23) Knob and tube wiring system: While much of it appears to have been replaced, energized knob and tube wiring was found in the attic. "Knob and tube" wiring was commonly installed until the 1950's. The circuits do not have an equipment ground and it is considered outdated by today's standards. The wire's insulation may become brittle and, as is the case here, often new circuits have been incorrectly tapped into the old wiring. It varies but some insurance companies may be unwilling to insure a home with knob and tube wiring. While energized circuits are present, it is not within the scope of the inspection to determine what percentage of wiring is knob and tube or to determine what percentage of the knob and tube wiring is energized vs abandoned. An electrician should evaluate knob and tube wiring and the electrical system and make repairs, or replace this wiring. To see a short video, produced by King of the House Inc., on the history and implications of knob and tube wiring, please follow this link:
http://youtu.be/Gn0NjKKAcVc
24) The main panel was made by Federal Pacific Electric and it utilizes "Stab-Lok" circuit breakers. These circuit breakers are known to fail and they are considered to be unsafe and a potential fire hazard. Additionally, there is no main shut-off in this electrical panel. To turn off the circuits would require tripping more than six circuit breakers. This is a safety concern. The panel shows signs of corrosion and past water intrusion. I recommend replacement of this electric panel with work to be completed by a licensed electrician. For additional background information, including testing data and court cases, please follow this link to a short video that was produced by a Washington D.C. electrical contractor:
http://youtu.be/qSBpyM7oo8s
25) Receptacles are not GFCI protected at the kitchen countertop. Other receptacles near water areas -- outside and baths -- are GFCI protected. GFCI protected receptacles reduce the likelihood of serious electrical shocks in wet environments. Licensed electrician to repair/replace as required onsite. GFCI protected receptacles should be, periodically, tested for function since they may fail unexpectedly. General guidelines for GFCI protection are included below:
* All outdoor receptacles located at grade level and at decks and porches
* Receptacles in garages and any other out buildings with a floor at or below grade level
* All receptacles, no exceptions, that are installed in bathrooms
* All receptacles installed to service kitchen countertop areas
* All receptacles within 6 ft of the outside edge of laundry, wet bar or utility sinks
* All receptacles located in crawl spaces, unfinished basements or mechanical rooms at grade level or below
* Receptacles supplying power to jetted tubs and pumps (ejector pumps and grinders, well pumps, outdoor pumps, etc.)
26) An exposed/bare light bulb was mounted at the ceiling over the bathtub-shower. Any bulb located less than 8 ft over the threshold of a shower stall or the rim of a tub, if the light fixture is subject to spray, must have a UL "wet location" rating. Typically
wet location approved fixtures are fully covered-enclosed. I recommend electrician repair, install proper light fixture over tub-shower.