This report published on Friday, August 19, 2022 9:44:00 AM PDT
Dear customer:
Thank you for choosing New Beginning Home Inspections to perform the following inspection on the property you wish to purchase. This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
All findings should be made to New Beginning Home Inspections.
This report represents our professional opinion of the condition of the inspected elements of the subject property, determine during a limited time inspection. This inspection was performed, where applicable, in a manner consistent with the standards of the home inspection industry, terms and conditions of the inspection agreement and limitations noted in the inspection agreement. Information contained herein was prepared exclusively for the named client and their authorized representatives.
We have inspected the subject property and must report to you exactly what we found. Because of the age, design and location of the home, we might find some hairline cracks on driveways or walls, may hear squeaking on raised or second story floors, see paint peeling off Walls, cracks on tiles, chipped bathtubs or some cracks over windows and doors. These are normal and cosmetic conditions.
While due care was exercised in the performance of this inspection, the company makes no representations or guarantees with respect to latent deficiencies or future conditions as part of the inspection or this report. This report is valid only for a period of thirty (30) days from the date of the inspection. This report, including any attachments, should be reviewed in its entirety. Any questions about the inspection or report should be resolved prior to title transfer.
This inspection report was prepared in a format specifically for the named client and such transfer does not cover all potential areas of concern a third party may have. This report is transferable only with the consent of the named client and such transfer does not imply any warranty or guarantee regarding the report by inspection firm.
If you have any questions regarding this report, please feel free to call us.
LIMITED WARRANTY
This inspection report is a written communication describing the condition of the property inspected. Its purpose is to indicate the existing condition of the subject property. It is not meant to be a demand for repairs by the owner of subject property and communicates a written report of the then existing conditions on the property at the time of the inspection.
During the inspection, our inspectors do not take apart equipment, structures, apply stress and/or perform destructive testing or move furniture and equipment to view areas. Any areas which are visually hidden or not readily accessible are not covered in this report.
Additionally, this report does not include and is not a substitute for a Real Estate Transfer Disclosure Statement, Form TDS-14, California Civil Code Section 1102.
This report does not cover the following items: Evaluate as to whether there are any city, county, or state code violations on the property. • Evaluate the slopes, grading or credibility of any retaining walls or drainage on the property. • Perform termite inspections. • Test security devices. • Evaluated the presence or extent of insulation and vapor barriers in exterior walls and soffits. • Enter crawl areas where headroom is less than three feet or where other adverse conditions exist. • Walk on the roof where it could damage the roof materials or be unsafe for the inspector. • Enter attic spaces that are not readily accessible or where headroom above the access panel is less than three feet. • Inspect underground drainage pipes or internal rain gutters and downspouts. • Operate any main branch or fixture valves that are turned off. • Inspect any plumbing components that are not visible or readily accessible. • Inspect water quality, water conditioning equipment and solar water heating systems. • Evaluate the ability of the systems to comply with the current codes. • Inspect or activate interior fire sprinkler systems. • Activate or operate any system that has been shut down. • Evaluate the mounting of any kitchen cabinets. • Make repairs or give estimates. Inspect septic tanks. • Inspect septic tanks. Inspect or test electronic thermostats. • Turn on or off pool valves. • Guarantee any appliances and/or pool equipment • Determine or test for leaks in the roof. • Any damage done in the attic or under the house, including air ducts, if a termite inspection is made to the property after the completed inspection. • Damage caused by testing and/or termite inspection.
How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
Safety
Poses a risk of injury or death
Major Defect
Correction likely involves a significant expense
Repair/Replace
Recommend repairing or replacing
Repair/Maintain
Recommend repair and/or maintenance
Minor Defect
Correction likely involves only a minor expense
Maintain
Recommend ongoing maintenance
Evaluate
Recommend evaluation by a specialist
Serviceable
Item or component is in serviceable condition
Comment
For your information
Infestation
Evidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.)
Conducive conditions
Conditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable, Required repairs, replacement and/or evaluation (see comments below)
1) Cracks, holes, settlement, heaving and/or deterioration were found in sidewalks and/or patios. Recommend that qualified contractor repair as necessary.
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Required repairs, replacement and/or evaluation (see comments below)
Apparent wall structure: Wood frame
Wall covering: Stucco
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Concrete slab on grade
Foundation/stem wall material: Concrete slab on grade
2) 1) One or more fences and gates were damaged or deteriorated and need repair. 2) Fungal rot was found at one or more sections of siding or trim, window frames, soffits, fascia, exposed beams and exterior wood areas . Conducive conditions for rot should be corrected (e.g. wood-soil contact, reverse perimeter slope). Recommend that a qualified person repair as necessary. All rotten wood should be replaced. 3) Stains were found at one or more soffit boards, but no elevated moisture levels were found and the wood appeared to be in good condition. Based on the inspector's findings, these stains may be from past leaks. Monitor these areas in the future. If moisture is observed, recommend that a qualified contractor evaluate and repair as necessary. 4) Evidence of active/past infestation of termites was found at one or more areas at the property . Recommend the following: Correct any conducive conditions for wood-destroying organisms mentioned in this report. Consult with the property owner about any history of infestation. Have a state-licensed pest control operator evaluate further and treat as necessary.
3) Cracks, deterioration and/or damage were found in one or more areas of the exterior stucco finish. In damp climates, moisture can enter cracks or damaged areas and further deteriorate the stucco. Also the wall behind the stucco can become damaged from moisture. Note that areas behind the stucco are inaccessible and excluded from this inspection. Recommend that a qualified contractor repair or replace stucco as necessary.
4) The paint or stain finish over much of the entire structure was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture. Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint or restain the entire building exterior per standard building practices. Any repairs needed to the siding or trim should be made prior to this.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.
Roof inspection method: Traversed
Condition of roof surface material: Near, at or beyond service life
Roof surface material: Built up tar and felt, Little Rock
Roof type: Flat or low slope
5) The roof surface was significantly deteriorated and appeared to be at or beyond its service life. It needs replacing now. This is a conducive condition for wood-destroying organisms. Consult with a qualified contractor to determine replacement options. Note that some structural repairs are often needed after old roof surfaces are removed and the structure becomes fully visible. Related roofing components such as flashings and vents should be replaced or installed as needed and per standard building practices.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors:
Condition of garage floor: Required repair, replacement and/or evaluation (see comments below)
7) 1) Garage was in serviceable condition. 2) Vehicle garage door opened and closed manually. 3) Substandard wiring was found in the garage . For example, exposed wiring, loose wiring, unterminated wires, exposed splices, missing cover plates . This is a safety hazard. Recommend that a qualified electrician evaluate and repair as necessary and per standard building practices. 4) A sub electrical panel should be installed at the garage. 5) Connections for washer and dryer machines.
8) Minor cracks were found in the concrete slab floor. These are common and appeared to be only a cosmetic issue.
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Required repair, replacement and/or evaluation (see comments below)
Primary service type: Overhead
Service voltage (volts): 120-240
Primary service overload protection type: Circuit breakers
Main disconnect rating (amps): Not applicable, no single main disconnect
Condition of main service panel: Required repair, replacement and/or evaluation (see comments below)
Condition of branch circuit wiring: Required repair, replacement and/or evaluation (see comments below)
Ground fault circuit interrupter (GFCI) protection present: Yes, No
9) 1) Electric system in general should be re evaluated by a professional electrician and repair, replace and/or upgrade as necessary and per standard building regulation. 2) Substandard wiring were found in the garage, exterior and interior of the house. This is a safety hazard. Recommend that a qualified electrician evaluate and repair as necessary and per standard building practices. 3) Branch circuit wiring installed in buildings built prior to the mid 1980s is typically rated for a maximum temperature of only 60 degrees Celsius. This includes non-metallic sheathed (Romex) wiring, and both BX and AC metal-clad flexible wiring. Knob and tube wiring, typically installed in homes built prior to 1950, may be rated for even lower maximum temperatures. Newer electric fixtures including lighting and fans typically require wiring rated for 90 degrees Celsius. Connecting newer fixtures to older, 60-degree-rated wiring is a potential fire hazard. Repairs for such conditions may involve replacing the last few feet of wiring to newer fixtures with new 90-degree-rated wire, and installing a junction box to join the old and new wiring.
It is beyond the scope of this inspection to determine if such incompatible components are installed, or to determine the extent to which they're installed. Based on the age of this building, the client should be aware of this safety hazard, both for existing fixtures and when planning to upgrade with newer fixtures. Consult with a qualified electrician for repairs as necessary.
10) One or more modern, 3-slot electric receptacles (outlets) were found with an open ground. Three-slot receptacles should have a hot, a neutral and a ground wire connected. Homeowners often install new 3-slot receptacles on older, 2-wire circuits that only have hot and neutral wires. This is a shock hazard when appliances that require a ground are used with these receptacles. Examples of such appliances include computers and related hardware, refrigerators, freezers, portable air conditioners, clothes washers, aquarium pumps, and electrically operated gardening tools. Where the electric system was installed prior to when grounded circuits were required (1960s), it is permissible to replace 3-slot receptacles with 2-slot receptacles to prevent appliances that require a ground from being plugged in to an ungrounded circuit. However, the client should be aware of this limitation when planning use for various rooms, such as an office. For newer electric systems, circuits should be repaired so grounded, 3-wire cables provide power to 3-slot receptacles. Recommend that a qualified electrician repair per standard building practices.
11) Based on the age of this structure and the appearance of existing smoke alarms, the alarms may have been installed more than 10 years ago. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit: http://www.reporthost.com/?SMKALRMLS
12) 2-slot receptacles (outlets) rather than 3-slot, grounded receptacles were installed in one or more areas. These do not have an equipment ground and are considered unsafe by today's standards. Appliances that require a ground should not be used with 2-slot receptacles. Examples of such appliances include computers and related hardware, refrigerators, freezers, portable air conditioners, clothes washers, aquarium pumps, and electrically operated gardening tools. The client should be aware of this limitation when planning use for various rooms, such as an office. Upgrading to grounded receptacles typically requires installing new wiring from the main service panel or sub-panel to the receptacle(s), in addition to replacing the receptacle(s). Consult with a qualified electrician about upgrading to 3-wire, grounded circuits.
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Location of main water meter: By street
Location of main water shut-off: Building exterior
Service pipe material: Galvanized steel
Condition of supply lines: Appeared serviceable
Supply pipe material: Galvanized steel
Condition of drain pipes: Appeared serviceable
Condition of waste lines: Appeared serviceable
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: Above ground
Location of main fuel shut-off valve: At gas meter
13) The plumbing system was in serviceable working condition. There was hot water at the kitchen and bathrooms, water pressure was good ad no active leaks were found at the time of the inspection.
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Capacity (in gallons): 40
Location of water heater: Closet
Condition of burners: Appeared serviceable
14) 1) The water heater was in good working condition. There was hot water atthe kitchen and bathrooms. 2) The gas supply to the water heater used only rigid pipe. An approved flexible connector should be installed between appliances and rigid gas piping so the piping won't break loose during an earthquake. Recommend that a qualified contractor repair per standard building practices. 3) The flexible connector used to supply gas to the water heater was longer than 3 feet. Flexible connectors longer than 3 feet are prohibited for gas appliances that are not moveable. Recommend that a qualified contractor repair per standard building practices.
15) A water heater was installed over a finished living space or in an area where leaking can cause damage, and there was no catch pan and no drain was installed. Consider having a qualified contractor install a catch pan and drain to prevent water damage if the water heater develops a leak. Note that installing a drain may be difficult or impossible depending on the location of the water heater.
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
16) 1) Wall heater/furnace were no inspected because at the time of the inspection the pilots were turned off. 2) Wall/window air conditioning unit was in serviceable working condition.
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
17) 1) The spark screen for the fireplace was missing . Recommend that a qualified person repair or replace as necessary. 2) One or more gaps were found between the fireplace face and the firebox. Heat from the firebox may penetrate these gaps to combustible materials in the wall structure. This is a potential fire hazard. Recommend that a qualified contractor repair as necessary. 3) No spark screen or rain cap was installed at one or more chimney flue terminations. Spark screens reduce the chance of embers exiting the flue and causing fires. They also prevent wildlife (e.g. birds, rodents, raccoons) from entering flues. Rain caps prevent water from entering flues, mixing with combustion deposits and creating caustic chemicals which can corrode flues. They also prevent damage to masonry from freeze-thaw cycles and prevent metal components (e.g. dampers, metal firebox liners) from rusting. Recommend that a qualified person install rain caps with spark screens per standard building practices where missing.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of dishwasher: N/A (none installed)
Condition of range, cooktop: N/A (none installed)
Condition of refrigerator: N/A (none installed)
18) Kitchen was in serviceable condition. No appliances were installed. Cabinets were fine.
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath
Location #B: 3/4 bath
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
19) Bathrooms were in good and serviceable condition. Toilets, sinks, showers and bathtubs were in serviceable working condition. Cabinets were fine.
20) Connections for washer and dryer machines at the garage.
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood, Glass panel, Glass broken
Condition of interior doors: Appeared serviceable
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
21) 1) At the time of the inspection, the interior of the house was in good and serviceable condition. 2) Walls and ceiling were fine. Floor was in good condition. 3) One or more closet doors were damaged . Recommend that a qualified person replace or repair doors as necessary. 4) One or more sliding closet doors were stuck or difficult to slide. Recommend that a qualified person adjust or repair as necessary. 5) Glass in one or more windows was broken. Recommend that a qualified contractor replace glass where necessary. 6) Stains were found in one or more ceiling areas. However, no elevated levels of moisture were found. The stain(s) may be due to past roof and/or plumbing leaks.Consult with the property owner and monitor the stained area(s) in the future, especially after heavy or prolonged rain. If elevated moisture is found in the future, then recommend that a qualified contractor evaluate and repair as necessary.