Property Inspection Report
Unofficial version!

Client(s): Buyers
Property address: 215 N Any Street
Los Angeles CA 90000
Inspection date: Sunday, March 9, 2025

This report published on Friday, April 11, 2025 7:58:42 AM PDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

Dear customer:

Thank you for choosing KS Home Inspections to perform the following inspection on the property you wish to purchase.
This report is the exclusive property of KS Home Inspections and the individual/s paying for the inspection fee and report. Use of this report by any unauthorized persons is prohibited.

All findings should be made to KS Home Inspections.

This report represents our professional opinion of the condition of the inspected elements of the subject property, determine during a limited time inspection. This inspection was performed, where applicable, in a manner consistent with the standards of the home inspection industry, terms and conditions of the inspection agreement and limitations noted in the inspection agreement. Information contained herein was prepared exclusively for the named client and their authorized representatives.

We have inspected the subject property and must report to you exactly what we found. Because of the age, design and location of the home, we might find some hairline cracks on driveways or walls, see paint peeling off Walls, cracks on tiles, chipped bathtubs or some cracks over windows and doors. These are normal and cosmetic conditions.

While due care was exercised in the performance of this inspection, the company makes no representations or guarantees with respect to latent deficiencies or future conditions as part of the inspection or this report. This report is valid only for a period of thirty (30) days from the date of the inspection. This report, including any attachments, should be reviewed in its entirety. Any questions about the inspection or report should be resolved prior to title transfer.

This inspection report was prepared in a format specifically for the individual/s paying for the inspections fee and report and such transfer does not cover all potential areas of concern a third party may have. This report is transferable only with the consent of the individual/s paying for inspections fee and report and such transfer does not imply any warranty or guarantee regarding the report by inspection firm.

If you have any questions regarding this report, please feel free to call us.

How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeServiceableItem or component is in serviceable condition
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Roof
Attic and Roof Structure
Garage
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
View summary

General InformationTable of contents
Time started: 10:00 AM
Time finished: 1:00 PM
Present during inspection: Client, Realtor
Client present for discussion at end of inspection: No
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Warm
Inspection fee: 800.00
Payment method: Zelle
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Front of building faces: East
Main entrance faces: East
Occupied: No
1)  Evidence of rodent infestation was found in the form of feces in the attic. Consult with the property owner about this. A qualified person should make repairs to seal openings in the structure, set traps, and clean rodent waste as necessary. Recommend following guidelines in these Center for Disease Control articles:
http://www.reporthost.com/?SEALUP
http://www.reporthost.com/?TRAPUP
http://www.reporthost.com/?CLEANUP
Photo
Photo 1-1 
Photo
Photo 1-2 
Photo
Photo 1-3 
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Masonry
Exterior and FoundationTable of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Smooth Stucco
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Concrete slab on grade
Foundation/stem wall material: Concrete slab on grade
Footing material (under foundation stem wall): Concrete slab
2)  Cracks were found in one or more areas of the exterior stucco finish. This is common on structures with smooth stucco. Cracks are aesthetic and may appear every 5 to 7 years. New owners may wish to repair the cracks for aesthetic reasons.
Photo
Photo 2-1 
Photo
Photo 2-2 
Photo
Photo 2-3 
Photo
Photo 2-4 
Photo
Photo 2-5 
Photo
Photo 2-6 
Photo
Photo 2-7 
Photo
Photo 2-8 
3)  Exterior Photos
Photo
Photo 3-1 
Photo
Photo 3-2 
Photo
Photo 3-3 
Photo
Photo 3-4 
4)  Balcony Photos
Photo
Photo 4-1 
Photo
Photo 4-2 
Photo
Photo 4-3 
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Drone
Condition of roof surface material: Appeared serviceable
Roof surface material: Clay tile, Synthetic plasticized or rubberized single-ply membrane
Roof type: Hipped
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable
5)  Significant amounts of debris such as leaves, needles, seeds, etc. have accumulated on the roof surface. Water may not flow easily off the roof, and can enter gaps in the roof surface. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend cleaning debris from the roof surface now and as necessary in the future.
Photo
Photo 5-1 
6)  Roof Photos
Photo
Photo 6-1 
Photo
Photo 6-2 
Photo
Photo 6-3 
Photo
Photo 6-4 
Photo
Photo 6-5 
Photo
Photo 6-6 
Photo
Photo 6-7 
Photo
Photo 6-8 
Photo
Photo 6-9 
Attic and Roof StructureTable of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch(es)
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Ceiling beams
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Mineral wool roll or batt
Vermiculite insulation present: None visible
Vapor retarder: None visible
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Gable end vents
7)  Attic Photos-Overall Good Condition
Photo
Photo 7-1 
Photo
Photo 7-2 
Photo
Photo 7-3 
Photo
Photo 7-4 
Photo
Photo 7-5 
Photo
Photo 7-6 
Photo
Photo 7-7 
Photo
Photo 7-8 
Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of door between garage and house: Appeared serviceable
Type of door between garage and house: Solid core
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Condition of automatic opener(s): Appeared serviceable
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
Condition of garage interior: Appeared serviceable
Garage ventilation: Exists
8)  Window crank for the garage window was not securely attached to the window. Recommend repair.
Photo
Photo 8-1 
Photo
Photo 8-2 
9)  Some drawers in the garage cabinets are difficult to operate. Recommend repair.
Photo
Photo 9-1 
Photo
Photo 9-2 
10)  The much of the garage was obscured by the current owner's belongings. The inspector was not able to view the entire garage. Recommend evaluation when this space is empty.
Photo
Photo 10-1 
Photo
Photo 10-2 
Photo
Photo 10-3 
Photo
Photo 10-4 
11)  The garage doors auto reversing safety feature was tested and operational at the time of inspection.
Photo
Photo 11-1 
Photo
Photo 11-2 
Photo
Photo 11-3 
Photo
Photo 11-4 
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Service voltage (volts): 120
Estimated service amperage: 320 or 400
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded copper
Main disconnect rating (amps): 350
System ground: Ground rod(s) in soil
Condition of main service panel: Appeared serviceable
Condition of sub-panel(s): Appeared serviceable
Location of main service panel #A: Bedroom
Location of main disconnect: Middle
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: copper
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: Yes
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: Yes, but not tested
Carbon monoxide alarms installed: Yes, but not tested
12)  One or more electric receptacles at the bar area had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
For more information, visit:
http://www.reporthost.com/?GFCI
Photo
Photo 12-1 
13)  One or more electric receptacles appeared to have no power. Recommend asking the property owner about this. Switches may need to be operated or GFCI/AFCI protection may need to be reset to make some receptacles energized. If necessary, recommend that a qualified electrician evaluate and repair.

Exterior Outlet
Photo
Photo 13-1 
Photo
Photo 13-2 
14)  Breakers in the exterior electrical panel were not seated properly and could possibly have bad connections. Breakers should not stick out. Recommend evaluation and repair by a qualified electrician.
Photo
Photo 14-1 
Photo
Photo 14-2 
15)  No screws were present for the exterior electrical panels interior cover. Recommend replacing.
Photo
Photo 15-1 
16)  Exterior electrical panel cover does not close and latch properly. Recommend repair.
Photo
Photo 16-1 
17)  GFCI outlet in the upstairs bathroom for the front bedroom was wired incorrectly and will not function as intended. Recommend repair.
Photo
Photo 17-1 
18)  The service drop wires were in contact with trees or vegetation. This can result in damage to wiring insulation or broken wires during high winds. Recommend pruning trees or vegetation as necessary. The utility company may prune trees at no charge.
Photo
Photo 18-1 
19)  All breakers were labeled at the time of inspection. All wire gages correctly corresponded to the breaker sizes. No double tapped breakers were noted in the electrical panel.
Photo
Photo 19-1 
Photo
Photo 19-2 
Photo
Photo 19-3 
Photo
Photo 19-4 
Photo
Photo 19-5 
Photo
Photo 19-6 
20)  Interior electrical panel photos.-All breakers labeled.
Photo
Photo 20-1 
Photo
Photo 20-2 
Photo
Photo 20-3 
Photo
Photo 20-4 
Photo
Photo 20-5 
Plumbing / Fuel SystemsTable of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Water pressure (psi): 69 PSI
Location of main water shut-off: Building exterior
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: None visible
Sewage ejector pump installed: None visible
Type of irrigation system supply source: Public
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: None visible
Location of main fuel shut-off valve: At gas meter
21)  The bathtub jets were not evaluated at the time of inspection. The water supply lines have not been in use for a while and the water has large amounts of sediment and is discolored. Recommend evaluation of the plumbing system for the cause of the sediment and brown water.

**Usually, the water clears up roughly within an hour. It did not clear.**
Photo
Photo 21-1 
Photo
Photo 21-2 
22)  The inspector performed a functional flow test with the plumbing supply system where multiple water outlets were turned on and monitored. The water flow did not decrease significantly with multiple outlets open.
Photo
Photo 22-1 All taps open
Photo
Photo 22-2 Kitchen faucet only
23)  Gas Meter
Photo
Photo 23-1 
24)  Water Meter
Photo
Photo 24-1 
25)  Water Shutoff
Photo
Photo 25-1 
26)  Water Pressure
Photo
Photo 26-1 
Water HeaterTable of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Estimated age: 2017
Capacity (in gallons): 75
Temperature-pressure relief valve installed: Yes
Location of water heater: Utility room, Exterior
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 103.8
Condition of burners: Appeared serviceable
27)  The water heater's earthquake straps or struts were substandard. For example, they may allow significant movement or use substandard fasteners. This is a potential safety hazard in the event of an earthquake due to the risk of the water heater tipping over, gas lines breaking if it's gas-fired, or electric wiring being damaged if powered by electricity. Leaks can also occur in water-supply pipes. Recommend that a qualified person repair or replace existing earthquake reinforcement per standard building practices.
Photo
Photo 27-1 
Photo
Photo 27-2 
28)  The outer flame shield for the water heater combustion chamber was missing. This is a potential fire hazard. Recommend that a qualified person replace any missing flame shields.
Photo
Photo 28-1 
29)  Corrosion or rust was found at the supply pipes or fittings. This can indicate past leaks, or that leaks are likely to occur in the future. Recommend that a qualified plumber evaluate and replace components or make repairs as necessary.
Photo
Photo 29-1 
30)  Water heater photos
Photo
Photo 30-1 
Photo
Photo 30-2 
Photo
Photo 30-3 
31)  Water Temperature
Photo
Photo 31-1 
32)  Tag Photo
Photo
Photo 32-1 
Heating, Ventilation and Air Condition (HVAC)Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air
General heating distribution type(s): Ducts and registers
Last service date of primary heat source: Unknown
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Electric
Estimated age of forced air furnace: Unknown
Location of forced air furnace: Roof
Condition of furnace filters: Appeared serviceable
Location for forced air filter(s): At base of air handler
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Type of combustion air supply: Intake duct
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location of heat pump or air conditioning unit: Building exterior, Roof
Type: Packaged unit
Condition of controls: Appeared serviceable
33)  The split level Heating Venting and Air Conditioning system was evaluated at the time of inspection. The system was in good working condition, responding to normal inputs on the installed thermostats.
Photo
Photo 33-1 
Photo
Photo 33-2 
Photo
Photo 33-3 
Photo
Photo 33-4 
Photo
Photo 33-5 
Photo
Photo 33-6 
Photo
Photo 33-7 
34)  Infrared thermal imaging photos were taken of all vent registers. Evenly distributed hot and cool air was noted at all vent registers.

*Photos of all vent registers are available upon request. *
Photo
Photo 34-1 
Photo
Photo 34-2 
Photo
Photo 34-3 
Photo
Photo 34-4 
Photo
Photo 34-5 
Photo
Photo 34-6 
Photo
Photo 34-7 
Photo
Photo 34-8 
Fireplaces, Stoves, Chimneys and FluesTable of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of gas-fired fireplaces or stoves: Appeared serviceable
Gas fireplace or stove type: Converted wood-burning fireplace
Condition of chimneys and flues: Appeared serviceable
Wood-burning chimney type: Metal
Gas-fired flue type: B-vent
35)  A converted gas burning fireplace was noted at inspection. The damper was operational with no damper clamp installed. Gas burning fireplaces emit Co2 and do not emit smoke. The damper clamp ensures that the Co2 can escape the chimney and not into the structure.


Lower and upper fireplaces
Photo
Photo 35-1 
Photo
Photo 35-2 
Photo
Photo 35-3 
Photo
Photo 35-4 
Photo
Photo 35-5 
Photo
Photo 35-6 
Photo
Photo 35-7 
Photo
Photo 35-8 
36)  Folding glass door was off track on the fireplace in the living room. Recommend repair.
Photo
Photo 36-1 
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop or oven: Appeared serviceable
Range, cooktop or oven type: Natural gas
Type of ventilation: Hood or built into microwave over range or cooktop
37)  No water or ice was available from the refrigerator. Water line may not be connected. Recommend evaluation and repair.
38)  The under-sink food disposal was inoperable. Recommend that a qualified contractor repair or replace as necessary.

Island sink
Photo
Photo 38-1 
Photo
Photo 38-2 
39)  1 cooktop burner(s) were inoperable. Recommend that a qualified person repair as necessary.

Left Rear
Photo
Photo 39-1 
40)  Water faucet at the range appears to be leaking. Recommend repair.
Photo
Photo 40-1 
Photo
Photo 40-2 
41)  One or more cabinet drawers were difficult to open or close. Recommend that a qualified person repair as necessary.
Photo
Photo 41-1 
Photo
Photo 41-2 
42)  Kitchen Photos
Photo
Photo 42-1 
Photo
Photo 42-2 
Photo
Photo 42-3 
Photo
Photo 42-4 
Photo
Photo 42-5 
Photo
Photo 42-6 
Photo
Photo 42-7 
Photo
Photo 42-8 
Bathrooms, Laundry and SinksTable of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Half bath, first floor
Location #B: Full bath, second floor
Location #C: Master bath, second floor
Location #D: 3/4 bath, second floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Bathroom and laundry ventilation type: Windows, Central exhaust fan
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: No
43)  Recommend replacing shower heads in the jr master bathroom.
Photo
Photo 43-1 
44)  Cabinet hardware such as hinges, latches, closers, magnets or pulls at location(s) #D were loose, missing or damaged at one or more cabinet drawers, doors or turntables. Recommend that a qualified person repair as necessary.
Photo
Photo 44-1 
45)  The sink at location(s) #B and D drained slowly. Recommend clearing drain and/or having a qualified plumber repair if necessary.

Upstairs common area bathroom, right sink.
Photo
Photo 45-1 
Photo
Photo 45-2 
46)  The laundry machines were evaluated for proper operation and drainage. The ability to clean and dry clothing was not evaluated.
Photo
Photo 46-1 
47)  Entry Level Bathroom Photos
Photo
Photo 47-1 
Photo
Photo 47-2 
Photo
Photo 47-3 
Photo
Photo 47-4 
48)  Master Bathroom Photos
Photo
Photo 48-1 
Photo
Photo 48-2 
Photo
Photo 48-3 
Photo
Photo 48-4 
Photo
Photo 48-5 
Photo
Photo 48-6 
Photo
Photo 48-7 
Photo
Photo 48-8 
Photo
Photo 48-9 
Photo
Photo 48-10 
49)  Jr Master bedroom Photos
Photo
Photo 49-1 
Photo
Photo 49-2 
Photo
Photo 49-3 
Photo
Photo 49-4 
Photo
Photo 49-5 
Photo
Photo 49-6 
Photo
Photo 49-7 
50)  Common Area Bathroom Photos
Photo
Photo 50-1 
Photo
Photo 50-2 
Photo
Photo 50-3 
Photo
Photo 50-4 
Photo
Photo 50-5 
Photo
Photo 50-6 
Photo
Photo 50-7 
Photo
Photo 50-8 
Photo
Photo 50-9 
Photo
Photo 50-10 
Photo
Photo 50-11 
Photo
Photo 50-12 
51)  Water damage was noted under the sink of the left sink in the main bathroom. This area was dry at the time of inspection and no leak were present.
Photo
Photo 51-1 
Interior, Doors and WindowsTable of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Metal, Glass panel
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Vinyl, Multi-pane
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Condition of concrete slab floor(s): Appeared serviceable
Flooring type or covering: Carpet, Tile
Condition of stairs, handrails and guardrails: Appeared serviceable
52)  Condensation or staining was visible between multi-pane glass in one or more windows. This usually indicates that the seal between the panes of glass has failed or that the desiccant material that absorbs moisture is saturated. As a result, the view through the window may be obscured, the window's R-value will be reduced, and accumulated condensation may leak into the wall structure below. Recommend that a qualified contractor evaluate and repair windows as necessary. Usually, this means replacing the glass in window frames.

Be aware that evidence of failed seals or desiccant may be more or less visible depending on the temperature, humidity, sunlight, etc. Windows or glass-paneled doors other than those that the inspector identified may also have failed seals and need glass replaced. It is beyond the scope of this inspection to identify every window with failed seals or desiccant.

Bedroom #1
Bedroom #2
Photo
Photo 52-1 
Photo
Photo 52-2 
53)  Window cranks at several locations were not securely attached to the windows. Recommend repair.
Photo
Photo 53-1 
Photo
Photo 53-2 
Photo
Photo 53-3 
54)  Cover plates were missing in one or more area. Recommend replacing where missing.
Photo
Photo 54-1 
Photo
Photo 54-2 
Photo
Photo 54-3 
55)  Built in drawer in the master bedroom was off track. Recommend repair.
Photo
Photo 55-1 
56)  Lock mechanisms on one or more windows were difficult to operate. This can pose a security risk. Recommend that a qualified person repair as necessary.

Common area upstairs bathroom
Bedroom #4
Photo
Photo 56-1 
Photo
Photo 56-2 
57)  All interior doors were evaluated at the time of inspection.
58)  All available windows were evaluated at the time of inspection.
59)  Smoke detectors and Co2 alarms have been installed in all necessary areas. If not new, recommend installing new units upon taking possession of the property.
Photo
Photo 59-1 
Photo
Photo 59-2 
Photo
Photo 59-3 
Photo
Photo 59-4 
Photo
Photo 59-5 
Photo
Photo 59-6 
Photo
Photo 59-7 
Photo
Photo 59-8 
60)  Screens were missing from some windows. These windows may not provide ventilation during months when insects are active.
Photo
Photo 60-1 
Photo
Photo 60-2 
Photo
Photo 60-3 
Photo
Photo 60-4 
61)  Interior Photos
Photo
Photo 61-1 
Photo
Photo 61-2 
Photo
Photo 61-3 
Photo
Photo 61-4 
Photo
Photo 61-5 
Photo
Photo 61-6 
Photo
Photo 61-7 
Photo
Photo 61-8 
Photo
Photo 61-9 
Photo
Photo 61-10 
Photo
Photo 61-11 
Photo
Photo 61-12 
Photo
Photo 61-13 
Photo
Photo 61-14 
Photo
Photo 61-15 
Photo
Photo 61-16 
Photo
Photo 61-17 
Photo
Photo 61-18 
Photo
Photo 61-19 
Photo
Photo 61-20 
62)   A gap between the bottom of the door and the weather stripping was noted at the time of inspection. Recommend replacing weather stripping to prevent drafts and unwanted pests.
Photo
Photo 62-1 
Photo
Photo 62-2