 16-12
Photo 16-13 Photo 16-14
Photo 16-15 Photo 16-16
Photo 16-17 Photo 16-18
17) Trees were in contact with or were close to the building at one or more locations. Damage to the building can occur, especially during high winds, or may have already occurred (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.
Photo 17-1 Photo 17-2
Photo 17-3 Photo 17-4
Photo 17-5 Photo 17-6
Photo 17-7
18) Caulk was in some areas. For example, around windows and/or around doors. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit: https://www.reporthost.com/?CAULK
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.
Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Wood
Beam material: Solid wood
Floor structure above: Solid wood joists
Condition of insulation underneath floor above: Appeared serviceable
Insulation material underneath floor above: Fiberglass roll or batt
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Viewed from ground, Viewed from ground with binoculars
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Required repair, replacement and/or evaluation (see comments below)
19) Stains were found on one or more gutters that indicate past leaks have occurred. However, the inspector was unable to verify that the gutters do or don't leak because of lack of recent rainfall. Monitor the gutters in the future while it's raining to determine if gutters leak. If they do, then recommend that a qualified person repair as necessary to prevent water from coming in contact with the building or accumulating around the building foundation.
20) Stains were found at the front of one or more gutters and indicate that the gutters have overflowed. If they have overflowed, it's usually due to debris clogging gutters or downspouts. The inspector was unable to verify that the gutters and downspouts drained adequately due to lack of recent, significant rainfall. Monitor the roof drainage system in the future while it's raining to determine if problems exist. Then if necessary, recommend that a qualified person clean, repair or replace gutters, downspouts and/or extensions.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Traversed
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Mineral wool roll or batt
Approximate attic insulation R value (may vary in areas): R-30
Vermiculite insulation present: None visible
Vapor retarder: None
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Gable end vents, Enclosed soffit vents
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of door between garage and house: Appeared serviceable
Type of door between garage and house: Solid core
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Condition of automatic opener(s): Appeared serviceable
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: Exists
21) Minor cracks were found in the concrete slab floor. These are common and appeared to be only a cosmetic issue.
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Service voltage (volts): 120-240
Estimated service amperage: 150
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Not determined (components inaccessible or obscured)
Main disconnect rating (amps): 150
System ground: Ground rod(s) in soil
Condition of main service panel: Appeared serviceable
Condition of sub-panel(s): Appeared serviceable
Location of main service panel #A: Basement
Location of main disconnect: No single main disconnect, use all breakers in main service panel
Carbon monoxide alarms installed: Yes, but not tested
22) One or more standard exterior electric receptacles were being used for appliances or systems that were constantly in use. This is a safety hazard for shock since water can reach receptacle slots. Recommend that a qualified person install "while in use" receptacle covers as necessary. For more information, visit: https://www.reporthost.com/?INUSECVR
23) Several lights not working ( Client stated many bulbs recently blown)
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Water pressure (psi): 45
Location of main water shut-off: Basement
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: No
Location of main fuel shut-off valve: At gas meter
24) A fire suppression system was installed on the premises. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. These systems normally require periodic inspection by a specialist to ensure correct operation. For example, checking for possible backflow contamination of the potable water system, or correct operation of valves and gauges. Recommend that a qualified specialist inspect this system in accordance with National Fire Prevention Association (NFPA) 25 standards.
Photo 24-1 Photo 24-2
Photo 24-3
25) One or more water shut-off valves were not labeled, and their function is unknown. Recommend consulting with the property owner to determine valves' functions, that you verify this yourself, or if necessary that a qualified plumber evaluate. Recommend labeling valves as necessary.
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Furnace
General heating distribution type(s): Ducts and registers
Source for last service date of primary heat source: Client
Condition of forced air heating/(cooling) system: Appeared serviceable
Estimated age of forced air furnace: 2007 Basement/ attic 1992
Location of forced air furnace: Basement, Attic
Condition of furnace filters: Required replacement
Location for forced air filter(s): At base of air handler
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location of heat pump or air conditioning unit: Building exterior, east
Type: Split system
Condition of controls: Appeared serviceable
26) The last service date of the gas or oil-fired forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC contractor when it's serviced. For more information visit: https://www.reporthost.com/?ANFURINSP
Photo 26-1 Photo 26-2
Photo 26-3 Photo 26-4
Photo 26-5 Photo 26-6
Photo 26-7
27) The estimated useful life for most heat pumps and air conditioning condensing units is 10-15 years. The inspector was unable to determine the age of this unit. Be aware that it may be near, at, or beyond its useful life and may need replacing or significant repairs at any time. Recommend attempting to determine the age (ask property owner or service technician), and budgeting for a replacement if necessary.
Photo 27-1 Photo 27-2
Photo 27-3 Photo 27-4
Photo 27-5
28) The estimated useful life for most forced air furnaces is 15-20 years. This furnace appeared to be near and/or beyond this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
Basement 2007 (13)/ Attic 1992 (28)
Photo 28-1 Photo 28-2
Photo 28-3 Photo 28-4
Photo 28-5 Photo 28-6
29) The estimated useful life for most heat pumps and air conditioning condensing units is 10-15 years. This unit appeared to be this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
30) 1.Forced Air Heating system was leaking in basement ( No catch Pan) 2. Pump had a cut/slice in electrical cord
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Required repair, replacement and/or evaluation (see comments below)
Condition of gas-fired fireplaces or stoves: Required repair, replacement and/or evaluation (see comments below)
Gas fireplace or stove type: Converted wood-burning fireplace
Condition of chimneys and flues: Appeared serviceable
Gas-fired flue type: B-vent
31) One or more solid fuel-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all solid fuel-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at: https://www.reporthost.com/?CSIA
32) Recommend that the client review all available documentation for gas-fired fireplaces and stoves. Depending on how they are operated (for routine heating versus ambiance), such appliances may need servicing annually or every few years. Consult with the property owner and/or a qualified specialist to determine if service is needed now. Any needed repairs noted in this report should be brought to the attention of the specialist when it's serviced. For more information visit: https://www.reporthost.com/?ANGFINSP
33) The gas fireplace or stove was not fully evaluated because the pilot light was off or a lighting procedure was required. The inspector only operates normal controls (e.g. on/off switch or thermostat) and does not light pilot lights or operate gas shut-off valves. Recommend that the client review all documentation for such gas appliances and familiarize themselves with the lighting procedure. If necessary, a qualified specialist should assist in lighting such appliances, and make any needed repairs.
Photo 33-1 Photo 33-2
Photo 33-3 Photo 33-4
Photo 33-5 Photo 33-6
Photo 33-7 Photo 33-8
Photo 33-9 Photo 33-10
Photo 33-11
34) One or more gas fireplaces or stoves did not respond to normal controls (e.g. on/off switch, thermostat, remote control) and were not fully evaluated as a result. The pilot light or gas supply may have been turned off, or some other condition may have prevented operation. The inspector only operates normal controls and does not light pilot lights or operate gas shut-off valves. Consult with the property owner, review all documentation for such gas appliances, and become familiar with the lighting procedure. If necessary, a qualified specialist should assist in lighting such appliances, and make any needed repairs.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of ranges, cooktops and/or ovens: Appeared serviceable
Range, cooktop, oven type: Electric
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: Appeared serviceable
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath, Master bath
Location #B: Full bath, second floor
Location #C: Full bath, first floor
Location #D: Half bath, first floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Windows, Spot exhaust fans
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: Yes
35) The bathroom with a shower or bathtub at location(s) # didn't have an exhaust fan installed. Moisture can accumulate and result in mold, bacteria or fungal growth. Even if the bathroom has a window that opens, it may not provide adequate ventilation, especially during cold weather when windows are closed or when wind blows air into the bathroom. Recommend that a qualified contractor install exhaust fans per standard building practices where missing in bathrooms with showers or bathtubs.
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Exterior door material: Wood
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Wood
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Flooring type or covering: Carpet, Wood or wood products
Condition of stairs, handrails and guardrails: Appeared serviceable
36) One or more bedrooms had windows that wouldn't open or were stuck shut. Unless a bedroom has an exterior entry door, at least one window requires adequate egress in the event of a fire or emergency to allow escape or to allow access by emergency personnel. Recommend that a qualified contractor repair or make modifications per standard building practices. For more information, visit: https://www.reporthost.com/?EGRESS
Photo 36-1 Photo 36-2
37) One or more windows that were designed to open and close were stuck shut. Recommend that a qualified person repair windows as necessary so they open and close easily.
Photo 37-1 Photo 37-2
Photo 37-3 Photo 37-4
Photo 37-5 Photo 37-6
Photo 37-7 Photo 37-8
Photo 37-9 Photo 37-10
Photo 37-11 Photo 37-12
Photo 37-13 Photo 37-14
Photo 37-15 Photo 37-16
Photo 37-17 Photo 37-18
Photo 37-19 Photo 37-20
38) One or more window screens were damaged or deteriorated. These window(s) may not provide ventilation during months when insects are active. Recommend replacing window screens as necessary.
Photo 38-1 Photo 38-2
Photo 38-3 Photo 38-4
Photo 38-5
39) One or more exterior doors had minor damage and/or deterioration. Although serviceable, the client may wish to repair or replace such doors for appearances' sake.
Photo 39-1 Photo 39-2
Photo 39-3 Photo 39-4
Photo 39-5 Photo 39-6
Photo 39-7 Photo 39-8
Photo 39-9 Photo 39-10
Photo 39-11 Photo 39-12
Photo 39-13 Photo 39-14
Photo 39-15 Photo 39-16
Photo 39-17 Photo 39-18
Photo 39-19 Photo 39-20
40) Screens were missing from some windows. These windows may not provide ventilation during months when insects are active.
Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: No
Visible evidence of active wood decay fungi: No
Visible evidence of past wood-destroying insects: No
Visible evidence of past wood decay fungi: No
Visible evidence of damage by wood-destroying insects: No
Visible evidence of damage by wood decay fungi: No
Visible evidence of conditions conducive to wood-destroying organisms: No
Photo X-1 Photo X-2
Photo X-3 Photo X-4
Photo X-5 Photo X-6
Photo X-7 Photo X-8
Photo X-9 Photo X-10
Photo X-11 Photo X-12
Photo X-13 Photo X-14
Photo X-15 Photo X-16
Photo X-17 Photo X-18
Photo X-19 Photo X-20
Photo X-21 Photo X-22
Photo X-23 Photo X-24
Photo X-25 Photo X-26
Photo X-27 Photo X-28
Photo X-29 Photo X-30
Photo X-31 Photo X-32
Photo X-33 Photo X-34
Photo X-35 Photo X-36
Photo X-37 Photo X-38
Photo X-39 Photo X-40
Photo X-41 Photo X-42
Photo X-43 Photo X-44
Photo X-45 Photo X-46
Photo X-47 Photo X-48
Photo X-49 Photo X-50
Photo X-51 Photo X-52
Photo X-53 Photo X-54
Photo X-55 Photo X-56
Photo X-57 Photo X-58
Photo X-59 Photo X-60
Photo X-61 Photo X-62
Photo X-63 Photo X-64
Photo X-65 Photo X-66
Photo X-67 Photo X-68
Photo X-69 Photo X-70
Photo X-71 Photo X-72
Photo X-73 Photo X-74
Photo X-75 Photo X-76
Photo X-77 Photo X-78
Photo X-79 Photo X-80
Photo X-81 Photo X-82
Photo X-83 Photo X-84
Photo X-85 Photo X-86
Photo X-87 Photo X-88
Photo X-89 Photo X-90
Photo X-91 Photo X-92
Photo X-93 Photo X-94
Photo X-95 Photo X-96
Photo X-97 Photo X-98
Photo X-99 Photo X-100
Photo X-101 Photo X-102
Photo X-103 Photo X-104
Photo X-105 Photo X-106
Photo X-107 Photo X-108
Photo X-109 Photo X-110
Photo X-111 Photo X-112
Photo X-113 Photo X-114
Photo X-115 Photo X-116
Photo X-117 Photo X-118
Photo X-119 Photo X-120
Photo X-121 Photo X-122
Photo X-123 Photo X-124
Photo X-125 Photo X-126
Photo X-127 Photo X-128
Photo X-129 Photo X-130
Photo X-131 Photo X-132
Photo X-133 Photo X-134
Photo X-135 Photo X-136
Photo X-137 Photo X-138
Photo X-139 Photo X-140
Photo X-141 Photo X-142
Photo X-143 Photo X-144
Photo X-145 Photo X-146
Photo X-147 Photo X-148
Photo X-149 Photo X-150
Photo X-151 Photo X-152
Photo X-153 Photo X-154
Photo X-155 Photo X-156
Photo X-157 Photo X-158
Photo X-159 Photo X-160
Photo X-161 Photo X-162
Photo X-163 Photo X-164
Photo X-165 Photo X-166
Photo X-167 Photo X-168
Photo X-169 Photo X-170
Photo X-171 Photo X-172
Photo X-173 Photo X-174
Photo X-175 Photo X-176
Photo X-177 Photo X-178
Photo X-179 Photo X-180
Photo X-181 Photo X-182
Photo X-183 Photo X-184
Photo X-185 Photo X-186
Photo X-187 Photo X-188
Photo X-189 Photo X-190
Photo X-191 Photo X-192
Photo X-193 Photo X-194
Photo X-195 Photo X-196
Photo X-197 Photo X-198
Photo X-199 Photo X-200
Photo X-201 Photo X-202
Photo X-203 Photo X-204
Photo X-205 Photo X-206
Photo X-207 Photo X-208
Photo X-209 Photo X-210
Photo X-211 Photo X-212
Photo X-213 Photo X-214
Photo X-215 Photo X-216
Photo X-217 Photo X-218
Photo X-219 Photo X-220
Photo X-221 Photo X-222
Photo X-223 Photo X-224
Photo X-225 Photo X-226
Photo X-227 Photo X-228
Photo X-229 Photo X-230
Photo X-231 Photo X-232
Photo X-233 Photo X-234
Photo X-235 Photo X-236
Photo X-237 Photo X-238
Photo X-239 Photo X-240
Photo X-241 Photo X-242
Photo X-243 Photo X-244
Photo X-245 Photo X-246
Photo X-247 Photo X-248
Photo X-249 Photo X-250
Photo X-251 Photo X-252
Photo X-253 Photo X-254
Photo X-255 Photo X-256
Photo X-257 Photo X-258
Photo X-259 Photo X-260
Photo X-261 Photo X-262
Photo X-263 Photo X-264
Photo X-265 Photo X-266
Photo X-267 Photo X-268 A/C unit off balance by 1 inch
Photo X-269 imbalanced A/C unit not level Photo X-270
Photo X-271 Photo X-272
Photo X-273 Photo X-274
Photo X-275 Photo X-276
Photo X-277 Photo X-278
Photo X-279 Photo X-280
Photo X-281 Photo X-282
Photo X-283 Photo X-284
Photo X-285 Photo X-286
Photo X-287 Photo X-288
Photo X-289 Photo X-290
Photo X-291 Photo X-292
Photo X-293 Photo X-294
Photo X-295 Photo X-296
Photo X-297 Photo X-298
Photo X-299 Photo X-300
Photo X-301 Photo X-302 failing gutter seams
Photo X-303 Photo X-304
Photo X-305 Photo X-306
Photo X-307 over saturation external moisture in wood trim and soffit Photo X-308
Photo X-309 Photo X-310
Photo X-311 Photo X-312
Photo X-313 Photo X-314
Photo X-315 Photo X-316
Photo X-317 Photo X-318
Photo X-319 Photo X-320
Photo X-321 Photo X-322
Photo X-323 Photo X-324
Photo X-325 Photo X-326
Photo X-327 Photo X-328
Photo X-329 Photo X-330
Photo X-331 Photo X-332
Photo X-333 Photo X-334
Photo X-335 Photo X-336
Photo X-337 Photo X-338
Photo X-339 Photo X-340
Photo X-341 Photo X-342
Photo X-343 Photo X-344
Photo X-345 Photo X-346
Photo X-347 Photo X-348
Photo X-349 Photo X-350
Photo X-351 Photo X-352
Photo X-353 Photo X-354
Photo X-355 Photo X-356
Photo X-357 Photo X-358
Photo X-359 Photo X-360
Photo X-361 Photo X-362
Photo X-363 Photo X-364
Photo X-365 Photo X-366
Photo X-367 Photo X-368
Photo X-369 Photo X-370
Photo X-371 Photo X-372
Photo X-373 Photo X-374
Photo X-375 Photo X-376 loose floor vent near kitchen entrance
Photo X-377 Photo X-378
Photo X-379 Photo X-380
Photo X-381 Photo X-382 Gas valve under deck to fireplace
Photo X-383 Photo X-384
Photo X-385 Photo X-386
Photo X-387 Photo X-388
Photo X-389 Photo X-390
Photo X-391 Photo X-392
Photo X-393 Photo X-394
Photo X-395 Photo X-396
Photo X-397 Photo X-398
Photo X-399 Photo X-400
Photo X-401 Photo X-402
Photo X-403 Photo X-404
Photo X-405 Photo X-406
Photo X-407 Photo X-408
Photo X-409 Photo X-410
Photo X-411 Photo X-412
Photo X-413 Photo X-414
Photo X-415 Photo X-416
Photo X-417 Photo X-418
Photo X-419 Photo X-420
Photo X-421 Photo X-422
Photo X-423 Photo X-424
Photo X-425 Photo X-426
Photo X-427 Photo X-428
Photo X-429 Photo X-430
Photo X-431 Photo X-432
Photo X-433 Photo X-434
Photo X-435 Photo X-436
Photo X-437 Photo X-438
Photo X-439 Photo X-440
Photo X-441 Photo X-442
Photo X-443 Photo X-444
Photo X-445 Photo X-446
Photo X-447 Photo X-448
Photo X-449 Photo X-450
Photo X-451 Photo X-452
Photo X-453 Photo X-454
Photo X-455 Photo X-456
Photo X-457 Photo X-458
Photo X-459 Photo X-460
Photo X-461 Photo X-462
Photo X-463 Photo X-464
Photo X-465 Photo X-466
Photo X-467 Photo X-468
Photo X-469 Photo X-470
Photo X-471 Photo X-472
Photo X-473 Photo X-474
Photo X-475 Photo X-476
Photo X-477 Photo X-478
Photo X-479 Photo X-480
Photo X-481 Photo X-482
Photo X-483 Photo X-484
Photo X-485 Photo X-486
Photo X-487 Photo X-488
Photo X-489 Photo X-490
Photo X-491 Photo X-492
Photo X-493 Photo X-494
Photo X-495 Photo X-496
Photo X-497 Photo X-498
Photo X-499 Photo X-500
Photo X-501 Photo X-502
Photo X-503 Photo X-504
Photo X-505 Photo X-506
Photo X-507 Photo X-508
Photo X-509 Photo X-510
Photo X-511 Photo X-512
Photo X-513 Photo X-514
Photo X-515 Photo X-516
Photo X-517 Photo X-518
Photo X-519 Photo X-520
Photo X-521 Photo X-522
Photo X-523 Photo X-524
Photo X-525 Photo X-526
Photo X-527 Photo X-528
Photo X-529 Photo X-530
Photo X-531 Photo X-532
Photo X-533 Photo X-534
Photo X-535 Photo X-536
Photo X-537 Photo X-538
Photo X-539 Photo X-540
Photo X-541 Photo X-542
Photo X-543 Photo X-544
Photo X-545 Photo X-546
Photo X-547 Photo X-548
Photo X-549 Photo X-550
Photo X-551 Photo X-552
Photo X-553 Photo X-554
Photo X-555 Photo X-556
Photo X-557 Photo X-558
Photo X-559 Photo X-560
Photo X-561 Photo X-562
Photo X-563 Photo X-564
Photo X-565 Photo X-566
Photo X-567 Photo X-568
Photo X-569 Photo X-570
Photo X-571 Photo X-572
Photo X-573 Photo X-574
Photo X-575 Photo X-576
Photo X-577 Photo X-578
Photo X-579 Photo X-580
Photo X-581 Photo X-582
Photo X-583 Photo X-584
Photo X-585 Photo X-586
Photo X-587 Photo X-588
Photo X-589 Photo X-590
Photo X-591 Photo X-592
Photo X-593 Photo X-594
Photo X-595 Photo X-596
Photo X-597 Photo X-598
Photo X-599 Photo X-600
Photo X-601 Photo X-602
Photo X-603 Photo X-604
Photo X-605 Photo X-606
Photo X-607 Photo X-608
Photo X-609 Photo X-610
Photo X-611 Photo X-612
Photo X-613 Photo X-614
Photo X-615 Photo X-616
Photo X-617 Photo X-618
Photo X-619 Photo X-620
Photo X-621 Photo X-622
Photo X-623 Photo X-624
Photo X-625 Photo X-626
Photo X-627 Photo X-628
Photo X-629 Photo X-630
Photo X-631 Photo X-632
Photo X-633 Photo X-634
Photo X-635 Photo X-636
Photo X-637 Photo X-638
Photo X-639 Photo X-640
Photo X-641 Photo X-642
Photo X-643 Photo X-644
Photo X-645 Photo X-646
Photo X-647 insulation fallen down or over stored in attic Photo X-648
Photo X-649 Photo X-650
Photo X-651 Photo X-652
Photo X-653 Photo X-654 previous water damages from previously leaking roof
Photo X-655 Photo X-656
Photo X-657 Photo X-658
Photo X-659 Photo X-660
Photo X-661 Photo X-662
Photo X-663 Photo X-664
Photo X-665 Photo X-666
Photo X-667 Photo X-668
Photo X-669 Photo X-670
Photo X-671 Photo X-672
Photo X-673 Photo X-674
Photo X-675 Photo X-676
Photo X-677 Photo X-678
Photo X-679 Photo X-680
Photo X-681 Photo X-682
Photo X-683 Photo X-684
Photo X-685 Photo X-686
Photo X-687 Photo X-688
Photo X-689 Photo X-690
Photo X-691 Photo X-692
Photo X-693 Photo X-694
Photo X-695 Photo X-696
Photo X-697 Photo X-698
Photo X-699 Photo X-700
Photo X-701 Photo X-702
Photo X-703 Photo X-704
Photo X-705 Photo X-706
Photo X-707 Photo X-708
Photo X-709 Photo X-710
This Inspection was visual only and was performed at the request of the client listed this inspection and report is considered comprehensive not exhaustive there are discoveries all along the process and other discoveries may be found completely through to the final inspection by the client any further discoveries found by the client may be included in this report up until the final inspection only if the discoveries are brought to the attention of the inspector 3 days before closing. The inspector and inspection company listed are not held liable to any repairs or discoveries from any repairs made after this inspection date.