Electric
23) One or more screws were missing from the dead front to panel #A and should be replaced. Because energized wiring may exist behind the holes with the missing screws, recommend that a qualified, licensed electrician replace these screws, or that care be taken to ensure that the new screws do not come in contact with wiring inside the panel when they are installed. Stock screws from the panel manufacturer should be used, or their equivalent.
24) Smoke detectors were missing from bedrooms. Additional smoke detectors should be installed as necessary so a functioning one exists in each hallway leading to bedrooms, in each bedroom, and one each level of the building. For more information, visit
http://www.cpsc.gov/cpscpub/pubs/5077.html
25) Smoke detectors were missing batteries in the following locations: hallways leading to bedrooms. A qualified person should replace smoke detectors or make repairs as necessary. For more information, visit:
http://www.cpsc.gov/cpscpub/pubs/5077.html
26) One or more electric receptacles at the following "wet" locations appeared to have no ground fault circuit interrupter (GFCI) protection: kitchen. This is a safety hazard due to the risk of shock. Recommend having a qualified electrician evaluate to determine if GFCI protection exists, and if not, repair as necessary. For more information, visit:
http://www.mikeholt.com/documents/nec/pdf/GFCI_requirement_page2.pdf
27) Based on the age of this structure and the appearance of existing smoke alarms, the alarms may be older than 10 years old. According to
National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit this article:
NFPA urges replacing home smoke alarms after 10 years.
28) One or more lamp covers were missing and should be replaced as necessary.
29) Electric panel(s) at location #D (unit #3) were not opened and fully evaluated due to the following conditions: no access to interior of unit. Recommend that repairs, modifications and/or cleanup be performed as necessary so panels can be opened and fully evaluated.
Evaluated 4/20/2018
Plumbing / Fuel Systems
33) One or more outside faucets were missing
backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the building. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.
Recommend installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit:
http://edis.ifas.ufl.edu/BODY_AE079
34) The handles at one or more outside faucets were missing. A qualified person should repair or replace as necessary.
35) Water supply lines were routed outside and are subject to freezing. Pipe wrap or foam sleeves are inexpensive and easily installed. Recommend insulating pipes as necessary to prevent pipes from freezing and bursting.
Water Heater - #3
44) The water heater did not have seismic straps or struts installed. This is a potential safety hazard. Leaks may also occur in water supply pipes. A qualified person should install seismic straps or struts as necessary and as per standard building practices.
NOTE: The body of the water heater was obscured by an insulation blanket. There were no straps visible.
45) Temperature-pressure relief valve drain line was too short. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. A qualified plumber should extend the drain line to 6 inches from the floor, or route it so as to drain outside.
NOTE: drain line present, not attached.
46) The water heater enclosure door or hardware was damaged. Recommend that a qualified person evaluate and repair or replace as necessary.
47) The estimated useful life for most water heaters is 8 to 12 years. The inspector was unable to determine the age of the water heater due to the manufacturer's label being obscured, no serial number being visible, or the serial number not clearly indicating the age. The client should be aware that this water heater may be near, at, or beyond its useful life and may need replacing at any time. Recommend attempting to determine the water heater's age, and budgeting for a replacement if necessary.
Fireplaces / Stoves / Chimneys
72) The damper at location #D was missing. A qualified contractor should evaluate and repair as necessary.
73) The handle to the damper at location #D was missing. A qualified person should evaluate and repair as necessary.
74) The rain cap for the chimney flue at location #C was deteriorated. They prevent the following:
- Rainwater entering flues and mixing with combustion deposits, creating caustic chemicals which can corrode flues
- Rainwater entering flues and causing damage to masonry from freeze-thaw cycles
A qualified person should install or replace rain caps, or make repairs where necessary.
Kitchen
76) The oven door handle was loose. A qualified person should repair as necessary.
77) The range can tip forward, and no anti-tip bracket appeared to be installed. This is a safety hazard since the range may tip forward when weight is applied to the open door, such as when a small child climbs on it, or if heavy objects are dropped on it. Anti-tip brackets have been sold with all free standing ranges since 1985. An anti-tip bracket should be installed to eliminate this safety hazard. For more information, visit
http://www.hgtv.com/hgtv/remodeling/article/0,1797,HGTV_3659_2017492,00.html
79) Drawers were loose in one or more cabinets. A qualified person should evaluate and repair as necessary.
80) The cooktop exhaust fan was inoperable. A qualified person should evaluate and repair or replace as necessary.
81) Water damage was found in the shelving or cabinet components below one or more sinks. A qualified contractor should evaluate and make repairs as necessary.
82) Refrigerator shelving was damaged and should be replaced or repaired as necessary.
83) Caulk was deteriorated where counters meet backsplashes. A qualified person should repair as necessary.
84) The dishwasher wasn't securely attached to the counter above. Fasteners were missing and/or loose. A qualified person should repair as necessary.
85) One or more light bulbs were missing in the range hood light fixture. The inspector was unable to determine if the light fixture is fully operable.
86) One or more filters for the cooktop exhaust fan were missing. Filters should be replaced as necessary.
87) The dishwasher drain line was not configured with a "high loop" or "air gap". A high loop is created by routing the drain line up to the bottom surface of the counter top above, and securely fastening it to that surface. It is meant to prevent water from siphoning out of the dishwasher, and to prevent water from the sink drain or food disposal from entering the dishwasher. Some dishwashers have a built-in high loop where one is not required to be configured in the drain line. The client should try to determine if a high loop is required for this brand and model of dishwasher (review installation instructions, etc.). If one is required, or it cannot be determined if one is not required, then a qualified contractor should install a high loop as per standard building practices.
Also, no "air gap" was installed. Air gaps are another device meant to prevent water from the sink drain or food disposal from entering the dishwasher. These are required in some municipalities for new construction and when remodeling. The client should consult with a qualified contractor to determine if an air gap should be installed.
NOTE: Unit #3 did have a high loop and air gap present.
Interior Rooms / Areas
104) One or more interior doors have a keyed lockset or deadbolt installed. This is a safety hazard for small children in the event that they lock themselves in the room, do not know how to unlock the door, and the key is not available. Keyed locksets and/or deadbolts should be replaced as necessary with "privacy" locksets that don't require a key.
106) One or more sliding glass doors were difficult to open or close. A qualified person should evaluate and repair or replace as necessary.
107) Cabinet were damaged in one or more areas. A qualified person should evaluate, and repair or replace as necessary.
108) One or more exterior doors had damage. A qualified person should repair or replace as necessary.
109) Trim or jambs around one or more exterior doors was damaged and/or missing. A qualified person should repair, replace or install as necessary.
110) The handles on one or more sliding glass doors were damaged. A qualified person should repair or replace as necessary.
111) Some interior doors were damaged and/or missing. A qualified person should repair or replace as necessary.
112) Some interior door hardware, including locksets and/or latch plates were inoperable, deteriorated and/or missing. A qualified person should repair or replace as necessary.
113) Damage (holes, etc.) were found in one or more wall sections. A qualified person should repair as necessary.
114) Trim/transition strip was missing in some areas. A qualified person should repair as necessary.
115) Laminate flooring was damaged in some areas. A qualified person should repair or replace as necessary.
116) Moderate deterioration or damage was found in floors in one or more areas, including cracked tile. A qualified person should repair as necessary.
117) Screens in some windows are damaged. A qualified person should evaluate and repair or replace as necessary.
118) The weatherstrip around one or more exterior doors was damaged. A qualified person should repair or replace as necessary.
119) Screens in one or more exterior doors were damaged. A qualified person should replace screens where necessary.
120) Floor guides are missing at some sliding closet doors.
121) Fixtures such as closet shelving, towel hangers and/or door stops were missing in one or more areas. A qualified person should install missing fixtures as per standard building practices.
122) Minor cracks and/or holes were found in ceilings in one or more areas. They do not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons.
123) Some damage and/or deterioration was found in ceilings in one or more areas. They do not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons.