Summary

Client(s):  Vernon Miller
Property address:  30311 Priem Rd
Elkhart IN 46514-8490
Inspection date:  Friday, October 25, 2019

This report published on Friday, October 25, 2019 3:55:16 PM EDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeMajor DefectCorrection likely involves a significant expense
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information


Grounds
1) Recommend replacing clean out On side of the house.
Photo
Photo 1-1 
2) Recommend a qualified person repair fence as needed.
Photo
Photo 2-1 

Roof
4) One or more gutters were damaged. Rainwater can come in contact with the building exterior or accumulate around the building foundation as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.

Back corner of the house
Photo
Photo 4-1 

Attic and Roof Structure
7) One or more exhaust fan ducts in the attic were not attached to a vent hood or cap. As a result, conditioned air will enter the attic when the fan is operated. Ducts terminating near an attic vent but without a dedicated vent hood or cap will likely blow conditioned air back into the attic. This can result in excessive moisture in the attic. Recommend that a qualified contractor repair per standard building practices, so exhaust fan ducts are permanently fastened to vent hoods or caps.

Electric
8) One or more ground fault circuit interrupter (GFCI) receptacles (outlets) wouldn't trip and/or wouldn't trip with a test instrument at the exterior. This is a potential shock hazard. Recommend that a qualified electrician evaluate and repair as necessary.

Back porch
Photo
Photo 8-1 
9) Neutral wires were doubled or bundled together under the same lug on the neutral bus bar in panel(s) #. This is a potential safety hazard in the event that one of the circuits needs to be isolated during servicing. For one neutral to be disconnected, other neutrals from energized circuits sharing the same lug will be loosened. Power surges may result on the energized circuits and result in damage or fire. Also, multiple wires under the same lug may not be secure, resulting in loose wires, arcing, sparks and fire. Recommend that a qualified electrician repair per standard building practices. For more information, visit:
http://www.reporthost.com/?DTNB

Also recommend isolating neutral and ground wires
Photo
Photo 9-1 
10) Smoke alarms were missing in the attached garage. Additional smoke alarms should be installed as necessary so a functioning alarm exists in each hallway leading to bedrooms, in each bedroom, on each level and in any attached garage. For more information, visit:
http://www.reporthost.com/?SMKALRM
11) One or more bushings were missing from where wires enter holes in panel(s) #. This is a potential safety hazard because the wiring insulation can be cut or abraded on the metal edge of the hole(s). Recommend that a qualified electrician install bushings where missing.
Photo
Photo 11-1 
12) Carbon monoxide alarms were missing from one or more sleeping areas and/or on one or more levels. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed in the vicinity of each sleeping area, on each level and in accordance with the manufacturer's recommendations. Recommend installing additional carbon monoxide alarms per these standards. For more information, visit:
http://www.reporthost.com/?COALRM
13) One or more globes or covers for light fixtures were missing or damaged. Recommend replacing as necessary to avoid exposed bulbs. With closet lighting or where flammable stored objects are near light fixtures, missing or broken covers can be a fire hazard.

Master bathroom
Photo
Photo 13-1 

Plumbing / Fuel Systems
15) The sump pump discharge pipe was routed so that it drained close to the foundation. Prolonged, high levels of moisture in soil can cause foundation settlement and failure. If drainage is near a crawl space or basement, water can accumulate in these spaces. Recommend that a qualified contractor repair as necessary so the discharge pipe terminates well away from the foundation and to soil that is sloping down and away from the foundation.
Photo
Photo 15-1 
16) Based on visible equipment or information provided to the inspector, this property appeared to have a yard irrigation (sprinkler) system. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. When this system is operated, recommend verifying that water is not directed at building exteriors, or directed so water accumulates around building foundations. Sprinkler heads may need to be adjusted, replaced or disabled. Consider having a qualified plumber verify that a backflow prevention device is installed per standard building practices to prevent cross-contamination of potable water. Recommend that a qualified specialist evaluate the irrigation system for other defects (e.g. leaks, damaged or malfunctioning sprinkler heads) and repair if necessary.

Heating, Ventilation and Air Condition (HVAC)
20) The last service date of the gas or oil-fired forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC contractor when it's serviced. For more information visit:
http://www.reporthost.com/?ANFURINSP
21) The estimated useful life for most heat pumps and air conditioning condensing units is 10-15 years. This unit appeared to be at this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.

Kitchen
26) The range could tip forward. An anti-tip bracket may not be installed. This is a potential safety hazard since the range can tip forward when weight is applied to the open door, such as when a small child climbs on it or if heavy objects are dropped on it. Anti-tip brackets have been sold with all free-standing ranges since 1985. Recommend installing an anti-tip bracket to eliminate this safety hazard. For more information, visit:
http://www.reporthost.com/?ATB
27) The dishwasher was inoperable. Recommend that a qualified specialist evaluate and repair or replace as necessary.
Photo
Photo 27-1 
28) Countertops and/or backsplashes were damaged or deteriorated. Recommend repairing or replacing as necessary.

Kitchen island is loose
Photo
Photo 28-1 

Bathrooms, Laundry and Sinks
30) The exhaust fan at location(s) #A and B was inoperable. Moisture may accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified person clean, repair or replace fans as necessary.

Basement bathroom
Main bath
Photo
Photo 30-1 
31) Recommend a qualified person replace handle on dryer door as necessary.
Photo
Photo 31-1 
32) The toilet fill valve or float mechanism in the toilet at location(s) #B and C did not operate properly or was inoperable. Recommend that a qualified person repair as necessary.

First floor main bathroom
Master bathroom
Photo
Photo 32-1