13) One or more electric receptacles (outlets) at the bathroom in detached bar structure had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
- Outdoors (since 1973)
- Bathrooms (since 1975)
- Garages (since 1978)
- Kitchens (since 1987)
- Crawl spaces and unfinished basements (since 1990)
- Wet bar sinks (since 1993)
- Laundry and utility sinks (since 2005)
For more information, visit:
http://www.reporthost.com/?GFCI
14) Smoke alarms were missing from bedrooms. Additional smoke alarms should be installed as necessary so a functioning alarm exists in each hallway leading to bedrooms, in each bedroom, on each level and in any attached garage. For more information, visit:
http://www.reporthost.com/?SMKALRM
15) One or more circuit breakers in panel(s) #A were "double tapped," where two or more wires were installed in the breaker's lug. Most breakers are designed for only one wire to be connected. This is a safety hazard since the lug bolt can tighten securely against one wire but leave other(s) loose. Arcing, sparks and fires can result. Recommend that a qualified electrician repair as necessary. For more information, visit:
http://www.reporthost.com/?DBLTAP
16) One or more smoke alarms were missing, damaged, or missing components. Smoke alarms should be replaced as necessary. For more information, visit:
http://www.reporthost.com/?SMKALRM
Plumbing / Fuel Systems
18) Copper tubing was installed as a supply line at water heater in basement. Copper tubing is not an approved gas line material as it can be easily damaged. Recommend having a qualified plumber extend black iron pipe to within 36" of water heater gas valve, then using an approved flexible connector to connect to valve.
19) One or more black steel gas supply pipes had substandard support or were loose. Gas leaks may occur as a result. Black steel gas supply pipes should have approved hangers every 6-8 feet. Hangers should be made from steel to prevent the pipes and hangers from corroding due to contact of dissimilar metals. Recommend that a qualified person install hangers or secure pipes per standard building practices.
20) Some or all of the water supply and drain or vent pipes were made of galvanized steel. Based on the age of this structure and the 40-60 year useful life of this piping, it will likely need replacing in the future. Leaks can develop, flooding and/or water damage may occur, flow can be restricted due to scale accumulating inside the piping, and water may be rusty. Note that it is beyond the scope of this inspection to determine what percentage of the piping is older, galvanized steel, as much of it is concealed in wall, floor and/or ceiling cavities. Recommend the following:
- That a qualified plumber evaluate to better understand or estimate the remaining life
- Consulting with a qualified plumber about replacement options and costs
- Budget for replacement in the future
- Monitor these pipes for leaks and decreased flow in the future
- Consider replacing old, galvanized steel piping proactively
For more information, visit:
http://www.reporthost.com/?GALVPIPE