This report published on Tuesday, September 29, 2020 10:59:46 AM EDT
This report is the exclusive property of this inspection company All Secure Home Inspections LLC and the client(s)Kennedi Woods listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
Safety
Poses a safety hazard
Repair/Replace
Recommend repairing or replacing
Repair/Maintain
Recommend repair and/or maintenance
Maintain
Recommend ongoing maintenance
Evaluate
Recommend evaluation by a specialist
Monitor
Recommend monitoring in the future
Comment
For your information
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Minor slope
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Open
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Wood
Condition of stairs, handrails and guardrails: Appeared serviceable
Exterior stair material: Wood
1) The soil or grading sloped down towards building perimeters in one or more areas. This can result in water accumulating around building foundations or underneath buildings. At a minimum, monitor these areas, and areas under the structure in the future for accumulated water. If water does accumulate, recommend grading soil so it slopes down and away from buildings with a slope of at least 1 inch per horizontal foot for at least 6 feet out from buildings.
Photo 1-1 Photo 1-2
Photo 1-3 Photo 1-4
Photo 1-5 Photo 1-6
Photo 1-7
2) Pavement sloped down towards building perimeters in one or more areas. This may result in water accumulating around building foundations or underneath buildings. Monitor these areas in the future, especially during and after periods of rain. If significant amounts of water are found to accumulate, then recommend that a qualified contractor evaluate and repair as necessary. For example, by installing drain(s) or removing old pavement and installing new.
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Wood
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Crawl space
Foundation/stem wall material: Concrete block, Stone, Preserved wood foundation
Footing material (under foundation stem wall): Poured in place concrete, Pre-cast concrete
3) Gaps were found between the bottom of one or more support posts and the footing or pier below. Such support posts don't transfer loads to the footing below. Floors and/or the structure can deflect, resulting in non-level floors or damage to the structure. Recommend that a qualified contractor repair as necessary.
4) Trees were in contact with or were close to the building at one or more locations. Damage to the building can occur, especially during high winds, or may have already occurred (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.
The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Traversed
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Wood, Bearing wall
Beam material: Solid wood
Floor structure above: Solid wood joists
Condition of insulation underneath floor above: Appeared serviceable
Insulation material underneath floor above: Fiberglass roll or batt
Condition of vapor barrier: Required repairs, replacement and/or evaluation (see comments below)
Vapor barrier present: Yes
Condition of crawl space ventilation: Appeared serviceable
Ventilation type: with vents
5) Evidence of prior water intrusion or accumulation was found in one or more sections of the crawl space. For example, sediment stains on the vapor barrier or foundation, and/or efflorescence on the foundation. Accumulated water is a conducive condition for wood-destroying organisms and should not be present in the crawl space. Recommend that the client review any disclosure statements available and ask the property owner about past accumulation of water in the crawl space. The crawl space should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, then recommend that a qualified contractor who specializes in drainage issues evaluate and repair as necessary. Typical repairs for preventing water from accumulating in crawl spaces include:
Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
Improving perimeter grading
Repairing, installing or improving underground footing and/or curtain drains
Ideally, water should not enter crawl spaces, but if water must be controlled after it enters the crawl space, then typical repairs include installing trenches, gravity drains and/or sump pump(s) in the crawl space.
Photo 5-1 Photo 5-2
Photo 5-3 Photo 5-4
Photo 5-5 Photo 5-6
Photo 5-7 Photo 5-8
6) One or more indoor crawl space access hatches or doors were not insulated, or had substandard insulation. Recommend installing insulation as necessary and per current standards at hatches or doors for better energy efficiency.
7) One or more support posts appear to have been added since the original construction based on the inspector's observations. Such posts may have been added to reduce bounce or sag in floors above. Consult with the property owner about this, or have a qualified contractor evaluate and make repairs if necessary.
Photo 7-1 Photo 7-2
Photo 7-3 Photo 7-4
Photo 7-5 Photo 7-6
Photo 7-7 Photo 7-8
Photo 7-9 Photo 7-10
Photo 7-11 Photo 7-12
8) Under-floor insulation was falling down in some areas. This may result in reduced energy efficiency. Recommend that a qualified person repair or replace insulation as necessary.
Photo 8-1 Photo 8-2
Photo 8-3 Photo 8-4
Photo 8-5 Photo 8-6
Photo 8-7 Photo 8-8
9) The vapor barrier in some areas of the crawl space was missing. Soil was exposed as a result and will allow water from the soil to evaporate up into the structure. This is a conducive condition for wood-destroying organisms. A 6 mil black plastic sheet should be placed over all exposed soil with seams overlapped to 24 inches, and not in contact with any wood structural components. The sheeting should be held in place with bricks or stones, not wood. Recommend that a qualified person replace or repair the vapor barrier where necessary and per standard building practices.
Photo 9-1 Photo 9-2
Photo 9-3 Photo 9-4
Photo 9-5 Photo 9-6
Photo 9-7 Photo 9-8
Photo 9-9 Photo 9-10
Photo 9-11 Photo 9-12
Photo 9-13 Photo 9-14
Photo 9-15 Photo 9-16
Photo 9-17 Photo 9-18
Photo 9-19 Photo 9-20
Photo 9-21 Photo 9-22
Photo 9-23 Photo 9-24
Photo 9-25 Photo 9-26
Photo 9-27 Photo 9-28
Photo 9-29 Photo 9-30
Photo 9-31 Photo 9-32
10) Minor amounts of standing water were found at one or more locations in the crawl space. Some minor seasonal water accumulation can be normal. However significant amounts of Water may evaporate and enter the structure above causing high levels of moisture in the structure. This can be a conducive condition for wood-destroying organisms. Rain runoff is the most common cause of wet crawl spaces but water can come from other sources such as groundwater or underground springs. Recommend monitoring the crawl space in the future, especially after heavy and/or prolonged periods of rain. Correct any issues related to outside perimeter grading and/or roof drainage (see any other comments about this in this report). Also, review any disclosure statements available and ask the property owner about past accumulation of water in the crawl space.
If standing water persists or increases in amount, recommend that a qualified contractor who specializes in drainage issues evaluate and repair as necessary. Typically such repairs include:
Repairing, installing or improving underground footing and/or curtain drains
Applying waterproof coatings to foundation walls
Digging trenches in the crawl space to collect or divert water
Installing sump pumps
Photo 10-1 Photo 10-2
Photo 10-3 Photo 10-4
11) One or more indoor crawl space access hatches or doors were not insulated, or had substandard insulation. Weatherstripping was also missing or substandard. Recommend installing weatherstripping and insulation per current standards at hatches or doors for better energy efficiency and to prevent dust or odor-laden air from the crawl space entering living spaces.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Traversed
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable, Flat or low slope
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable
12) Extensions such as splash blocks or drain pipes for one or more downspouts were missing. Water can accumulate around the building foundation or inside crawl spaces or basements as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Traversed
Condition of roof structure: Appeared serviceable
Ceiling structure: Ceiling beams
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass loose fill
Approximate attic insulation R value (may vary in areas): R-30
Vermiculite insulation present: None visible
Vapor retarder: None
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Open soffit vents
13) One or more recessed lights were installed in the attic and were in contact with insulation. The inspector was unable to find a label or markings that indicated that these lights are designed to be in contact with insulation. If lights are not "IC" rated then this is a fire hazard. Recommend further evaluation by a qualified contractor to determine if these lights are rated for contact with insulation. If they aren't, or if their rating can't be determined, then recommend that a qualified person make permanent repairs as necessary. For example, by installing shields around lights or moving insulation.
Photo 13-1 Photo 13-2
Photo 13-3 Photo 13-4
14) One or more soffit vents were blocked by insulation. This can reduce air flow through the roof structure or attic and result in reduced service life for the roof surface materials because of high temperatures. Moisture from condensation is also likely to accumulate in the roof structure and/or attic and can be a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary so air flows freely through all vents. For example, by moving or removing insulation and installing cardboard baffles.
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Service voltage (volts): 120-240
Estimated service amperage: 150
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 150
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Living room
Location of main disconnect: No single main disconnect, use all breakers in main service panel
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Location of main water shut-off: In hall closet, In utility room
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper, PEX plastic
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: No
Condition of fuel system: Appeared serviceable
Location of main fuel shut-off valve: At gas meter
15) A fire suppression system was installed on the premises. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. These systems normally require periodic inspection by a specialist to ensure correct operation. For example, checking for possible backflow contamination of the potable water system, or correct operation of valves and gauges. Recommend that a qualified specialist inspect this system in accordance with National Fire Prevention Association (NFPA) 25 standards.
16) One or more water shut-off valves were not labeled, and their function is unknown. Recommend consulting with the property owner to determine valves' functions, that you verify this yourself, or if necessary that a qualified plumber evaluate. Recommend labeling valves as necessary.
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Electricity
Estimated age: 2020
Capacity (in gallons): Not determined (label obscure or inaccessible), est 40 gal
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air
General heating distribution type(s): Ducts and registers
Last service date of primary heat source: New
Source for last service date of primary heat source: Label
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: 2020
Location of forced air furnace: Attic
Condition of furnace filters: N/A (none visible)
Location for forced air filter(s): Inside air handler
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location of heat pump or air conditioning unit: Building exterior
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of ranges, cooktops and/or ovens: Appeared serviceable
Range, cooktop, oven type: Natural gas
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: Appeared serviceable
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath, Master bath
Location #B: Full bath
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Central exhaust fan
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes
17) Caulk around the base of the toilet at location(s) #A and B was missing, substandard and/or deteriorated. Modern standards require caulk to be installed around the entire toilet base where it meets the floor for sanitary reasons. Without it, soiled water can soak into flooring and sub-floor materials if the toilet overflows. Condensation from the toilet can also soak into the flooring. Recommend that a qualified person caulk around toilet bases per standard building practices.
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Vinyl
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Flooring type or covering: Vinyl, linoleum or marmoleum, Wood or wood products
18) Floors in one or more areas were not level. This can be caused by foundation settlement or movement of the foundation, posts and/or beams. Significant repairs may be needed to make floors level. Recommend that a qualified contractor and/or engineer evaluate further. Repairs should be performed by a qualified contractor.
Photo 18-1 Photo 18-2
Photo 18-3 Photo 18-4
19) Screens were missing from some windows. These windows may not provide ventilation during months when insects are active.
Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: No
Visible evidence of active wood decay fungi: No
Visible evidence of past wood-destroying insects: No
Visible evidence of past wood decay fungi: No
Visible evidence of damage by wood decay fungi: No
Visible evidence of conditions conducive to wood-destroying organisms: No
Photo X-1 Photo X-2
Photo X-3 Photo X-4
Photo X-5 Photo X-6
Photo X-7 Photo X-8
Photo X-9 Photo X-10
Photo X-11 Photo X-12
Photo X-13 Photo X-14
Photo X-15 Photo X-16
Photo X-17 Photo X-18
Photo X-19 Photo X-20
Photo X-21 Photo X-22
Photo X-23 Photo X-24
Photo X-25 Photo X-26
Photo X-27 Photo X-28
Photo X-29 Photo X-30
Photo X-31 Photo X-32
Photo X-33 Photo X-34
Photo X-35 Photo X-36
Photo X-37 Photo X-38
Photo X-39 Photo X-40
Photo X-41 Photo X-42
Photo X-43 Photo X-44
Photo X-45 Photo X-46
Photo X-47 Photo X-48
Photo X-49 Photo X-50
Photo X-51 Photo X-52
Photo X-53 Photo X-54
Photo X-55 Photo X-56
Photo X-57 Photo X-58
Photo X-59 Photo X-60
Photo X-61 Photo X-62
Photo X-63 Photo X-64
Photo X-65 Photo X-66
Photo X-67 Photo X-68
Photo X-69 Photo X-70
Photo X-71 Photo X-72
Photo X-73 Photo X-74
Photo X-75 Photo X-76
Photo X-77 Photo X-78
Photo X-79 Photo X-80
Photo X-81 Photo X-82
Photo X-83 Photo X-84
Photo X-85 Photo X-86
Photo X-87 Photo X-88
Photo X-89 Photo X-90
Photo X-91 Photo X-92
Photo X-93 Photo X-94
Photo X-95 Photo X-96
Photo X-97 Photo X-98
Photo X-99 Photo X-100
Photo X-101 Photo X-102
Photo X-103 Photo X-104
Photo X-105 Photo X-106
Photo X-107 Photo X-108
Photo X-109 Photo X-110
Photo X-111 Photo X-112
Photo X-113 Photo X-114
Photo X-115 Photo X-116
Photo X-117 Photo X-118
Photo X-119 Photo X-120
Photo X-121 Photo X-122
Photo X-123 Photo X-124
Photo X-125 Photo X-126
Photo X-127 Photo X-128
Photo X-129 Photo X-130
Photo X-131 Photo X-132
Photo X-133 Photo X-134
Photo X-135 Photo X-136
Photo X-137 Photo X-138
Photo X-139 Photo X-140
Photo X-141 Photo X-142
Photo X-143 Photo X-144
Photo X-145 Photo X-146
Photo X-147 Photo X-148
Photo X-149 Photo X-150
Photo X-151 Photo X-152
Photo X-153 Photo X-154
Photo X-155 Photo X-156
Photo X-157 Photo X-158
Photo X-159 Photo X-160
Photo X-161 Photo X-162
Photo X-163 Photo X-164
Photo X-165 Photo X-166
Photo X-167 Photo X-168
Photo X-169 Photo X-170
Photo X-171 Photo X-172
Photo X-173 Photo X-174
Photo X-175 Photo X-176
Photo X-177 Photo X-178
Photo X-179 Photo X-180
Photo X-181 Photo X-182
Photo X-183 Photo X-184
Photo X-185 Photo X-186
Photo X-187 Photo X-188
Photo X-189 Photo X-190
Photo X-191 Photo X-192
Photo X-193 Photo X-194
Photo X-195 Photo X-196
Photo X-197 Photo X-198
Photo X-199 Photo X-200
Photo X-201 Photo X-202
Photo X-203 Photo X-204
Photo X-205 Photo X-206
Photo X-207 Photo X-208
Photo X-209 Photo X-210
Photo X-211 Photo X-212
Photo X-213 Photo X-214
Photo X-215 Photo X-216
Photo X-217 Photo X-218
Photo X-219 Photo X-220
Photo X-221 Photo X-222
Photo X-223 Photo X-224
Photo X-225 Photo X-226
Photo X-227 Photo X-228
Photo X-229 Photo X-230
Photo X-231 Photo X-232
Photo X-233 Photo X-234
Photo X-235 Photo X-236
Photo X-237 Photo X-238
Photo X-239 Photo X-240
Photo X-241 Photo X-242
Photo X-243 Photo X-244
Photo X-245 Photo X-246
Photo X-247 Photo X-248
Photo X-249 Photo X-250
Photo X-251 Photo X-252
Photo X-253 Photo X-254
Photo X-255 Photo X-256
Photo X-257 Photo X-258
Photo X-259 Photo X-260
Photo X-261 Photo X-262
Photo X-263 Photo X-264
Photo X-265 Photo X-266
Photo X-267 Photo X-268
Photo X-269 Photo X-270
Photo X-271 Photo X-272
Photo X-273 Photo X-274
Photo X-275 Photo X-276
Photo X-277 Photo X-278
Photo X-279 Photo X-280
Photo X-281 Photo X-282
Photo X-283 Photo X-284
Photo X-285 Photo X-286
Photo X-287 Photo X-288
Photo X-289 Photo X-290
Photo X-291 Photo X-292
Photo X-293 Photo X-294
Photo X-295 Photo X-296
Photo X-297 Photo X-298
Photo X-299 Photo X-300
Photo X-301 Photo X-302
Photo X-303 Photo X-304
Photo X-305 Photo X-306
Photo X-307 Photo X-308
Photo X-309 Photo X-310
Photo X-311 Photo X-312
Photo X-313 Photo X-314
Photo X-315 Photo X-316
Photo X-317 Photo X-318
Photo X-319 Photo X-320
Photo X-321 Photo X-322
Photo X-323 Photo X-324
Photo X-325 Photo X-326
Photo X-327 Photo X-328
Photo X-329 Photo X-330
Photo X-331 Photo X-332
Photo X-333 Photo X-334
Photo X-335 Photo X-336
Photo X-337 Photo X-338
Photo X-339 Photo X-340
Photo X-341 Photo X-342
Photo X-343 Photo X-344
Photo X-345 Photo X-346
Photo X-347 Photo X-348
Photo X-349 Photo X-350
Photo X-351 Photo X-352
Photo X-353 Photo X-354
Photo X-355 Photo X-356
Photo X-357 Photo X-358
Photo X-359 Photo X-360
Photo X-361 Photo X-362
Photo X-363 Photo X-364
Photo X-365 Photo X-366
Photo X-367 Photo X-368
Photo X-369 Photo X-370
Photo X-371 Photo X-372
Photo X-373 Photo X-374
Photo X-375 Photo X-376
Photo X-377 Photo X-378
Photo X-379 Photo X-380
Photo X-381 Photo X-382
Photo X-383 Photo X-384
Photo X-385 Photo X-386
Photo X-387 Photo X-388
Photo X-389 Photo X-390
Photo X-391 Photo X-392
Photo X-393 Photo X-394
Photo X-395 Photo X-396
Photo X-397 Photo X-398
Photo X-399 Photo X-400
Photo X-401 Photo X-402
Photo X-403 Photo X-404
Photo X-405 Photo X-406
Photo X-407 Photo X-408
Photo X-409 Photo X-410
Photo X-411 Photo X-412
Photo X-413 Photo X-414
Photo X-415 Photo X-416
Photo X-417 Photo X-418
Photo X-419 Photo X-420
Photo X-421 Photo X-422
Photo X-423 Photo X-424
Photo X-425 Photo X-426
Photo X-427 Photo X-428
Photo X-429 Photo X-430
Photo X-431 Photo X-432
Photo X-433 Photo X-434
Photo X-435 Photo X-436
Photo X-437 Photo X-438
Photo X-439 Photo X-440
Photo X-441 Photo X-442
Photo X-443 Photo X-444
Photo X-445 Photo X-446
Photo X-447 Photo X-448
Photo X-449 Photo X-450
Photo X-451 Photo X-452
Photo X-453 Photo X-454
Photo X-455 Photo X-456
Photo X-457 Photo X-458
Photo X-459 Photo X-460
Photo X-461 Photo X-462
Photo X-463 Photo X-464
Photo X-465 Photo X-466
Photo X-467 Photo X-468
Photo X-469 Photo X-470
Photo X-471 Photo X-472
Photo X-473 Photo X-474
Photo X-475 Photo X-476
Photo X-477 Photo X-478
Photo X-479 Photo X-480
Photo X-481 Photo X-482
Photo X-483 Photo X-484
Photo X-485 Photo X-486
Photo X-487 Photo X-488
Photo X-489 Photo X-490
Photo X-491 Photo X-492
Photo X-493 Photo X-494
Photo X-495 Photo X-496
Photo X-497 Photo X-498
Photo X-499 Photo X-500
Photo X-501 Photo X-502
Photo X-503 Photo X-504
Photo X-505 Photo X-506
Photo X-507 Photo X-508
Photo X-509 Photo X-510
Photo X-511 Photo X-512
Photo X-513 Photo X-514
Photo X-515 Photo X-516
Photo X-517 Photo X-518
Photo X-519 Photo X-520
Photo X-521 Photo X-522
Photo X-523 Photo X-524
Photo X-525 Photo X-526
Photo X-527 Photo X-528
Photo X-529 Photo X-530
Photo X-531 Photo X-532
Photo X-533 Photo X-534
Photo X-535 Photo X-536
Photo X-537 Photo X-538
This Inspection was visual only and was performed at the request of the client listed this inspection and report is considered comprehensive not exhaustive there are discoveries all along the process and other discoveries may be found completely through to the final inspection by the client any further discoveries found by the client may be included in this report up until the final inspection only if the discoveries are brought to the attention of the inspector 3 days before closing. The inspector and inspection company listed are not held liable to any repairs or discoveries from any repairs made after this inspection date.