Dear customer:
Thank you for choosing New Beginning Home Inspections to perform the following inspection on the property you wish to purchase.
This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
All findings should be made to New Beginning Home Inspections.
This report represents our professional opinion of the condition of the inspected elements of the subject property, determine during a limited time inspection. This inspection was performed, where applicable, in a manner consistent with the standards of the home inspection industry, terms and conditions of the inspection agreement and limitations noted in the inspection agreement. Information contained herein was prepared exclusively for the named client and their authorized representatives.
We have inspected the subject property and must report to you exactly what we found. Because of the age, design and location of the home, we might find some hairline cracks on driveways or walls, may hear squeaking on raised or second story floors, see paint peeling off Walls, cracks on tiles, chipped bathtubs or some cracks over windows and doors. These are normal and cosmetic conditions.
While due care was exercised in the performance of this inspection, the company makes no representations or guarantees with respect to latent deficiencies or future conditions as part of the inspection or this report. This report is valid only for a period of thirty (30) days from the date of the inspection. This report, including any attachments, should be reviewed in its entirety. Any questions about the inspection or report should be resolved prior to title transfer.
This inspection report was prepared in a format specifically for the named client and such transfer does not cover all potential areas of concern a third party may have. This report is transferable only with the consent of the named client and such transfer does not imply any warranty or guarantee regarding the report by inspection firm.
If you have any questions regarding this report, please feel free to call us.
LIMITED WARRANTY
This inspection report is a written communication describing the condition of the property inspected. Its purpose is to indicate the existing condition of the subject property. It is not meant to be a demand for repairs by the owner of subject property and communicates a written report of the then existing conditions on the property at the time of the inspection.
During the inspection, our inspectors do not take apart equipment, structures, apply stress and/or perform destructive testing or move furniture and equipment to view areas. Any areas which are visually hidden or not readily accessible are not covered in this report.
Additionally, this report does not include and is not a substitute for a Real Estate Transfer Disclosure Statement, Form TS-14, California Civil Code Section 1102.
This report does not cover the following items:
• Evaluate as to whether there are any city, county, or state code violations on the property.
• Evaluate the slopes, grading or credibility of any retaining walls or drainage on the property.
• Perform termite inspections.
• Test security devices.
• Evaluated the presence or extent of insulation and vapor barriers in exterior walls and soffits.
• Enter crawl areas where headroom is less than three feet or where other adverse conditions exist.
• Walk on the roof where it could damage the roof materials or be unsafe for the inspector.
• Enter attic spaces that are not readily accessible or where headroom above the access panel is less than three feet.
• Inspect underground drainage pipes or internal rain gutters and downspouts.
• Operate any main branch or fixture valves that are turned off.
• Inspect any plumbing components that are not visible or readily accessible.
• Inspect water quality, water conditioning equipment and solar water heating systems.
• Evaluate the ability of the systems to comply with the current codes.
• Inspect or activate interior fire sprinkler systems.
• Activate or operate any system that has been shut down.
• Evaluate the mounting of any kitchen cabinets.
• Make repairs or give estimates. Inspect septic tanks.
• Inspect septic tanks. Inspect or test electronic thermostats.
• Turn on or off pool valves.
• Guarantee any appliances and/or pool equipment
• Determine or test for leaks in the roof.
• Any damage done in the attic or under the house, including air ducts, if a termite inspection is made to the property after the completed inspection.
• Damage caused by tenting and/or termite inspection.
General Information
Report number: 173/16
Time started: 10:00
Time finished: 11:45
Present during inspection: Client, Tenant
Client present for discussion at end of inspection: Yes
Inspector: Jose Antonio Feo
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Warm
Ground condition: Dry
Recent weather: Dry (no rain)
Overnight temperature: Cool
Inspection fee: $249.00
Payment method: Check
Type of building: Single family
Buildings inspected: One house
Age of main building: 1956
Source for main building age: Municipal records or property listing - 616 sq ft
Occupied: Furniture or stored items were present
Grounds
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Asphalt
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Exterior and Foundation
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Stucco
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Concrete slab on grade
1)
In general, the exterior of the property was in serviceable and good condition.
Photo 1-1
Photo 1-2
Roof
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.
2)
The roof surface appeared to be near the end of its service life and will likely need replacing in the near future even if repairs are made now. Recommend discussing replacement options with a qualified contractor, and budgeting for a replacement roof surface in the near future. The client may also wish to consider having a qualified contractor attempt to issue a "2 year roof certificate."
Clients should consult with the HOA about maintenance and future repairs of the roof.
Attic and Roof Structure
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch(es)
Location of attic access point #A: Hallway
Location of attic access point #B: Hallway
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Ceiling beams
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
3)
Attic was in serviceable and good condition. Attic had good ventilation and insulation. Roof structure was in serviceable condition.
Photo 3-1
Photo 3-2
Photo 3-3
Photo 3-4
Garage or Carport
Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Condition of garage vehicle door(s): Required repair, replacement and/or evaluation (see comments below)
Type of garage vehicle door: Tilt
Number of vehicle doors: 1
Condition of automatic opener(s): Near, at or beyond service life
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: Inadequate
4)
No "photo eye" sensors were installed for one or more garage vehicle doors' automatic opener. These have been required on all automatic door openers since 1993 and improve safety by triggering the door's auto-reverse feature without need for the door to come in contact with the object, person or animal that is preventing the door from closing. Recommend that a qualified contractor install "photo eye" sensors where missing for improved safety. For more information on garage door safety issues, visit:
http://www.cpsc.gov/cpscpub/pubs/523.html
6)
Substandard wiring and connections was found in the garage . For example, exposed wiring, loose wiring, unterminated wires, exposed splices, missing cover plates and/or extension or lamp cord used as permanent wiring . This is a safety hazard. Recommend that a qualified electrician evaluate and repair as necessary and per standard building practices.
One or more automatic door openers were inoperable . Recommend that a qualified contractor evaluate and repair or replace opener(s) as necessary.
Photo 6-1
Photo 6-2
Photo 6-3
Photo 6-4
Photo 6-5
Photo 6-6
Photo 6-7
Photo 6-8
7)
AT the time of the inspection we observed that the garage identification number was recently changed 6 for 7. We recommend to consult with the listing agent and/or HOA about this situation.
Electric
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide detectors is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide detectors should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Service voltage (volts): 120-240
Condition of main service panel: Appeared serviceable
8)
Smoke alarms were missing on living room and/or in the attached garage. Additional smoke alarms should be installed as necessary so a functioning detector exists in each hallway leading to bedrooms, in each bedroom, on each level and in any attached garage. For more information, visit:
http://www.cpsc.gov/cpscpub/pubs/5077.htmlSmoke detectors and CO detectors were in good working condition.
Photo 8-1
Photo 8-2
Photo 8-3
9)
At the time of the inspection, electric system was in serviceable working condition. Lights and switches worked properly.
Doorbell was inoperable or damaged at the main entrance. The client wish to have one installed for convenience sake.
Photo 9-1
Photo 9-2
Photo 9-3
Photo 9-4
Plumbing / Fuel Systems
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Location of main water meter: By street
Location of main water shut-off: Building exterior
Water service: Public
Service pipe material: Copper
Condition of supply lines: Appeared serviceable
Condition of drain pipes: Appeared serviceable
Condition of waste lines: Appeared serviceable
Location(s) of plumbing clean-outs: Building exterior
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: Above ground
Location of main fuel shut-off valve: At gas meter
10)
Plumbing system inside the property, was in serviceable working condition. We did not observed any active leaks at the time of the inspection.
Photo 10-1
Photo 10-2
Photo 10-3
Photo 10-4
Photo 10-5
Photo 10-6
Photo 10-7
Photo 10-8
Photo 10-9
Photo 10-10
Photo 10-11
Water Heater
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
11)
Water heater was common for all the units. Water heater appeared to be in working condition There was hot water at the kitchen and bathroom.
Heating, Ventilation and Air Condition (HVAC)
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
12)
The furnace heating system was not fully evaluated because the gas supply was off and/or pilot light was off. Recommend that a full evaluation be made by a qualified person when conditions have been corrected so the system is operable. Note that the inspector does not operate shut-off valves, pilot lights or circuit breakers, or any controls other than normal controls (thermostat).
Photo 12-1
Photo 12-2
13)
The primary heating system for this home was powered by electricity, and the electric service to the home appeared to be rated at less than 200 amps. A 200 amp service is typically installed to provide adequate power for all-electric heat. Recommend consulting with a qualified electrician about upgrading the electric service. Note that the electric service's rating is based on the lowest rating for the meter base, the service conductors, the main service panel and the main disconnect switch. One or more of these components may need replacing to upgrade.
Photo 13-1
Kitchen
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: N/A (none installed)
Condition of refrigerator: Appeared serviceable
Condition of built: N/A (none installed)
Condition of hot water dispenser: N/A (none installed)
Condition of trash compactor: N/A (none installed)
14)
One or more electric receptacles (outlets) at the kitchen, bathroom(s) , garage exterior had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
Outdoors (since 1973)
Bathrooms (since 1975)
Garages (since 1978)
Kitchens (since 1987)
Crawl spaces and unfinished basements (since 1990)
Wet bar sinks (since 1993)
Laundry and utility sinks (since 2005)
For more information, visit:
http://www.cpsc.gov/cpscpub/pubs/099.pdf
Photo 14-1
15)
The cooktop exhaust fan was inoperable, noisy or vibrated and/or excessively slow . Recommend that a qualified person repair or replace as necessary.
Photo 15-1
16)
Kitchen, in general was in serviceable and good condition. Cabinets and counter tops were in good condition. Appliances were in working condition.
Photo 16-1
Photo 16-2
Photo 16-3
Photo 16-4
Photo 16-5
Photo 16-6
Photo 16-7
Bathrooms, Laundry and Sinks
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: Yes
17)
The exhaust fan was inoperable, noisy or vibrated or excessively weak or slow . Moisture may accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified person clean, repair or replace fans as necessary
Photo 17-1
Photo 17-2
18)
One or more cabinets, drawers and/or cabinet doors were deteriorated and/or did not opened /closed properly/ Recommend that a qualified person repair or replace as necessary.
Photo 18-1
19)
Bathrooms in general, were in serviceable and good condition. Toilets, sinks, showers and bath tubs were in working condition.
Photo 19-1
Photo 19-2
Photo 19-3
Photo 19-4
Photo 19-5
Interior, Doors and Windows
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Metal
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Flooring type or covering: Wood or wood products
20)
Glass in one or more windows was cracked, broken and/or missing. Recommend that a qualified contractor replace glass where necessary.
Photo 20-1
21)
One or more ceiling fans wobbled excessively during operation. This is a potential safety hazard and may be caused by loose fasteners, blades, rod-fan body junction, the fan itself being loose, or bent, misaligned or unbalanced blades. Recommend that a qualified person repair as necessary. For more information, visit:
http://www.google.com/search?q=unbalanced+ceiling+fan
Photo 21-1
Photo 21-2
22)
Doorbell was inoperable or damaged at the main entrance. The client wish to have one installed for convenience sake.
Photo 22-1
Photo 22-2
23)
One or more interior doors wouldn't latch or were difficult to latch. Recommend that a qualified person repair as necessary. For example, by adjusting latch plates or locksets.
Photo 23-1
24)
Interior of the property in general, was in serviceable and good condition. Doors and windows were in good and working condition. Floor was in good condition. Carpet was in serviceable condition. Walls were clean and in good condition.
Photo 24-1
Photo 24-2
Photo 24-3
Photo 24-4
Photo 24-5
Photo 24-6
Photo 24-7
Photo 24-8
25)
Screens were missing from some windows. These windows may not provide ventilation during months when insects are active.
Photo 25-1
Photo 25-2
Photo 25-3