Summary

Client(s):  Betsy Ross
Property address:  456 Clover Lane
Moab UT 84532-2724
Inspection date:  Friday, August 13, 2021

This report published on Saturday, October 9, 2021 12:48:44 PM MDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information
Concern typeConducive conditionsConditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)


Grounds
2) Cracks, holes, settlement, heaving and/or deterioration resulting in trip hazards were found in the driveway, For safety reasons, recommend that a qualified contractor repair as necessary.

Exterior and Foundation
4) Conducive conditionsCracks, deterioration and/or damage were found in one or more areas of the exterior stucco finish. In damp climates, moisture can enter cracks or damaged areas and further deteriorate the stucco. Also the wall behind the stucco can become damaged from moisture. Note that areas behind the stucco are inaccessible and excluded from this inspection. Recommend that a qualified contractor repair or replace stucco as necessary.
5) Conducive conditionsTrees were in contact with or were close to the building at one or more locations. Damage to the building can occur, especially during high winds, or may have already occurred (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.

Basement
6) Handrails at NE basement bedroom egress stairs were missing. This is a potential fall hazard. Handrails should be installed at stairs with four or more risers or where stairs are greater than 30 inches high. Recommend that a qualified contractor install handrails where missing and per standard building practices.

Roof
7) Conducive conditionsOne or more rubber or neoprene pipe flashings were split or cracked at ADU. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor replace flashings where necessary.
8) Some composition shingles were cracked or otherwise damaged. Leaks can occur as a result. Recommend that a qualified contractor repair as necessary. For example, by replacing shingles.

Garage or Carport
10) The photoelectric sensors that trigger the auto-reverse feature on one or more garage vehicle doors' automatic openers were located higher than 4-6 inches from the floor. This is a potential safety hazard. A qualified person should relocate sensors so they are 4-6 inches from the floor per standard building practices. For more information on garage door safety issues, visit:
http://www.reporthost.com/?GDPES

Electric
11) Panel(s) #D and #E used screw-in fuses for the over-current protection devices. Fuses are prone to tampering and over-fusing, which can damage wiring and cause fire hazards. Insurance companies may deny coverage for homes with fused panels. Modern panels use circuit breakers for over-current protection devices, which can be reset easily after tripping rather than needing to replace fuses. Modern panels also offer more flexibility for new, safer protective technologies like ground fault circuit interrupters (GFCls) and arc fault circuit interrupters (AFCls). Consult with a qualified electrician about replacement options for fused panels, and about other system upgrades as necessary.
12) Panel(s) #C were manufactured by the Federal Pacific Electric company and used "Stab-Lok" circuit breakers. There is significant evidence that both double and single pole versions of these circuit breakers fail by not tripping when they are supposed to. However, in 2011 the Consumer Products Safety Commission (CPSC) closed an investigation into this product because they did not have enough data to establish that the circuit breakers pose a serious risk of injury to consumers. Regardless, and due to other evidence of safety issues, recommend that a qualified electrician carefully evaluate all Federal Pacific panels and make repairs as necessary. Consider replacing Federal Pacific panels with modern panels that offer more flexibility for new, safer protective technologies like ground fault circuit interrupters (GFCls) and arc fault circuit interrupters (AFCls). For more information, visit:
http://www.reporthost.com/?FP1
http://www.reporthost.com/?FP2
http://www.reporthost.com/?FP3
13) One or more electric receptacles (outlets) at the bathroom in detached bar structure had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
For more information, visit:
http://www.reporthost.com/?GFCI
14) Smoke alarms were missing from bedrooms. Additional smoke alarms should be installed as necessary so a functioning alarm exists in each hallway leading to bedrooms, in each bedroom, on each level and in any attached garage. For more information, visit:
http://www.reporthost.com/?SMKALRM
15) One or more circuit breakers in panel(s) #A were "double tapped," where two or more wires were installed in the breaker's lug. Most breakers are designed for only one wire to be connected. This is a safety hazard since the lug bolt can tighten securely against one wire but leave other(s) loose. Arcing, sparks and fires can result. Recommend that a qualified electrician repair as necessary. For more information, visit:
http://www.reporthost.com/?DBLTAP
16) One or more smoke alarms were missing, damaged, or missing components. Smoke alarms should be replaced as necessary. For more information, visit:
http://www.reporthost.com/?SMKALRM

Plumbing / Fuel Systems
17) HVAC condensate drain and water heater PRV were routed to a drain pipe with no visible p-trap. Sewer gases may enter home. Recommend evaluation by a qualified plumber to determine if trap is present and make repairs as needed.
18) Copper tubing was installed as a supply line at water heater in basement. Copper tubing is not an approved gas line material as it can be easily damaged. Recommend having a qualified plumber extend black iron pipe to within 36" of water heater gas valve, then using an approved flexible connector to connect to valve.
19) One or more black steel gas supply pipes had substandard support or were loose. Gas leaks may occur as a result. Black steel gas supply pipes should have approved hangers every 6-8 feet. Hangers should be made from steel to prevent the pipes and hangers from corroding due to contact of dissimilar metals. Recommend that a qualified person install hangers or secure pipes per standard building practices.
20) Some or all of the water supply and drain or vent pipes were made of galvanized steel. Based on the age of this structure and the 40-60 year useful life of this piping, it will likely need replacing in the future. Leaks can develop, flooding and/or water damage may occur, flow can be restricted due to scale accumulating inside the piping, and water may be rusty. Note that it is beyond the scope of this inspection to determine what percentage of the piping is older, galvanized steel, as much of it is concealed in wall, floor and/or ceiling cavities. Recommend the following:
  • That a qualified plumber evaluate to better understand or estimate the remaining life
  • Consulting with a qualified plumber about replacement options and costs
  • Budget for replacement in the future
  • Monitor these pipes for leaks and decreased flow in the future
  • Consider replacing old, galvanized steel piping proactively
For more information, visit:
http://www.reporthost.com/?GALVPIPE

Water Heater
25) The draft hood for the water heater flue was loose. This is a potential safety hazard due to the risk of exhaust gases entering living spaces. A qualified person should permanently secure the draft hood with appropriate fasteners per standard building practices.
26) The hot water temperature was greater than 120 degrees Fahrenheit. This is a safety hazard due to the risk of scalding. The thermostat should be adjusted so the water temperature doesn't exceed 120 degrees. If the water heater is powered by electricity, a qualified person should perform the adjustment, since covers that expose energized equipment normally need to be removed. For more information on scalding dangers, visit:
http://www.reporthost.com/?SCALD

Water Heater (ADU)
27) The hot water temperature was greater than 120 degrees Fahrenheit. This is a safety hazard due to the risk of scalding. The thermostat should be adjusted so the water temperature doesn't exceed 120 degrees. If the water heater is powered by electricity, a qualified person should perform the adjustment, since covers that expose energized equipment normally need to be removed. For more information on scalding dangers, visit:
http://www.reporthost.com/?SCALD

Heating, Ventilation and Air Condition (HVAC)
28) Recommend replacing or washing HVAC filters upon taking occupancy depending on the type of filters installed. Regardless of the type, recommend checking filters monthly in the future and replacing or washing them as necessary. How frequently they need replacing or washing depends on the type and quality of the filter, how the system is configured (e.g. always on vs. "Auto"), and on environmental factors (e.g. pets, smoking, frequency of house cleaning, number of occupants, the season).

Heating, Ventilation and Air Condition (ADU HVAC)
29) Conducive conditionsEvaporative cooler was leaking onto roof of ADU. Recommend a qualified person repair as necessary.
30) Air filters for the heating and/or cooling system were difficult to access. Recommend a qualified HVAC contractor install a filter enclosure per current building practice.

Kitchen
32) The cooktop exhaust fan was inoperable at kitchen in ADU. Recommend that a qualified person repair or replace as necessary.
33) Grout at tile countertop in ADU was deteriorated. Recommend installing new grout in deteriorated areas to prevent water from infiltrating substructure.

Bathrooms, Laundry and Sinks
34) The exhaust fan at location(s) #B was noisy or vibrated excessively. Moisture may accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified person clean, repair or replace fans as necessary.

Interior, Doors and Windows
35) Handrails at basement stairs were too low and pose a fall hazard. Handrails should be located at least 34 inches and at most 38 inches above the nose of each tread/riser. Recommend that a qualified person repair per standard building practices.
36) What was being used as a bedroom in the basement had windows that were too high off the floor. At least one window requires adequate egress in the event of a fire or emergency to allow escape or to allow access by emergency personnel. Such windows should have a maximum sill height of 44 inches off the floor. At a minimum, keep a chair or something that serves as a ladder below the window at all times. If concerned, have a qualified contractor repair or make modifications per standard building practices. For more information, visit:
http://www.reporthost.com/?EGRESS