Ark Engineering Consultant, P.C.

213-37 39th Ave, Suite 298 
Bayside NY 11361-2071
Inspector: Rich Lee

Property Inspection Report

Client(s):  Ms. Cordelia Li
Property address:  47 Roosevelt Ave
Syosset NY 11791-3013
Inspection date:  Saturday, March 19, 2022

This report published on Monday, March 21, 2022 5:11:43 PM EDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeMajor DefectCorrection likely involves a significant expense
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Basement
Roof
Attic and Roof Structure
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows

View summary

General Information
Table of contents
Report number: 22032
Time started: 9:30 AM
Time finished: 10:45 AM
Present during inspection: Client, Property owner, Realtor
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain), Sunny
Temperature during inspection: Cool, Warm
Type of building: Two family Residence (Reported by Listing Agent)
Buildings inspected: One house
Number of residential units inspected: 2
Age of main building: Reported built in 1950
Front of building faces: North
Main entrance faces: North
Occupied: Yes
1) The inspector operates only "normal" controls such as faucets, and does not operate shut-off valves to the water meter or building. As a result, plumbing supply, drain waste and vent lines, traps, pumps, fixtures, and some appliances such as water heaters weren't fully evaluated. The water pressure was not determined. Recommend that a qualified person make a full evaluation of the plumbing system. Areas below the building should be evaluated after plumbing has been operated to check for leaks. Any problems that are found after this evaluation should be repaired by a qualified plumber.
2) The client should be aware that prior to 1976, factory-built homes in America were built only according to voluntary standards. Because this building was built prior to 1976, it may be significantly substandard in safety, efficiency, quality, durability, etc. Factory-built homes since 1976 have been required to comply with federal construction and safety standards (the HUD Code). This code is administered by the U.S. Department of Housing and Urban Development (HUD), and standardizes design, construction, energy efficiency, fire resistance, transportability, strength, and durability. It also mandates performance standards for the electrical, plumbing, air conditioning, thermal, and heating systems.
3)  The inspector operates only "normal controls" such as switches or knobs, and does not reset or turn on circuit breakers or remove or install fuses. As a result, branch circuit wiring, receptacles, fixtures such as lights and fans, switches, ground fault circuit interrupter (GFCI) devices, arc fault circuit interrupter (AFCI) devices, and some appliances such as electrically powered water heaters, forced air furnaces, heat pumps, air conditioning units, and kitchen appliances weren't fully evaluated. Recommend that a qualified person make a full evaluation of the electric system and electrically powered appliances. Any problems that are found after this evaluation should be repaired by a qualified contractor.
4)  The inspector operates only "normal" controls such as thermostats and on/off switches, and does not operate oil shut-off valves or attempt to re-light furnaces. As a result, items such as but not limited to the fuel oil supply system and oil fired furnaces or boilers weren't fully evaluated. Recommend that a qualified person make a full evaluation of the fuel oil supply system and oil-fired appliances. Any problems that are found after this evaluation should be repaired by a qualified contractor.
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level, Minor slope
Condition of driveway: Required repair, replacement and/or evaluation (see comments below), Near, at or beyond service life
Driveway material: Asphalt
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Asphalt
5) Cracks, holes, settlement, heaving and/or deterioration were found in the driveway. Recommend that qualified contractor repair as necessary.
Photo
Photo 5-1 
Photo
Photo 5-2 
Photo
Photo 5-3 
Exterior and Foundation
Table of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering:
Apparent wall structure: Wood frame
Wall covering: Stucco, Brick veneer
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Unfinished basement
Foundation/stem wall material: Concrete block
Footing material (under foundation stem wall): Not determined (inaccessible or obscured)
6) The masonry (brick or stone) veneer was deteriorated or damaged in some areas. Where cracks or openings are exposed, water can enter the wall structure causing mold, fungal growth and structural damage. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor repair as necessary. For example, by repointing mortar or replacing broken or missing masonry.
Photo
Photo 6-1 
Photo
Photo 6-2 
Photo
Photo 6-3 
Photo
Photo 6-4 
Photo
Photo 6-5 
Photo
Photo 6-6 
Photo
Photo 6-7 
Photo
Photo 6-8 
7) One or more windows or doors were installed with no "drip cap" or "Z" flashings installed above them. Better building practices call for such flashings, which greatly reduce the chance of leaks above windows and doors. Without this flashing, caulk and paint must be maintained or water can enter the wall structure and cause rot and possible structural damage. Depending on the exposure (e.g. roof overhang, height of exterior wall, direction of prevailing rain) this may or may not be an issue. The client should monitor these areas in the future and maintain caulk and paint as necessary. Consult with a qualified contractor about installing flashings where needed, and per standard building practices. Note that when trim or siding is removed to install flashing, damaged wood may be found and additional repairs may be needed.
Photo
Photo 7-1 
Photo
Photo 7-2 
8) Cracks, deterioration and/or damage were found in one or more areas of the exterior stucco finish. In damp climates, moisture can enter cracks or damaged areas and further deteriorate the stucco. Also the wall behind the stucco can become damaged from moisture. Note that areas behind the stucco are inaccessible and excluded from this inspection. Recommend that a qualified contractor repair or replace stucco as necessary.
Photo
Photo 8-1 
Photo
Photo 8-2 
Photo
Photo 8-3 
Photo
Photo 8-4 
Photo
Photo 8-5 
Photo
Photo 8-6 
Photo
Photo 8-7 
Photo
Photo 8-8 
Photo
Photo 8-9 
Photo
Photo 8-10 
Photo
Photo 8-11 
Photo
Photo 8-12 
Photo
Photo 8-13 
9) Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 9-1 
Photo
Photo 9-2 
Photo
Photo 9-3 
Photo
Photo 9-4 
10) Trees were in contact with or were close to the building at one or more locations. Damage to the building can occur, especially during high winds, or may have already occurred (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.
Photo
Photo 10-1 
Photo
Photo 10-2 
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Wood
Beam material: Solid wood
Floor structure above: Wood trusses
Condition of insulation underneath floor above: Not applicable, none installed
Insulation material underneath floor above: None visible
11) Evidence of prior water intrusion was found in one or more sections of the basement. For example, water stains or rust at support post bases, efflorescence on the foundation, etc. Accumulated water is a conducive condition for wood-destroying organisms and should not be present in the basement. Recommend reviewing any disclosure statements available and ask the property owner about past accumulation of water in the basement. The basement should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, then recommend that a qualified contractor who specializes in drainage issues evaluate and repair as necessary. Typical repairs for preventing water from accumulating in basements include:
  • Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
  • Improving perimeter grading
  • Repairing, installing or improving underground footing and/or curtain drains
Ideally, water should not enter basements, but if water must be controlled after it enters the basement, then typical repairs include installing a sump pump.
Photo
Photo 11-1 
Photo
Photo 11-2 
Photo
Photo 11-3 
Photo
Photo 11-4 
Photo
Photo 11-5 
Photo
Photo 11-6 
Photo
Photo 11-7 
Photo
Photo 11-8 
Photo
Photo 11-9 
Photo
Photo 11-10 
Photo
Photo 11-11 
Photo
Photo 11-12 
Photo
Photo 11-13 
Photo
Photo 11-14 
Photo
Photo 11-15 
Photo
Photo 11-16 
12) One or more minor cracks (1/8 inch or less) were found in the foundation. These didn't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitor them in the future. Numerous products exist to seal such cracks including hydraulic cement, non-shrinking grout, resilient caulks and epoxy sealants.
Photo
Photo 12-1 
Photo
Photo 12-2 
Photo
Photo 12-3 
Photo
Photo 12-4 
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Viewed from ground
Condition of roof surface material: Required repair, replacement and/or evaluation (see comments below)
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Required repair, replacement and/or evaluation (see comments below)
Condition of gutters, downspouts and extensions: Appeared serviceable
13) The age of the roof could not be determined at the time of inspection. A roof surface near the end of its service life will likely need replacing in the near future even if repairs are made now. Recommend discussing replacement options with a qualified contractor, and budgeting for a replacement roof surface in the near future. The client may also wish to consider having a qualified contractor attempt to issue a "5 year roof certificate."
Photo
Photo 13-1 
Photo
Photo 13-2 
14) One or more roof flashings were missing. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.

The chimney flashing appeared to be missing, damaged, or beyond its lifespan.
15) Significant amounts of debris that accumulate in one or more gutters or downspouts can overflow and cause water to come in contact with the building exterior, or water can accumulate around the foundation. This is a conducive condition for wood-destroying organisms. Recommend cleaning gutters and downspouts now and as necessary in the future.
16) Significant amounts of debris such as leaves, needles, seeds, etc. can accumulate on the roof surface. Water may not flow easily off the roof, and can enter gaps in the roof surface. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend cleaning debris from the roof surface now and as necessary in the future.
Attic and Roof Structure
Table of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Condition of roof structure: Not determined (inaccessible or obscured)
Roof structure type: Not determined (inaccessible or obscured)
Ceiling structure: Not determined (inaccessible or obscured)
Ceiling insulation material: Not determined (inaccessible or obscured)
Approximate attic insulation R value (may vary in areas): Not determined (inaccessible or obscured)
Condition of roof ventilation: Not determined (inaccessible or obscured)
17) No accessible attic spaces were found or inspected at this property. The inspector attempts to locate attic access points and evaluate attic spaces where possible. When a home is occupied, such access points may be obscured by stored items or furnishings. Home inspection standards of practice do not require inspectors to move stored items, furnishings or personal belongings. If such access points are found in the future and/or made accessible, a qualified person should fully evaluate those attic spaces and roof structures.
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Number of service conductors: 2
Primary service overload protection type: Circuit breakers
Main disconnect rating (amps): 100 per panel, total of 2 panels
Condition of main service panel: Appeared serviceable
Condition of sub-panel(s): Appeared serviceable
Location of main service panel #A: Basement
Location of main service panel #B: Basement
Plumbing / Fuel Systems
Table of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Condition of supply lines: Appeared serviceable
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic, Galvanized steel
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic, Galvanized steel
Vent pipe condition: Not determined (inaccessible, obscured, or water service off)
Type of irrigation system supply source: Public
Condition of fuel system: Not determined (gas service off or no fuel oil)
Visible fuel storage systems: Below ground
Water Heater
Table of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Integral with heating system, tankless
Energy source: Oil
Estimated age: not determined
Location of water heater: Basement
Heating, Ventilation and Air Condition (HVAC)
Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Oil Burner
General heating distribution type(s): Pipes and radiators
Last service date of primary heat source: 2/1/2022
Source for last service date of primary heat source: Label
Condition of controls: Appeared serviceable
Fireplaces, Stoves, Chimneys and Flues
Table of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Appeared serviceable
Wood-burning fireplace type: Masonry
Condition of chimneys and flues: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below), Maintenance
Wood-burning chimney type: Masonry
18) One or more solid fuel-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all solid fuel-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at:
http://www.reporthost.com/?CSIA
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of ranges, cooktops and/or ovens: Appeared serviceable
Range, cooktop, oven type: Electric
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: N/A (none installed)
Bathrooms, Laundry and Sinks
Table of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath, first floor
Location #B: Full bath, second floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Bathroom and laundry ventilation type: Windows
19) Gaps, no caulk, or substandard caulking were found around the sink or bathtub at location(s) #A. Water can penetrate these areas and cause damage. Recommend that a qualified person repair as necessary. For example, by installing or replacing caulk.
Photo
Photo 19-1 
Photo
Photo 19-2 
Photo
Photo 19-3 
Interior, Doors and Windows
Table of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood
Condition of interior doors: Appeared serviceable
Condition of walls and ceilings: Appeared serviceable, Required repairs, replacement and/or evaluation (see comments below)
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Flooring type or covering: Carpet
20) Minor cracks, nail pops and/or blemishes were found in walls and/or ceilings in one or more areas. Cracks and nail pops are common, are often caused by lumber shrinkage or minor settlement, and can be more or less noticeable depending on changes in humidity. They did not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons.
Photo
Photo 20-1 
Photo
Photo 20-2 
Photo
Photo 20-3 
Photo
Photo 20-4 
Photo
Photo 20-5 
Photo
Photo 20-6 
Photo
Photo 20-7 
Photo
Photo 20-8 
Photo
Photo 20-9 
Photo
Photo 20-10 
Photo
Photo 20-11 
Photo
Photo 20-12 
Photo
Photo 20-13 
Photo
Photo 20-14 
Photo
Photo 20-15 
Photo
Photo 20-16 
Photo
Photo 20-17 
Photo
Photo 20-18 
Photo
Photo 20-19 
Photo
Photo 20-20 
Photo
Photo 20-21 
Photo
Photo 20-22 
Photo
Photo 20-23 
Photo
Photo 20-24 
Photo
Photo 20-25 
Photo
Photo 20-26 
Photo
Photo 20-27 
Photo
Photo 20-28 
Photo
Photo 20-29 

Report Suggestions & Limitations:

All appliances, appurtenances, electrical and mechanical systems, defects and leaks should be checked and verified to be in working condition prior to purchase.

A termite inspection was not performed. A certified termite inspection and preventative termite treatments should be implemented.

This is not an environmental report. Environmental hazards including but not limited to lead paint, mold, algae, radon, asbestos, toxins and other environmental contaminates have not been tested and is not part of this report. Consult with certified hygienist or specialist for such tests.

This report is not a code compliance inspection. It is suggested that you check with the current owner or local code enforcement agencies such as but not limited to the local building department for all applicable permits and certificates of occupancy if they exist.

This report is based on a visual inspection that is preliminary and limited in scope that was accessible from the ground level. Areas concealed, obstructed and/or closed off were not inspected and did not involve dismantling or removal of such areas or items. The information and opinions rendered in this report are limited and shall not be evaluated beyond its capabilities. Some existing conditions may not have been inspected due to limited access, obstructed areas, and available line of sight. This report is date sensitive and represents the condition of the inspected property at the time of inspection. Material samples, testing equipment, and monitoring equipment were not taken and/or used for this inspection. No guarantee or warranty on the condition of the property or its’ systems is made with respect to this report, whether implied or expressed.

This report is prepared on behalf of and exclusively for the client. Alteration or unauthorized reproduction is prohibited without written consent.