Property Inspection Report AMICUS HOME INSPECTION LLC
Client(s):
ANDREA SPATS
Property address:
624 WESTERN PARK DRIVE WEST HEMPSTEAD NY 11552
Inspection date:
Monday, April 1, 2024
This report published on Tuesday, April 9, 2024 3:51:07 PM EDT
This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
Safety
Poses a safety hazard
Repair/Replace
Recommend repairing or replacing
Repair/Maintain
Recommend repair and/or maintenance
Maintain
Recommend ongoing maintenance
Evaluate
Recommend evaluation by a specialist
Monitor
Recommend monitoring in the future
Serviceable
Item or component is in serviceable condition
Comment
For your information
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain), Windy
Temperature during inspection: Cold
Inspection fee: WAIVED
Type of building: Single family, RANCH STYLE
Buildings inspected: One house, ATTACHED GARAGE
Number of residential units inspected: 2
Age of main building: 68 YEARS - 1956
Source for main building age: Property owner
Front of building faces: South
Main entrance faces: South
Occupied: Yes
1) Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit: https://www.reporthost.com/?EPA https://www.reporthost.com/?CPSC https://www.reporthost.com/?CDC
2) The he water supply is part of the Town Public Water System.
3) there is Natural Gas supplied to the residence.
4) INSPECTION OF THE PREMISE WAS CHALLANGING DUE TO CLUTTER AND OWNERS POSSESSIONS OBSCURING SOME OF THE PERTINENT INSPECTION DETAILS.
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Minor slope, GROUNDS SLOPE GENTLY AWAY FROM STRUCTURE
Condition of driveway: Appeared serviceable
Driveway material: Asphalt
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Condition of decks, porches and/or balconies: Appeared serviceable
5) THE SOUTH ENTERANCE AREA OF HOME INCLUDED THE ASPHALT DRIVEWAY, PAVER WALKWAY AND A ONE STEP PORCH PAVED AREA. ALL WERE IN SERVICABLE CONDITION AT THE TIME OF INSPECTION.
WALKWAY AREA ON LEFT (WEST) SIDE OF HOME HAD MINOR CRACKS AND THAT AREA AND FULL DRIVEWAY SHOULD BE MONITORED AND MINOR RESURFACING SHOULD BE CONSIDERED IN THE FUTURE.
NOTE: -MINOR CRACK IN WEST WALK WAY ASPHALT AREA -MINOR CRACK IN YARD (NORTH SIDE) CEMENT WALKWAY -TRIP CONDITION IN NORTH SIDE YEAR CEMENT BLOCK OVER BASEMENT STEP AREA IS NOTED AND RECOMMENDED TO BE REVIEWED BY QUALIFIED CONCRETE SPECIALIST -STREET AREA BY DRIVEWAY ENTERENCE WAS CRACKED, CRUMBLING AND IN NEED OF REPAIR. THIS WILL CAUSE POOLING OF WATER AND ICE FORMATION IN WINTER MONTHS. A QUALIFIED DRIVEWAY SPECIALIST SHOULD BE CONSULTED FOR REPAIR AS THIS CAN BE A CAUSE OF A TRIP AND FALL HAZARD.
6) GENERAL GRADE OF PROPERTY WAS GENTLY SLOPED AWAY FROM STRUCTURE SOIL CONDITION APEARES SERVICIBLE AT TIME OF INSPECTION
NOTED: DRAIN ASSISTANCE WERE APPARENT AS ELEPHANT HOSES AT SOUTH AND NORTH EASTERN CORNERS OF THE STRUCTURE
VEGETATION WAS PROPERLY DISTANCED FROM STRUCTURE
POURED CEMENT ENCOMPASSED 2 SIDES OF HOME AT NORTH, EAST SIDES OF HOME. ASPHALT AND CEMENT ON THE WEST SIDE OF HOME.
7) NOTE THERE ARE TALL AND OLD TREES ALONG THE FRONT WALK. THESE SHOULD BE MONITORED FOR ROOT DAMAGE TO SIDEWALK AND DRIVEWAY.
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Vinyl, Brick veneer, Stone or faux stone veneer
Condition of foundation and footings: Not determined, SIDING EXTENDED TO GROUND
Apparent foundation type: POURED CONCRETE (VIEWED FROM INTERIOR BASEMENT)
Foundation/stem wall material: Poured in place concrete, Not determined (inaccessible or obscured)
Footing material (under foundation stem wall): Not determined (inaccessible or obscured)
8) THE FOUNDATION ON THE EXTERIOR OF THE HOME COULD NOT BE VIEWED, AS THE VYNAL SIDING EXTENDED TO THE GROUND ELEMENTS ON ALL SIDES OF THE STRUCTURE AT TIME OF INSPECTION.
NOTE: -THE STONE AND BRICK AT THE FRONT OF THE HOME SEEMED SERVICEABLE AT THE TIME OF INSPECTION, HOWEVER,THE LEFT CORNER AT THE HOME AND GARAGE IS IN NEED OF CALKING AND SEALING. WATER MAY ENTER THIS AREA AND PERMIT DETERIOATION TO HOME OR GARAGE. A QUALIFIED CONTRACTOR SHOULD REVIEW AND CORRECT.
-SIDING NEXT TO CHIMNEY APPEARED WARPED FROM PRIOR PERIOD. A CHIMNEY AND SIDING SPECIALIST SHOULD BE CONTACTED TO ASSESS THE CAUSE AND DAMAGE. THE AREA SHOULD BE MONITORED GOING FORWARD.
9) AT THE BASEMENT ENTERANCE THERE IS A DRY WELL THAT SHOULD BE MINITORED, CHECKED AND CLEARED OF LEAVES AND DEBRIS.
WINDOW WELLS SHOULD BE MONITORED AND KEPT CLEAN FOR PROPER DRAINAGE.
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.
The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
10) THERE WAS NO APPARENT CRAWL SPACE AT THE STRUCTRE AT THE TIME OF INSPECTION.
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.
Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: NEWLY INSTALLED SOLID VINYL
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Steel
Beam material: Steel
Floor structure above: Solid wood joists
Condition of insulation underneath floor above: Not applicable, none installed
11) A water-proofing system was found in the basement (e.g. grooves in floors along walls). This may be an indication that water has accumulated in the basement in the past. Consult with the property owner and/or reviewing disclosure statements. Also monitor the basement for accumulated water in the future. The inspector did not determine if drainage issues have or haven't been resolved and does not guarantee or warrant that water will not accumulate in the basement in the future.
A FRENCH DRAIN SYSTEM WAS INSTALLED WEST AND NORTH SIDE OF THE BASEMENT AREA, INCLUDING A SUMP PUMP COMPONENT. THE NORTH WEST BASEMENT WALL APPEARED TO HAVE SOME WATERPROOFING COMPONENT ADDED. THE AREA AND COMPONENTS DID NOT APPEAR DAMP AT THE TIME OF INSPECTION, HOWEVER, THE AREA SHOULD BE MONITORED AND A REVIEW BY A QUALIFIED TECHNITIAN IS ENCOURAGED TO VERIFY THE PROPER COMPONENT INSTALLATION.
12) THE BASEMENT AREA WAS COMPLETELY RENOVATED AND INCLUDED A LARGE SITING AREA AND A THREE ROOM AREA-LIVING ROOM, BEDROOM AND KITCHEN AND A FULL BATHROOM.
THE BASEMENT HAD TWO EGRESS AREAS- THE DOOR FROM THE 1ST FLOOR PREMISES AND THE REAR FULL DOOR IN THE BASEMENT LIVING ROOM TO THE EXTERIOR STAIRS. THE DOORS AND DOOR COMPONENTS WERE SERVICEABLE AT THE TIME OF INSPECTION.
SUPPORT INCLUDED STEEL LALLY COLUMNS AND TWO STEEL GIRDERS OBSERVED AND IN SERVICEABLE CONDITION AT THE TIME OF INSPECTION.
SHEETROCK WALLS AND DROPPED CEILING OF ACOUSTIC TILE OR SHEET ROCK SEEMED IN SERVICIBLE CONDITION AT THE TIME OF INSPECTION.
NOTE: -FULL REVIEW OF ABOVE UNDERFLOOR JOIST AND COMPONENTS WAS OBSCURED BY THE DROPPED CEILING. -FULL REVIEW OF FOUNDATION ELEMENTS WAS OBSECURED BY THE BASEMNENT SHEET ROCK WALL COVERING. -ONE CEILING TILE SHOWED SOME PRIOR WATER LEAK DAMAGE.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Viewed from ground
Condition of roof surface material: Appeared serviceable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable
13) THE OWNER ATTESTED THAT THE ROOF WAS FULLY REPLACED WITH ENGINEERED COMPOSIT ASPHALT TILES AT THE SAME TIME THE PORCH AREA WAS RENOVATED IN 2016. THE ROOF APPEARD IN SERVICEABLE CONDITION AT THE TIME OF INSPECTION. GUTTERS AND DOWNSPOUT DRAINAGE WERE REPLACED AT THE TIME OF THE ROOF REPLACEMENT AND APPEARED IN SERVICEABLE CONDITION ATE THE TIME OF INSPECTION. A LEAF FITTER GUTTER GUARD SYSTEM WAS INSTALLED AT A LATER DATE AFTER THE ROOF REPLACEMENT AND SEEMED SECURE AND SERVICEABLE AT THE TIME OF INSPECTION.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Traversed
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Ceiling insulation material: Fiberglass roll or batt
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Gable end vents, Enclosed soffit vents
14) THE INTERIOR ATTIC AND ROOF AREA WAS ACCESSED BY A PULL DOWN STAIR COMPONENT FROM THE MAIN ENTERANCE HALLWAY. THAT STAIR COMPONENT WAS IN SERVICEABLE CONDITION AT THE TIME OF INSPECTION. THERE WAS AN ADDITIONAL ATTIC ACCESS IN THE MASTER CLOSET CEILING WHICH APPEARS TO BE SEALD.
THE ATTIC WITH EXPOSED RAFTERS, COLLAR TIES AND RIDGE BEAM WAS DRY AND APPEARED SERVICEABLE AND UNDAMAGED AT THE TIME OF INSPECTION.
THE ATTIC INCLUDED RIDGE VENTS, TWO ROOF TURTLE VENTS AND A CIRCULAR ROOF FAN . ALL WERE SERVICEABLE AT THE TIME OF INSPECTION.
THE ATTIC FLOOR WAS PARTIALLY COVERED BY PLYWOOD AND OFFERED ONLY A PARTIAL INSPECTION OF THE JOIST AND INSULATION ON THE ATTIC FLOOR (CEILING BELOW).
NOTE: -THE ATTI FLOOR INSTALLATION OF ROLLED BAT INSULATION WAS REVERSED WITH THE VAPOR BARRIER TO THE ATTIC COLD SIDE. A QUALIFIED INSULATION SPECIALIST SHOULD BE ENGAGED TO REVIEW AND RECOMMEND CORRECTION.
-ALTHOUGH SOFFIT BAFFELS WERE NOT OBSERVED THERE WAS OPEN SOFFIT VENTILATION EVIDENCED AT THE TIME OF INSPECTION.
- THE HOME ATTIC SPACE IS EXPOSED TO THE OPEN AREA ABOVE THE GAREAGE. THIS IS A HEALTH AND FIRE HAZARD AND THE SPACE BETWEEN THE GARAGE AND THE LIVING SPACE SHOULD BE SEALED WITH PROPER FIRE RATED MATERIAL AS SOON AS POSSIBLE. A LICENSED CONTRACTOR SHOULD BE ENGAGED FOR THIS SAFETY ISSUE.
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: None visible
15) One or more holes were found in the attached garage walls or ceilings. Current standard building practices call for wooden-framed ceilings and walls that divide the house and garage to provide limited fire-resistance rating to prevent the spread of fire from the garage to the house. Recommend that a qualified person repair per standard building practices. For example, by patching openings or holes, firestopping holes or gaps with fire-resistant caulking, and/or installing fire-resistant wall covering (e.g. Type X drywall). For more information, visit: https://www.reporthost.com/?AGFR
16) THE ATTACHED GARAGE HAD A SECTIONAL LIFT MANUAL DOOR THAT SEEMED SERVICEABLE AND OPERATING AT THE TIME OF INSPECTION.
NOTE: -THE GARAGE WAS CLUTTERED WHICH MADE OBSERVATION DIFFICULT AND LIMITED.
-GARAGE WALLS AND CEILING WERE SHEETROCKED, FURTHER LIMITING INSPECTION ANALYSIS.
-IT WAS NOTED THAT DAMAGE AND HOLES IN THE GARAGE CEILING WILL EXPOSE THE HOME AREA TO FUMES AND FIRE HAZARDS IF NOT REPAIRED (SEE ATTIC SECTION FOR FURTHER DETAIL) A QUALIFIED HANDYMAN SHOULD BE ENGAGED AS SOON AS POSSIBLE FOR THIS REPAIR.
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded copper
Main disconnect rating (amps): 200
System ground: Concrete encased electrode, Copper
Condition of main service panel: Appeared serviceable
Condition of sub-panel(s): Appeared serviceable
Location of main service panel #A: Basement, MAIN SERVICE PANEL IN BASEMENT SITTING OR OPEN AREA
Location of main service panel #B: Basement, AIR CONDITIONING SYSTEM BASEMENT BOILER ROOM
Location of sub-panel #C: Basement, FIRST FLOOR KITCHEN BASEMENT BOILER ROOM
Location of sub-panel #D: Basement, BASEMENT APARTMENT PANEL IN KITCHEN AREA
Location of main disconnect: Breaker at top of main service panel
Branch circuit wiring type: non-metallic sheathed, armor clad (AC), metal clad (MC) or flexible metal conduit (FMC)
Smoke alarms installed: Installed and appear to be functioning properly at this time
Carbon monoxide alarms installed: Dual fire & carbon monoxide devices were installed and appeared to be working property at this time
17) THE THREE WIRE 200 AMP DROP ELECTRICAL SERVICE WAS LOCATED ON THE WEST SIDE (GARAGE SIDE) OF THE HOME.
-THE SERVICE ENTRANCE WIRES AND ENTRY SERVICE BOX APPEARED SERVICEABLE AT THE TIME OF INSPECTION.
-EXTENDED CABLE RUN FROM ENTRY SERVICE BOX TO THE MAIN IN HOME SERVICE PANEL SHOULD BE REVIEWED BY AN ELECTRICIAN FOR PROPER DISTANCE AND ROUTING.
-THE 200 AMP SQUARE D MAIN PANEL INCLUDED 4 30 AMP CIRCUIT BREAKERS TRACED TO THE A/C UNIT, THE ELECTRIC DRYER, THE MAIN KITCHEN AND THE BASEMENT APARTMENT.
-THERE WERE AN NUMBER OF JUNCTION BOXES THAT WERE OPEN WITHOUT PROPER COVERS. THESE SHOULD BE COVERED IMMEDIATELY AS THE DANGER OF ELECTRIC ARCHING IN AN UNCOVERED BOX MAY CAUSE A FIRE.
-THERE ARE A NUMBER OF ELECTRIC OUTLETS THAT TEST AS NOT GROUNDED. THAT IS TYPICAL FOR A HOME OVER 60 YEARS. HOWEVER AN ELECTRICIAN SHOULD BE ENGAGED TO REVIEW THE OVERALL ELECTRICIAL COMPONENTS OF THE HOME BEFORE MOVING INTO THIS HOME. REPLACEING THE NON GROUNDED OUTLETS WITH GFIC BY A QUALIFIED ELECTRICIAN IS RECOMMENDED.
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Location of main water shut-off: Basement
Condition of supply lines: Original at construction of structure, aged but appeared functional at time of inspection.
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Cast iron
Vent pipe condition: Appeared serviceable
Vent pipe material: Cast iron
Sump pump installed: Yes
Condition of sump pump: Appeared serviceable
Sewage ejector pump installed: Yes
Condition of sewage ejector pump: Appeared serviceable
Type of irrigation system supply source: Public
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: Basement, above ground, oil tank
Location of main fuel shut-off valve: By furnace
18) Based on visible equipment or information provided to the inspector, this property appeared to have a yard irrigation (sprinkler) system. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. When this system is operated, recommend verifying that water is not directed at building exteriors, or directed so water accumulates around building foundations. Sprinkler heads may need to be adjusted, replaced or disabled. Consider having a qualified plumber verify that a backflow prevention device is installed per standard building practices to prevent cross-contamination of potable water. Recommend that a qualified specialist evaluate the irrigation system for other defects (e.g. leaks, damaged or malfunctioning sprinkler heads) and repair if necessary.
19) A sewage ejector pump was installed on the premises. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. These systems are typically sealed and involve moving parts. They are subject to clogging and/or damage from disposal of items such as disposable diapers and sanitary napkins. Recommend that this pump and related equipment (piping, valves, etc.) be evaluated by a qualified plumber and repaired if necessary. This should be done per the manufacturer's recommendations in the future, or annually if unable to verify the manufacturer's recommendations. Typically, these pumps have a lifespan of 7-10 years. For more information, visit: https://www.reporthost.com/?SEWEJPMP
20) A sump pump was installed in the basement. These are specialty systems and only a limited evaluation was performed as part of this inspection. The inspector does not determine the adequacy of sump pumps and their associated drainage systems. The presence of a sump pump may indicate that water routinely accumulates below or inside the structure. Recommend asking the property owner how often the sump pump operates and for how long at different times of the year. The client should be aware that the service life of most sump pumps is 5-7 years, and that the pump may need replacing soon depending on its age and how often it operates.
21) THE COMPLETELY FINISHED BASEMENT AREA LIMITED THE VISUAL SCOPE OF THE PLUMBING AND FUEL INSPECTION.
THE HOME RECEIVES PUBLIC WATER WITH SERVICEABLE WATER METER, TWO SHUTOFF VALVES, COPPER ENTRY PIPING AND BACKFLOW PREVENTION AT THE WATER SERVICE METER ENTERANCE WERE OBSERVED. PRESSURE AND LISTED COMPONENTS SEEMED SERVICEABLE AT THE TIME OF INSPECTION.
REVIEW OF THE WATER PIPING AND DRAINAGE SYSTEM WAS OBSCURED IN GREAT PART BY THE BASEMENT FINISHING AND CLUTTER. THE INSPECTOR, WHEN ABLE TO VIEW THE PLUMBING, OBSERVED COPPER PLUMBING SUPPLY PIPING IN THOSE AREAS. DRAINAGE, INTERIOR VENTING APPEARED AS PVC PIPING IN AREAS WHERE THE INSPECTOR HAD ACCESS.
THE HOME INCLUDED ONE SUMP PUMP INCLUDED IN AS FRENCH DRAIN SYSTEM (DISCUSSED IN THE BASEMENT AREA ABOVE), AND A SEWAGE DISPOSAL PUMP IN THE BASEMENT EAST WALL LIVING SPACE. THE SEWAGE DISPOSAL PUMP WAS WORKING AND SERVICEABLE AT THE TIME OF INSPECTION. THE SUMP PUMP WAS NOT ACTIVATED AT THE TIME OF INSPECTION AND THE HOME OWNER SHOULD BE QUESTIONED ABOUT THE OPERABILITY OF THE SUMP PUMP.
THE DRAIN AND WASTE PIPING WERE COMPOSED OF PVC PIPING WITH A CAST IRON P TRAP WASTE PIPE. THE VENT PIPING WAS CAST IRON WITH A MAIN VENT AND KITCHEN VENT STACK PROTRUDING TO THE EXTERIOR THROUGH THE ROOF. THESE COMPONENTS, WHERE THE INSPECTOR COULD OBSERVE, SEEMED SERVICEABLE AT THE TIME OF INSPECTION.
THE BASEMENT LAUNDRY ROOM SINK EMITTED A FUNCTIONAL WATER FLOW, HOWEVER THE DRAINAGE APPEARED SLOW AND SHOULD BE REVIEWED BY A QUALIFIED PLUMBER.
COMPONENTS OF THE FUEL SYSTEM WERE FUEL OIL BASED, WITH A FILL AND VENT LINE AT THE REAR NORTH AREA OF THE HOME CONNECTED TO A DOUBLE INSULATED ABOVE GROUND ROTH DWT MODEL, NON METALIC, 250 GALLON OIL STORAGE TANK. THE TANK AND COMPONENTS SEEMED SERVICEABLE AT THE TIME OF INSPECTION.
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable, NEWLY INSTALLED FEB. 16, 2024
Type: Tank
Energy source: Oil
Capacity (in gallons): 40
Temperature-pressure relief valve installed: Yes
Location of water heater: Basement
Hot water temperature tested: No
22) THE WATER HEATER WAS A NEWLY INSTALLED (02/16/2024) BOCK TURBOFLUE OIL FIRED 40 GALLON WATER HEATER, WHICH WAS OPERATING AND APPEARED SERVICEABLE AT THE TIME OF INSPECTION.
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Furnace
General heating distribution type(s): Pipes and convectors
Source for last service date of primary heat source: Property owner
Type of hydronic or steam heat: Hydronic (hot water)
Hydronic or steam heat fuel type: Oil
Condition of burners: Appeared serviceable
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location of heat pump or air conditioning unit: Building exterior, west
Type: Split system
Condition of controls: Appeared serviceable
23) THE HEATING SYSTEM SYSTEM IS COMPOSED OF A PEERLESS BOILER SERIES WBV 126,000 BTU OIL FIRED HOT WATER SYSTEM, HEATING 2 ZONES WITH BASE BOARD HEATING CONVECTORS. THE BOILER FURNACE WAS INSTALLED IN 2016 AS NEW AND WAS IN OPERATION AND APPEARED SERVICEABLE AT THE TIME OF INSPECTION.
EMERGENCY CUT OFF SWITCHES WERE VIEWED AT THE TOP OF BASEMENT STAIRS AND ABOVE THE FURNACE. THESE WERE NOT TESTED AT THE TIME OF INSPECTION.
THERMOSTATS FOR THE 2 ZONES WERE LOCATED IN THE FIRST FLOOR HALLWAY AND IN THE OPEN BASEMENT SITTING AREA.
-THE A/C UNIT IS A SPLIT SYSTEM WITH THE NEWLY INSTALLED (2019) EVCON R-407C COPMPESSURE LOCATED ON THE OUTSIDE WEST AREA OF THE HOME. THE CONVECTOR AND DISTRIBUTION UNIT IS LOCATED IN THE ATTIC AREA. THE TEMPERTURE AT THE TIME OF INSPECTION PRECLUDED TESTING OF THE A/C UNIT. -THE A/C AIR INTAKE VENT WAS LOCATED IN THE HALL SPACE ADJACENT TO THE KITCHEN. A/C OUTPUT VENTS WERE LOCATED IN THE CEILING OF THE VARIOUS ROOMS. THESE VENTS WERE NOT TESTED AT THE TIME OF INSPECTION DUE TO HE PREVAILING TEMPERATURE AT THE TIME OF INSPECTION. THE VENT CONDITIONS SEEMED UNDAMAGED AT THE TIME OF INSPECTION.
-CLIENT WILL ADVISE IF AN ADDITIONAL INSPECTION AND FEE IS APPROVED FOR A RETEST OF THE A/C UNIT, INTAKE AND OUTFLOW VENTS OR IF AN AIR CONDINTIONING TECHNICIAN WILL REVIEW THE SYSTEM BEFORE MOVING INTO THE HOME.
IT IS RECOMMENDED THAT A HEATING AND AIR CONDIDTIONING QUALIFIED SPECIALIST REVIEW AND ADVISE ON THESE SYSTEMS BEFORE MOVING INTO THE PREMISES.
NOTE: -AN OLD LEAK IN THE ATTIC A/C PAN WAS APPARANT THROUGH THE KITCHEN CEILING. THIS APPEARS TO HAVE BEEN CORRECTED, HOWEVER, THE INSPECTOR ADVISES A QUALIFIED A/C TECHNICIAN BE RECRUTED TO REVIEW AND REPORT ON THIS MATTER. THE DAMAGED CEILING SHOULD BE REPAIRED AS SOON AS POSSIBLE.
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of gas-fired fireplaces or stoves: Appeared serviceable
Condition of chimneys and flues: Appeared serviceable
Gas-fired flue type: B-vent
24) THE HOME IS SUPPLIED WITH DIRECT GAS WITH PSEG. THE HOME HAS TWO GAS STOVES IN EACH OF THE KITCHENS ON THE MAIN AND BASEMENT AREA. BOTH STOVES WERE OPERATING AT THE TIME OF INSPECTION. BOTH STOVES WERE PURCHASED AFTER 2016 ACCORDING TO THE OWNER.
THE HOME ALSO HAS INSTALLED (IN 2020) A GAS FIRED FIREPLACE IN THE FIRST FLOOR LIVING AREA. THE INSPECTOR TESTED THE UNIT AND IT WAS OPERATIONAL AT THE TIME OF INSPECTION.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of ranges, cooktops and/or ovens: Appeared serviceable
Range, cooktop, oven type: Natural gas
Condition of refrigerator: Appeared serviceable, ICE MAKER WAS NOT OPERATABLE
25) THE MAIN FIRST FLOOR KITCHEN INCLUDED GRANITE COUNTERTOPS AND ISLAND. STAINLESS STEEL APPLIANCES INCLUDED A GAS RANGE/OVEN, A MICROWAVE OVEN, FRIDGEDAIR GALLERY MODEL REFRIDGERATOR AND A FRIDGEDAIR GALLERY DISHWASHER. ALL APPLIANCES WERE OPERABLE AT THE TIME OF INSPECTION.
THE MICROWAVE INCLUDED AN EXHAUST FAN THE WAS OPERABLE AT THE TIME OF INSPECTION AND VENTED TO THE OUTSIDE OF THE HOME
THE DISHWASHER WAS OPERATIONAL AT THE TIME OF INSPECTION.
THE KITCHEN SINK WAS A STAINLESS STEEL UNDERMOUNT MODEL WITH PROPER P-TRAP.
NOTE: THE FRIDGEDAIR REFRIDGERATOR ICEMAKER WAS NOT WORKING AT THE TIME OF INSPECTION.
THE KICK PLATE ON THE KITCHEN CANINETS WAS BECOMING DETACHED AND NEEDS TO BE PROPERLY FASTENED.
26) THE BASEMENT KITCHEN INCLUDED A GE REFRIDGERATOR, A GE GAS STOVE AND OVEN. BOTH WERE OPERABLE AT THE TIME OF INSPECTION. THE QUARTZ COUNTERTOP AND STAINLESS STEEL UNDERMOUNT SINK WERE SERVICEABLE AT THE TIME OF INSPECTION.
NOTE: THE OVEN HOOD FAN DID NOT VENT TO THE OUTSIDE OF HOME.
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #B: Full bath, GUEST-SHOWER REPLACED BATHTUB
Location #C: Full bath, BASEMENT
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Bathroom and laundry ventilation type: Windows, Spot exhaust fans
27) THE LAUNDRY ROOM WAS LOCATED IN THE BASEMENT AREA WITH GE ELECTRIC APPLIANCES INSTALLED IN 2021 AS PER OWNER.
THE DRYER OPERATES ON A 220 30 AMP CURRENT.
BOTH APPLIANCES WERE OPERABLE AND SERVICEABLE AT THE TIME OF INSPECTION.
NOTE: -THE VENTILATION FAN IN THAT LAUNDRY WAS NOT OPERABLE AT THE TIME OF INSPECTION AND SHOULD BE REPAIRED AND REPLACED AS SOON AS POSSIBLE TO AVOID FUMES AND MOISTURE BIULDUP IN THE ROOM.
-THE DRYER HAS BEEN HARD WIRED TO THE APPLIANCE AND IT IS RECOMMENDED THAT A QUALIFIED ELECTRICIAN INSTAL A PROPER OUTLET AND PROPER PLUG FOR THE DRYER.
THE DRYER EXHAUST IS AN ALUMINIUM ACCORDIAN TYPE. THIS SHOULD BE REPLACED AS SOON AS POSSIBLE WITH A RIDGED ALUMINIUM EXHAUST PIPE. THE ACCORDIAN TYPE CAN SNAG AND ACCUMULATE LINT AND CAUSE A DANGEROUS FIRE HAZARD.
28) THE BASEMENT BATHROOM INCLIDED A BATH/SHOWER, A COMODE AND SINK. THESE WERE OPERABLE AT THE TIME OF INSPECTION.
QUARTZ COUNTERTOP, CABINETS AND DRAWERS WERE IN GOOD CONDITION AND OPERABLE AT THETIME OF INSPECTION.
HE FUNCTIONAL FLOW OF THE WATER COMPONENTS AND THE DRAINAGE WERE ADMISSABLE AT THE TIME OF INSPECTION.
VENTILATION WAS FROM THE EXISTING WINDOW.
NOTE: SHOWER SOAP DISH WAS MISSING FROM SHOWER WALL AND NEEDS TO BE REPLACED AND REPAIRED.
29) THE MASTER BATH WAS RENOVATED IN 2016 AND APPEARED OPERABLE AND SERVICEABLE AT THE TIME OF INSPECTION.
COMPONENTS OF THE SHOWER, SINK, SINK CABINET AND COMMODE WERE STABLE, AND OPERABLE AT THE TIME OF INSPECTION.
THE FUNCTIONAL FLOW OF THE WATER COMPONENTS AND THE DRAINAGE WERE ADMISSABLE AT THE TIME OF INSPECTION.
VENTILATION WAS FROM THE EXISTING WINDOW.
30) THE FIRST FLOOR GUEST BATH WAS RENOVATED IN 2021 AND INCLUDED AS SHOWER, COMODE AND SINK AND APPEARED OPERABLE AND SERVICEABLE AT THE TIME OF INSPECTION.
QUARTZ COUNTERTOP, CABINETS AND DRAWERS WERE IN GOOD CONDITION AND OPERABLE AT THETIME OF INSPECTION.
THE FUNCTIONAL FLOW OF THE WATER COMPONENTS AND THE DRAINAGE WERE ADMISSABLE AT THE TIME OF INSPECTION.
VENTILATION WAS FROM AN OVERHEAD EXHAUST FAN ELIMINATING TO THE OUTSIDE OF THE HOME.
31) THE LAUNDRY ROOM WAS LOCATED IN THE BASEMENT AREA. APPLIANCES A GE WASHER AND GE DRYER ARE THREE YEARS OLD AS PER THE OWNER. THESE WERE NOT TESTED AT THE INSPECTION DATE.
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Fiberglass or vinyl
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Vinyl, Double-hung, Casement
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Flooring type or covering: Carpet, Wood or wood products, Tile
Condition of stairs, handrails and guardrails: Appeared serviceable
32) ENTERANCE FRONT, REAR AND BASEMENT ENTRANCE DOORS WERE SOLID CORE, VINYL, DEAD BOLT LOCKED AND ALL INSTALLED WITHIN FOUR YEARS. THEY WERE FUNCTIONAL, OPERABLE AND SERVICEABLE AT THE TIME OF INSPECTION
ALL WIDOWS WERE REPLACE IN 2016 WITH NEW VINYL DOUBLE HUNG AND CASEMENT ON THE FIRST FLOOR AND SLIDING VINYL IN THE BASEMENT AREA.
THE SELECTED WINDOWS TESTED WERE OPERABLE AND SERVICEABLE AT THE TIME OF INSPECTION.
WALLS AND CEILINGS THROUGHOUT THE PREMISES WERE DRYWALL SAVE FOR THE BASEMENT SITTING AREA AND LITCHEN WHICH WERE A FIBER DROPPED CEILING TILES.
THERE IS WALL PAPER IN FIRST FLOOR HALLWAY WHICH APPEARD SERVICEABLE AT THE TIME OF INSPECTION.
FLOORS THROUGHOUT THE FIRST FLOOR ARE OAK WOOD OR VINYL TILE AND ALL WERE SERVICEABLE AT THE TIME OF INSPECTION.
FLOORS IN THE BASEMENT AREA INCLUDE RUG SQUARES IN THE BASEMENT SITTING AREA, VINYL TILES THROUGH THE KITCHEN, BEDROOM , LIVING ROOM AND LAUNDRY ROOM. THE BATH ROOM IS VINYL TYLE.
NOTE: -FRONT DOOR DEAD BOLT WAS DIFFICULT TO OPERATE AND SHOULD BE REVIEWED AND REPAIRED BY A HANDY MAN. -THE VINYL TILE HAS A LOOSE AREA NEAR THE BASEMENT ENTRY DOOR.
Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
33) AT THE TIME OF INSPECTION AND WITH THE LIMITED AREA THAT COULD BE VIEWED THERE WAS NO OVERT INDICATION OF CURRENT WOOD DESTROYING INSECT ACTIVITY. HOWEVER, THERE WERE EVIDENCE OF WOOD DESTROYING INSECT TRAPS FROM A PRIOR PERIOD PLACED AROUND THE HOME.
IT IS STRONGLY RECOMMENDED THAT A LICENSED QULIFIED EXTERMINATOR BE ENGAGED TO REVIEW AND STUDY THE PREMISES.