Speed Quality Home Inspection (Certificate#9929730)
3564 Elk Horn Trl SW Atlanta GA 30349-8794
Inspector: Antonio Speed
Property Inspection Report Unofficial version!
Client(s):
Britt Walker
Property address:
355 Brook Dr Sandy Springs GA 30328-2109
Inspection date:
Saturday, April 8, 2023
This report published on Saturday, April 8, 2023 4:24:39 PM EDT
This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
Safety
Poses a safety hazard
Major Defect
Correction likely involves a significant expense
Repair/Replace
Recommend repairing or replacing
Repair/Maintain
Recommend repair and/or maintenance
Maintain
Recommend ongoing maintenance
Evaluate
Recommend evaluation by a specialist
Monitor
Recommend monitoring in the future
Comment
For your information
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Rain
Temperature during inspection: Cold
Inspection fee: 275
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: 64
Source for main building age: Municipal records or property listing
Front of building faces: North
Main entrance faces: North
Occupied: No
1) Microbial growths were found at one or more locations in the basement. It is beyond the scope of this inspection to identify what substance or organism this staining is. However such staining is normally caused by excessively moist conditions, which in turn can be caused by plumbing or building envelope leaks and/or substandard ventilation. These conducive conditions should be corrected before making any attempts to remove or correct the staining. Normally affected materials such as drywall are removed, enclosed affected spaces are allowed to dry thoroughly, a mildewcide may be applied, and only then is drywall reinstalled. For evaluation and possible mitigation, consult with a qualified industrial hygienist or mold/moisture mitigation specialist. For more information, visit: http://www.reporthost.com/?MOLDCDC http://www.reporthost.com/?MOLDEPA
2) Microbial growths were found at one or more locations in . It is beyond the scope of this inspection to identify what substance or organism this staining is. However such staining is normally caused by excessively moist conditions, which in turn can be caused by plumbing or building envelope leaks and/or substandard ventilation. These conducive conditions should be corrected before making any attempts to remove or correct the staining. Normally affected materials such as drywall are removed, enclosed affected spaces are allowed to dry thoroughly, a mildewcide may be applied, and only then is drywall reinstalled. For evaluation and possible mitigation, consult with a qualified industrial hygienist or mold/moisture mitigation specialist. For more information, visit: http://www.reporthost.com/?MOLDCDC http://www.reporthost.com/?MOLDEPA
Photo 2-1 Evidence of a prior leak. Mold and rot on boards should be replaced. Photo 2-2
3) The water service was not turned on during the inspection. The inspector operates only "normal" controls such as faucets, and does not operate shut-off valves to the water meter or house. As a result, plumbing supply, drain waste and vent lines, traps, pumps, fixtures, and some appliances such as water heaters weren't fully evaluated. The water pressure was not determined. Recommend that a qualified person make a full evaluation of the plumbing system after the water supply is turned back on. Areas below the house should be evaluated after plumbing has been operated to check for leaks. Any problems that are found after this evaluation should be repaired by a qualified plumber.
4) The client should be aware that prior to 1976, factory-built homes in America were built only according to voluntary standards. Because this building was built prior to 1976, it may be significantly substandard in safety, efficiency, quality, durability, etc. Factory-built homes since 1976 have been required to comply with federal construction and safety standards (the HUD Code). This code is administered by the U.S. Department of Housing and Urban Development (HUD), and standardizes design, construction, energy efficiency, fire resistance, transportability, strength, and durability. It also mandates performance standards for the electrical, plumbing, air conditioning, thermal, and heating systems.
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Minor slope
5) Significant amounts of standing water or evidence of past accumulated water were found at one or more locations in the yard or landscaped areas, and no drain was visible. If evidence of past water was found (e.g. silt accumulation or staining), monitor these areas in the future during periods of heavy rain. If standing water exists, recommend that a qualified person repair as necessary. For example, installing one or more drains, or grading soil.
Photo 5-1 Standing water in yard should be redirected by grading of the yard or with drainage system.
6) Soil was in contact with one or more wooden deck, porch or balcony support posts. This is a conducive condition for wood destroying organisms. Even if posts are made of treated wood, the cut ends below soil may not have been field treated. Recommend grading soil or repairing as necessary to prevent wood-soil contact.
Photo 6-1 Deck boards should be on top of concrete pilars.
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.
Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of floor substructure above: Required repairs, replacement and/or evaluation (see comments below)
Pier or support post material: Steel
Beam material: Steel
Floor structure above: Solid wood joists
7)
Photo 7-1 Minor mortar cracking in joints should be repointed. Photo 7-2 Water from ceiling hole on basement stairs.
Photo 7-3 Galvanized pipes are known to rust and leak. Photo 7-4 Hole in basement stairway leaked water.
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Finished basement
Foundation/stem wall material: Concrete block
8) One or more minor cracks (1/8 inch or less) were found in the foundation. These didn't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitor them in the future. Numerous products exist to seal such cracks including hydraulic cement, non-shrinking grout, resilient caulks and epoxy sealants.
9) Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo 9-1 Trees to close to building could allow pest, rodents, and debris to enter home. Photo 9-2
10)
Photo 10-1 Some floor boards are deteriorating and should be replaced. Photo 10-2 Rotting boards should be replaced, also flashing should be installed to prevent roof leaks.
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Required repair, replacement and/or evaluation (see comments below)
Primary service type: Overhead
Number of service conductors: 2
Primary service overload protection type: Fuses
Condition of branch circuit wiring: Required repair, replacement and/or evaluation (see comments below)
11) Knob and tube wiring and/or related components at one or more locations was damaged or deteriorated. This is a potential fire and shock hazard. Recommend that a qualified electrician repair as necessary.
Photo 11-1 Outdated electrical panel should be upgraded. Photo 11-2
Photo 11-3
12) The electric service to this property appeared to be rated at substantially less than 200 amps and may be inadequate. Depending on the client's needs, recommend consulting with a qualified electrician about upgrading to a 200 amp service. Note that the electric service's rating is based on the lowest rating for the meter base, the service conductors, the main service panel and the main disconnect switch. One or more of these components may need replacing to upgrade.
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Required repair, replacement and/or evaluation (see comments below)
Water service: Public
Location of main water shut-off: Basement
Condition of supply lines: Required repair, replacement and/or evaluation (see comments below)
Supply pipe material: Galvanized steel
Condition of drain pipes: Required repair, replacement and/or evaluation (see comments below)
Drain pipe material: Galvanized steel
Condition of waste lines: Required repair, replacement and/or evaluation (see comments below)
13) The main water service pipe material was made of galvanized steel. Based on the age of the building, the apparent age of the pipe and/or the low-flow condition of the water supply system, this service pipe may have significant corrosion or rust on the inside and need replacing. Replacing the service pipe can significantly increase flow to the water supply pipes. Recommend consulting with a qualified plumber about replacing the main service pipe. Note that this can be an expensive repair since excavation is typically required.
Photo 13-1 Galvanized pipes are known to rust and leak. Photo 13-2 Galvanized exhaust pipes should be removed and upgraded.
14) One or more leaks were found in pipes or fittings. A qualified plumber should evaluate and repair as necessary.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Viewed from ground
Condition of roof surface material: Required repair, replacement and/or evaluation (see comments below)
Roof type: Gable
Condition of gutters, downspouts and extensions: Required repair, replacement and/or evaluation (see comments below)
15) The roof surface appeared to be near the end of its service life and will likely need replacing in the near future even if repairs are made now. Recommend discussing replacement options with a qualified contractor, and budgeting for a replacement roof surface in the near future. The client may also wish to consider having a qualified contractor attempt to issue a "5 year roof certificate."
16) One or more gutters and/or downspouts were damaged. Rainwater can come in contact with the building exterior or accumulate around the building foundation as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Condition of roof structure: Required repair, replacement and/or evaluation (see comments below)
Roof structure type: Trusses
17) One or more rafters in the roof structure were damaged or split. This may significantly weaken the roof structure. Recommend that a qualified contractor repair as necessary.
Photo 17-1 Some attic boards showed signs of moisture and rotting. Photo 17-2 Attic access was barely accessible.
18) Attic spaces less than 30 inches in height may exist in this building, but had no visible access points. This is acceptable per standard building practices. However, these spaces were not inspected and are excluded from this inspection.
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air
General heating distribution type(s): Ducts and registers