Inspector: Jacob Schwegel
TN 1342
MS MHIB #0653

Property Inspection Report

Client(s):  Sample Report
Property address:  123 Sample Lane
North MS or Memphis
Inspection date:  Tuesday, May 15, 2018

This report published on Tuesday, July 23, 2019 9:54:19 AM CDT

A home inspection is designed to find things wrong with the home. Sometimes it can seem overwhelming when you are wanting to buy a house, and you get a report of only negative things. If there is an area of concern for you, I want to encourage you to contact a professional for further evaluation.

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a safety hazard
Repair/ReplaceRecommend repairing or replacing
Repair/MaintainRecommend repair and/or maintenance
Minor DefectCorrection likely involves only a minor expense
MaintainRecommend ongoing maintenance
EvaluateRecommend evaluation by a specialist
MonitorRecommend monitoring in the future
CommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Roof
Exterior and Foundation
Grounds
Garage or Carport
Attic and Roof Structure
Plumbing / Fuel Systems
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Electric
Water Heater
Water Heater 2
Heating, Ventilation and Air Condition (HVAC)
Heating, Ventilation and Air Condition (HVAC) 2
Heating, Ventilation and Air Condition (HVAC) 3
Crawl Space
Limitations Of An Inspection

View summary

General InformationTable of contents
Time started: 4 30
Time finished: 6:00
Present during inspection: Client, Tenant
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Hot
Inspection fee: *
Payment method: Check
Buildings inspected: One house, One detached garage
Number of residential units inspected: 1
Age of main building: 1982
Source for main building age: Municipal records or property listing
1) Safety, Comment - Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
http://www.reporthost.com/?EPA
http://www.reporthost.com/?CPSC
http://www.reporthost.com/?CDC
2) Repair/Maintain, Evaluate - What appeared to be microbial growths were found at one or more locations in interior rooms. It is beyond the scope of this inspection to identify what substance or organism this staining is. However such staining is normally caused by excessively moist conditions, which in turn can be caused by plumbing or building envelope leaks and/or substandard ventilation. These conducive conditions should be corrected before making any attempts to remove or correct the staining. Normally affected materials such as drywall are removed, enclosed affected spaces are allowed to dry thoroughly, a mildewcide may be applied, and only then is drywall reinstalled. For evaluation and possible mitigation, consult with a qualified industrial hygienist or mold/moisture mitigation specialist. For more information, visit:
http://www.reporthost.com/?MOLDCDC
http://www.reporthost.com/?MOLDEPA
Photo
Photo 2-1 Master bathroom above the toilet
Photo
Photo 2-2 Master bathroom under sink
Roof inspection method: Partially traversed
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable
Exterior and FoundationTable of contents
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Wood fiber, brick
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Crawl space
3) Repair/Replace - Fungal rot was found at one or more sections of siding or trim. Conducive conditions for rot should be corrected (e.g. wood-soil contact, reverse perimeter slope). Recommend that a qualified contractor repair as necessary. All rotten wood should be replaced.
Photo
Photo 3-1 
Photo
Photo 3-2 
Photo
Photo 3-3 
Photo
Photo 3-4 
Photo
Photo 3-5 
Photo
Photo 3-6 
Photo
Photo 3-7 
4) Maintain - Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 4-1 
Site profile: Level
Condition of driveway: Appeared serviceable
Condition of sidewalks and/or patios: Appeared serviceable
Condition of deck, patio and/or porch covers: Required repairs, replacement and/or evaluation (see comments below)
5) Safety, Repair/Maintain - Handrails at one or more flights of stairs were loose. This is a safety hazard. Recommend that a qualified person repair as necessary.
Photo
Photo 5-1 
6) Repair/Replace - One or more deck, patio and/or porch covers were showing high abouts if moisture and water damage. Recommend that a qualified person repair or replace as necessary, and per standard building practices.
Photo
Photo 6-1 
Photo
Photo 6-2 
Photo
Photo 6-3 
7) Repair/Replace - The roof surface material on one or more deck, patio or porch covers was at or beyond its service life. Recommend that a qualified contractor replace roof surfaces as necessary.
Photo
Photo 7-1 
Garage or CarportTable of contents
Type: Attached, Detached
Condition of door between garage and house: Appeared serviceable
Condition of exterior entry doors: Appeared serviceable
Condition of garage vehicle door(s): Appeared serviceable
Condition of automatic opener(s): Required repair, replacement and/or evaluation (see comments below)
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Condition of detached garage or carport structure: Appeared serviceable
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Steel frame
Condition of roof structure: Appeared serviceable
Roof type: Gable
8) Repair/Replace, Evaluate - One or more garage vehicle doors wouldn't close with the automatic opener because the opener auto-reversed while the door was closing. This can be caused by photoelectric sensors being out of adjustment, the door binding, the mechanical auto-reverse sensor having problems, etc. Note that because of this, the inspector was unable to verify that the auto-reverse functions for the automatic opener were operable. A qualified person should evaluate, repair as necessary and verify that auto-reverse functions are working.
Photo
Photo 8-1 
Photo
Photo 8-2 
Attic and Roof StructureTable of contents
Attic inspection method: Partially traversed
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Condition of roof ventilation: Appeared serviceable
Plumbing / Fuel SystemsTable of contents
Condition of service and main line: Appeared serviceable
Water service: Public
Location of main water shut-off: Under bathroom sink
Condition of supply lines: Appeared serviceable
Supply pipe material: CPVC plastic
Condition of drain pipes: Appeared serviceable
Vent pipe condition: Appeared serviceable
9) Repair/Replace, Evaluate - One or more hose bibs appeared to be inoperable. No water flowed from the bib(s) when turned on. This may be due to a shut-off valve being turned off. Note that the inspector does not operate shut-off valves. Recommend consulting with the property owner about inoperable hose bibs, and if necessary have a qualified plumber make repairs.
Photo
Photo 9-1 
Photo
Photo 9-2 
10) Repair/Maintain - One or more hose bibs leaked when tested. When hose bibs leak while turned off, it's often caused by a worn valve seat or a loose bonnet. When hose bibs leak while turned on, it may be due to worn "packing" around the stem or a defective backflow prevention device. Recommend that a qualified plumber repair as necessary.
Photo
Photo 10-1 
Photo
Photo 10-2 
Photo
Photo 10-3 
11) Maintain, Evaluate - Based on visible components or information provided to the inspector, this property appeared to have a private sewage disposal (septic) system. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Generally, septic tanks should be pumped and inspected every 3 years. Depending on the type of system and municipal regulations, inspection and maintenance may be required more frequently, often annually. Recommend the following:
  • Consult with the property owner about this system's maintenance and repair history
  • Review any documentation available for this system
  • Review inspection and maintenance requirements for this system
  • That a qualified specialist evaluate, perform maintenance and make repairs if necessary
For more information, visit:
http://www.reporthost.com/?SEPTIC
Fireplaces, Stoves, Chimneys and FluesTable of contents
12) Safety, Repair/Maintain, Evaluate - One or more wood-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all wood-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at:
http://www.reporthost.com/?CSIA
Photo
Photo 12-1 
Photo
Photo 12-2 
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: N/A (none installed)
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop or oven: Appeared serviceable
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: Appeared serviceable
Bathrooms, Laundry and SinksTable of contents
Location #A: Full bath, second floor
Location #B: Full bath, second floor
Location #C: Full bath, Master bath
Location #D: Half bath, first floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Required repair, replacement and/or evaluation (see comments below)
13) Repair/Replace - The bathroom with a shower or bathtub at location(s) #A and B didn't have an exhaust fan installed. Moisture can accumulate and result in mold, bacteria or fungal growth. Even if the bathroom has a window that opens, it may not provide adequate ventilation, especially during cold weather when windows are closed or when wind blows air into the bathroom. Recommend that a qualified contractor install exhaust fans per standard building practices where missing in bathrooms with showers or bathtubs.
Photo
Photo 13-1 
Photo
Photo 13-2 
14) Repair/Maintain - One or more sink drains were leaking at location(s) #C. A qualified person should repair as necessary.
Photo
Photo 14-1 Master Sink
Interior, Doors and WindowsTable of contents
Condition of exterior entry doors: Appeared serviceable
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Required repair, replacement and/or evaluation (see comments below)
Condition of walls and ceilings: Required repairs, replacement and/or evaluation (see comments below)
Condition of flooring: Appeared serviceable
Condition of stairs, handrails and guardrails: Required repairs, replacement and/or evaluation (see comments below)
15) Safety, Repair/Replace - Risers for stairs at one or more locations were higher than 7 3/4 inches and posed a fall or trip hazard. Risers should be 7 3/4 inches or shorter. At a minimum, be aware of this hazard, especially when guests who are not familiar with the stairs are present. Recommend that a qualified contractor repair per standard building practices.
Photo
Photo 15-1 
Photo
Photo 15-2 
16) Repair/Replace, Evaluate - Condensation or staining was visible between multi-pane glass in one or more windows. This usually indicates that the seal between the panes of glass has failed or that the desiccant material that absorbs moisture is saturated. As a result, the view through the window may be obscured, the window's R-value will be reduced, and accumulated condensation may leak into the wall structure below. Recommend that a qualified contractor evaluate and repair windows as necessary. Usually, this means replacing the glass in window frames.

Be aware that evidence of failed seals or desiccant may be more or less visible depending on the temperature, humidity, sunlight, etc. Windows or glass-paneled doors other than those that the inspector identified may also have failed seals and need glass replaced. It is beyond the scope of this inspection to identify every window with failed seals or desiccant.
Photo
Photo 16-1 
17) Repair/Replace, Evaluate - Stains and elevated levels of moisture were found in one or more ceiling areas. The stains appear to be due to an active roof leak. Recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 17-1 2nd floor near furnace
18) Repair/Replace - Glass in one or more windows was cracked, broken and/or missing. Recommend that a qualified contractor replace glass where necessary.
Photo
Photo 18-1 
19) Monitor - Stains were found in one or more ceiling areas. However, no elevated levels of moisture were found. The stain(s) may be due to past roof and/or plumbing leaks.Consult with the property owner and monitor the stained area(s) in the future, especially after heavy or prolonged rain. If elevated moisture is found in the future, then recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 19-1 Master
Photo
Photo 19-2 
Electric service condition: Appeared serviceable
Primary service type: Overhead
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded copper
Main disconnect rating (amps): 200
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Building exterior
Location of main service panel #B: Building exterior
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: Non-metallic sheathed
20) Safety, Repair/Replace, Evaluate - Modifications were made to panel(s) #C or to equipment inside. Electric panels and equipment inside are Underwriter Laboratory rated devices, and modifications to them are not allowed. Recommend that a qualified electrician evaluate and replace components or make repairs as necessary.
Photo
Photo 20-1 
21) Safety, Repair/Replace, Evaluate - One or more receptacles were scorched. The wiring for these receptacles may be damaged due to overheating. Recommend that a qualified electrician replace such receptacles, evaluate related wiring and repair if necessary.
Photo
Photo 21-1 
Photo
Photo 21-2 
Photo
Photo 21-3 Shown inside
22) Safety, Repair/Replace, Evaluate - One or more ground fault circuit interrupter (GFCI) receptacles wouldn't trip and/or wouldn't trip with a test instrument at the kitchen, bathroom(s) and/or exterior. This is a potential shock hazard. Recommend that a qualified electrician evaluate and repair as necessary.
Photo
Photo 22-1 
Photo
Photo 22-2 
Photo
Photo 22-3 
Photo
Photo 22-4 
Photo
Photo 22-5 
Photo
Photo 22-6 
23) Safety, Repair/Replace - Non-metallic sheathed wiring in the attic was routed on surfaces within 6 feet of one or more access hatches or doors, and was subject to damage. Wiring can be damaged when hatches are lifted and set aside, when stored items are moved into or out of the attic, etc. This is a potential shock and/or fire hazard. Recommend that a qualified electrician repair per standard building practices.
Photo
Photo 23-1 
Photo
Photo 23-2 
24) Safety, Repair/Replace - Wire splices were exposed and were not contained in a covered junction box. This is a potential shock or fire hazard. Recommend that a qualified electrician repair per standard building practices. For example, by installing permanently mounted junction boxes with cover plates where needed to contain wiring splices.
Photo
Photo 24-1 
Photo
Photo 24-2 
25) Safety, Repair/Replace - One or more modern, 3-slot electric receptacles were found with an open ground. Three-slot receptacles should have a hot, a neutral and a ground wire connected. Homeowners often install new 3-slot receptacles on older, 2-wire circuits that only have hot and neutral wires. This is a shock hazard when appliances that require a ground are used with these receptacles. Examples of such appliances include computers and related hardware, refrigerators, freezers, portable air conditioners, clothes washers, aquarium pumps, and electrically operated gardening tools. Where the electric system was installed prior to when grounded circuits were required (1960s), it is permissible to replace 3-slot receptacles with 2-slot receptacles to prevent appliances that require a ground from being plugged in to an ungrounded circuit. However, the client should be aware of this limitation when planning use for various rooms, such as an office. For newer electric systems, circuits should be repaired so grounded, 3-wire cables provide power to 3-slot receptacles. Recommend that a qualified electrician repair per standard building practices.
Photo
Photo 25-1 
Photo
Photo 25-2 
26) Safety, Repair/Replace - One or more electric receptacles had reverse-polarity wiring, where the hot and neutral wires were reversed. This is a shock hazard. Recommend that a qualified electrician repair as necessary. For more information, visit:
http://www.reporthost.com/?RPR
Photo
Photo 26-1 
27) Safety, Minor Defect - One or more exterior receptacle covers were broken. This is a potential shock hazard. Recommend that a qualified person replace covers where necessary.
Photo
Photo 27-1 
Photo
Photo 27-2 
28) Repair/Replace, Evaluate - One or more electric receptacles appeared to have no power. Recommend asking the property owner about this. Switches may need to be operated or GFCI/AFCI protection may need to be reset to make some receptacles energized. If necessary, recommend that a qualified electrician evaluate and repair.
Photo
Photo 28-1 
Photo
Photo 28-2 
Photo
Photo 28-3 
Photo
Photo 28-4 
Photo
Photo 28-5 
29) Evaluate - Bulbs in one or more light fixtures were missing or broken. These light fixtures couldn't be fully evaluated. If replacement bulbs are inoperable, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
Photo
Photo 29-1 
Photo
Photo 29-2 
Photo
Photo 29-3 
Photo
Photo 29-4 
Photo
Photo 29-5 
Water HeaterTable of contents
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Electricity
Estimated age: 2004
Capacity (in gallons): 40
Temperature-pressure relief valve installed: Yes
Location of water heater: Closet
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 124
30) Safety - The hot water temperature was greater than 120 degrees Fahrenheit. This is a safety hazard due to the risk of scalding. The thermostat should be adjusted so the water temperature doesn't exceed 120 degrees. If the water heater is powered by electricity, a qualified person should perform the adjustment, since covers that expose energized equipment normally need to be removed. For more information on scalding dangers, visit:
http://www.reporthost.com/?SCALD
Photo
Photo 30-1 
Photo
Photo 30-2 
Water Heater 2Table of contents
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Electricity
Estimated age: 2017
Capacity (in gallons): 40
Temperature-pressure relief valve installed: Yes
Location of water heater: Closet
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 117
31) - water heater
Photo
Photo 31-1 
Heating, Ventilation and Air Condition (HVAC)Table of contents
General heating system type(s): Forced air, Furnace
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Location of forced air furnace: Closet
Condition of furnace filters: Appeared serviceable
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Type of combustion air supply: Intake duct
Condition of venting system: Appeared serviceable
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Type: Split system
Age: 2010
Condition of controls: Appeared serviceable
32) Repair/Maintain - One or more heating or cooling air supply registers were missing. The air flow cannot be controlled as a result. Recommend installing registers where missing.
Photo
Photo 32-1 
33) Repair/Maintain - One or more air supply registers were loose or installed in a substandard way. Recommend that a qualified person repair as necessary so registers are securely attached and are flush with the surface on which they are installed.
Photo
Photo 33-1 
34) Repair/Maintain - Insulation on the heat pump or air conditioning condensing unit's refrigerant lines was deteriorated or missing in some areas. This may result in reduced efficiency and increased energy costs. Recommend that a qualified person replace or install insulation as necessary.
Photo
Photo 34-1 
35) Maintain - Recommend replacing or washing HVAC filters upon taking occupancy depending on the type of filters installed. Regardless of the type, recommend checking filters monthly in the future and replacing or washing them as necessary. How frequently they need replacing or washing depends on the type and quality of the filter, how the system is configured (e.g. always on vs. "Auto"), and on environmental factors (e.g. pets, smoking, frequency of house cleaning, number of occupants, the season).
Photo
Photo 35-1 
Photo
Photo 35-2 
Heating, Ventilation and Air Condition (HVAC) 2Table of contents
General heating system type(s): Forced air, Furnace
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Appeared serviceable
Estimated age of forced air furnace: 2010
Location of forced air furnace: Closet
Condition of furnace filters: N/A (none visible)
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Type of combustion air supply: Intake duct
Condition of venting system: Appeared serviceable
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Type: Ductless heat pump
Age: 2010
Condition of controls: Appeared serviceable
36) Maintain - Air filters for the heating and/or cooling system were missing at one or more locations where they should have been installed. Indoor air quality will be reduced as a result. Recommend installing good quality filters at intended locations (e.g. in or at the air handler, behind return air grills). Filters should be sized correctly to minimize air gaps. Many types of filters are available. Recommend installing pleated filters or better rather than the cheapest disposable kind. For more information, visit:
http://www.reporthost.com/?FLTRTPS
Photo
Photo 36-1 
Photo
Photo 36-2 
Heating, Ventilation and Air Condition (HVAC) 3Table of contents
General heating system type(s): Forced air, Furnace
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: 2004 or 2007
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Type of combustion air supply: Intake duct
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Type: Packaged unit
Condition of controls: Appeared serviceable
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Condition of floor substructure above: Required repairs, replacement and/or evaluation (see comments below)
Condition of insulation underneath floor above: Not applicable, none installed
Condition of vapor barrier: Required repairs, replacement and/or evaluation (see comments below)
Condition of crawl space ventilation: Appeared serviceable
37) Repair/Replace, Evaluate - Fungal rot was found at one or more sections of floor sheathing. Recommend that a qualified contractor evaluate and repair as necessary. All rotten wood should be replaced.
Photo
Photo 37-1 
38) Repair/Replace - No under-floor insulation was installed in the crawl space. Recommend that a qualified person install insulation for better energy efficiency and per standard building practices. Typically this is R-19 rated fiberglass batt with the attached facing installed against the warm (floor) side.
Photo
Photo 38-1 
39) Repair/Maintain - One or more outdoor crawl space access hatches or doors were missing, damaged, deteriorated or substandard. Water and/or vermin can enter the crawl space. Recommend that a qualified person replace, install or repair hatches or doors where necessary.
Photo
Photo 39-1 
40) Repair/Maintain - The vapor barrier in some areas of the crawl space was loose or askew. Soil was exposed as a result and will allow water from the soil to evaporate up into the structure. This is a conducive condition for wood-destroying organisms. A 6 mil black plastic sheet should be placed over all exposed soil with seams overlapped to 24 inches, and not in contact with any wood structural components. The sheeting should be held in place with bricks or stones, not wood. Recommend that a qualified person replace or repair the vapor barrier where necessary and per standard building practices.
Photo
Photo 40-1 
Limitations Of An InspectionTable of contents
41) Comment - Roof: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
42) Comment - Exterior and Foundation: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
43) Comment - Grounds: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
44) Comment - Garage or Carport: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
45) Comment - Attic and Roof Structure: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
46) Comment - Plumbing / Fuel Systems: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
47) Comment - Fireplaces, Stoves, Chimneys and Flues: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
48) Comment - Kitchen: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
49) Comment - Bathrooms, Laundry and Sinks: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
50) Comment - Interior, Doors and Windows: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
51) Comment - Electric: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
52) Comment - Water Heater: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
53) Comment - Heating, Ventilation and Air Condition (HVAC): The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).


Thank you for choosing Olive Branch Home Inspections. If you have any questions please call 901-336-7211 or find us on facebook.