Single Family Home Inspection Report
Unofficial version!

Client(s): Tami Zapata
Property address: 1652 Wilson Ave
Escondido CA 92027-2038
Inspection date: Monday, June 10, 2024

This report published on Wednesday, August 7, 2024 9:15:15 PM PDT

[/b]This report is the exclusive property of Elite Property Inspections and for Tami Zapata listed in the report title. Use of this report by any unauthorized persons is prohibited. This is a limited Inspection: It is impossible to inspect every square inch of every area of a home in a limited time frame. A home inspection is designed to reflect, as accurately as possible, the visible condition of the home at the time of the inspection only and does not reflect, anticipate or predict future conditions. Conditions at a home for sale can change radically in only a day or two, so a home inspection is not meant to guarantee what condition a home will be in when the transaction closes. It’s not uncommon for conditions to change between the time of the inspection and the closing date. During this inspection your inspector did not dismantle equipment, dismantle any structural items, apply stress or destructive testing. Areas that are hidden, painted over, disguised and/or not readily visible are not covered in this report. Our report is not a guarantee or warranty on the condition of your property or its contents. This report provides an unbiased visual inspection only. Elite Property Inspections are performed with consideration given the age of the structure. Defects will be indicated and marked as such, even though the condition may be normal for the age and should be inspected by the appropriate licensed contractor. Opinions vary from person to person and this report is the opinion of the inspector and must be considered as such. The Inspector does not determine the age or remaining life of any system or building material during this inspection. Cosmetic items are considered obvious and are often not included in your report.

How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeServiceableItem or component is in serviceable condition
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds and Roof
Electricity
Plumbing
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Kitchen
Bathrooms, Sinks and Laundry
Interior, Windows(Int/Ext) & Attic
View summary

General InformationTable of contents
Report number:06102024: 4 Bedroom single family home
Time finished:: 1430
Present During inspection: Property owner
Client present for discussion at end of inspection: Yes
Inspector: Elite Property Inspections: Elite Property Inspections Inspectors
Weather Conditions During inspection: Dry (no rain), Sunny
Temperature During Inspection: Warm
Ground Condition: Dry
Recent Weather: Rain
Overnight Temperature: Warm
Inspection fee: $300:
Payment Method: Check
Front of Building Faces: North
Main Entrance Faces: North
Occupied by Three Tenants: Yes
1)  The residential dwelling unit appeared to be single family home that is managed and maintained by a "Home Owners". This inspection is limited to a visual evaluation of the systems and components that are located within the dwelling home inspected. The current condition of "Common Elements" are excluded from this inspection. Such elements include, but are not limited to:
  • The building site condition, structural stability, drainage systems and insulation
  • All exterior surfaces, materials and structure
  • All roof surfaces, materials and structure
  • All attic spaces
  • The building foundation, floor substructure and all spaces below, such as basements and/or crawl spaces
  • All stairs, landings, porches, hallways, walks and balconies, elevators, utility metering, parking stalls/ports
  • All decks, patios, pools, spas, recreational areas/equipment
  • All common areas on the property
Any comments regarding these items in this report have been made as a courtesy only. Consult with the Home Owners
2)  The water service was turned on during the inspection. The inspector operates only "normal" controls such as faucets, and does not operate shut-off valves to the water meter or house. As a result, plumbing supply, drain waste and vent lines, traps, pumps, fixtures, and some appliances such as water heaters weren't fully evaluated. The water pressure was not determined. Recommend that a qualified person make a full evaluation of the plumbing system after the water supply is turned back on. Areas below the house should be evaluated after plumbing has been operated to check for leaks. Any problems that are found after this evaluation should be repaired by a qualified plumber.
3)  The natural gas service was turned on during the inspection. The inspector operates only "normal" controls such as thermostats, stove burner knobs, and on/off switches, and does not operate gas shut-off valves or activate pilot lights. As a result, items such as but not limited to the gas supply system, gas-fired water heater(s), gas-fired forced air furnace(s), gas fireplace(s), stove(s), and range(s) weren't fully evaluated. The inspector was unable to test for gas leaks. Recommend that a qualified person make a full evaluation of the gas supply system and gas-fired appliances after the gas supply is turned back on. Any problems that are found after this evaluation should be repaired by a qualified contractor.
4)  Electricity was available during the inspection. The inspector operates only "normal controls" such as switches or knobs, and does not reset or turn on circuit breakers or remove or install fuses. As a result, branch circuit wiring, receptacles, fixtures such as lights and fans, switches, ground fault circuit interrupter (GFCI) devices, arc fault circuit interrupter (AFCI) devices, and some appliances such as electrically powered water heaters, forced air furnaces, heat pumps, air conditioning units, and kitchen appliances weren't fully evaluated.
5)  A few areas and items at this property were obscured by furniture, and stored items, due to home being dwelled in. This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.
6)  Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation.
Grounds and RoofTable of contents
Condition of Patio: Appeared serviceable
Patio Material: Concrete
7)  
Photo
Photo 7-1 Front view
Photo
Photo 7-2 Front right side view
Photo
Photo 7-3 Front right side view of home
Photo
Photo 7-4 Front right side view of home
Photo
Photo 7-5 Back side of house (right side view from street)
Photo
Photo 7-6 Back side of house view looking towards street
Photo
Photo 7-7 Backyard view
Photo
Photo 7-8 Backyard right view
Photo
Photo 7-9 Back left view of home
Photo
Photo 7-10 Back view of home
Photo
Photo 7-11 Backyard
Photo
Photo 7-12 Backyard
Photo
Photo 7-13 Side of house
Photo
Photo 7-14 Side of house
Photo
Photo 7-15 Left side of home view from street side
Photo
Photo 7-16 Left side, backyard
Photo
Photo 7-17 Front left side of home
Photo
Photo 7-18 Garage side, right view
Photo
Photo 7-19 Front view of home and garage
Photo
Photo 7-20 Front view of home
Photo
Photo 7-21 side of house
8)  
Photo
Photo 8-1 Roof installed in 2020 - checked good at time of inspection
Photo
Photo 8-2 Roof installed in 2020 - checked good at time of inspection
Photo
Photo 8-3 Roof installed in 2020 - checked good at time of inspection
Photo
Photo 8-4 Roof installed in 2020 - checked good at time of inspection
Photo
Photo 8-5 Roof installed in 2020 - checked good at time of inspection
9)   
Photo
Photo 9-1 Roof installed in 2020 - checked good at time of inspection
10)   
Photo
Photo 10-1 Back yard
11)   
Photo
Photo 11-1 
Photo
Photo 11-2 
Photo
Photo 11-3 
Photo
Photo 11-4 
Photo
Photo 11-5 
Photo
Photo 11-6 
Photo
Photo 11-7 
Photo
Photo 11-8 
Photo
Photo 11-9 
Photo
Photo 11-10 
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric Service Condition: Appeared serviceable
Primary Service Type: Overhead
Primary Service Overload Protection Type: Circuit breakers
Condition of Main Service Panel: Appeared serviceable
Condition of Branch Circuit Wiring: Serviceable
Branch circuit wiring type: non-metallic sheathed
12)  All ground fault circuit interrupter (GFCI) circuit breakers in panel(s) # would reset when tested. GFCI breakers reduce the chance of shock when using equipment in wet areas. This is a potential shock hazard. Recommend that a qualified electrician evaluate and repair as necessary.
13)  All ground fault circuit interrupter (GFCI) devices protecting receptacles at the kitchen, bathroom(s)!1/2 bath, 3/4 bath, full bath in master bath, and laundry area would trip when tested. All would tripped when energized.
14)  
Photo
Photo 14-1 All lighting in hallway checked good
Photo
Photo 14-2 All lighting in bedrooms fully functional and checked good
Photo
Photo 14-3 All lighting in bathrooms checked good
Photo
Photo 14-4 Master bathroom lights checked good
Photo
Photo 14-5 All bedroom lights functional, checked good. All closet sliding doors fully functional.
Photo
Photo 14-6 All electrical outlets checked good at time of inspeciton
Photo
Photo 14-7 All bathroom lights fully functional at time of inspection
15)  Electrical Panel
Located in garage.
Photo
Photo 15-1 Electrical panel located in garage
Photo
Photo 15-2 Electrical panel located in garage
Photo
Photo 15-3 Electrical panel
Photo
Photo 15-4 Electrical panel located in garage
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
16)  
Photo
Photo 16-1 Under kitchen sink. No leaks, no moisture detected at time of inspection.
Photo
Photo 16-2 
17)  
Photo
Photo 17-1 Master bathroom sink
Photo
Photo 17-2 Fully functional and pressure checked good at time of inspection
Photo
Photo 17-3 Master shower
Photo
Photo 17-4 Master bathroom shower
Photo
Photo 17-5 Main bathroom - fully functional, checked good at time of inspection. No moisture detected around toilet nor bathtub at time of inspection.
Photo
Photo 17-6 Main bathroom sink - fully functional, checked good at time of inspection.
Photo
Photo 17-7 Main bathroom shower - fully functional, checked good at time of inspection.
Photo
Photo 17-8 Second bathroom shower - fully functional, checked good at time of inspection.
Photo
Photo 17-9 Master bathroom sink - fully functional, checked good at time of inspection.
Photo
Photo 17-10 Master bathroom shower - fully functional, checked good at time of inspection.
Photo
Photo 17-11 Master bathroom shower - fully functional, checked good at time of inspection.
Photo
Photo 17-12 Master bathroom shower - fully functional, checked good at time of inspection.
Photo
Photo 17-13 Fully functional when operated at time of inspection
Photo
Photo 17-14 Kitchen sink and under sink before items were moved.
18)   
Photo
Photo 18-1 The entire house was redone with copper piping 15 years ago.
Photo
Photo 18-2 
Photo
Photo 18-3 The entire house was redone with copper piping 15 years ago.
Water HeaterTable of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
19)  
Photo
Photo 19-1 Water heater - strapped checked good at time of inspection
Photo
Photo 19-2 
Photo
Photo 19-3 Water heater
Photo
Photo 19-4 Checked good at time of inspection
20)   
Photo
Photo 20-1 Water heater
Photo
Photo 20-2 Checked good at time of inspection
Photo
Photo 20-3 Top of water heater
Heating, Ventilation and Air Condition (HVAC)Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
21)  
Photo
Photo 21-1 This system is approx. 15 years old
Photo
Photo 21-2 Temp guage fully functional at time of inspection
22)   The air system. is approx. 15 years old
23)   
Photo
Photo 23-1 
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
24)  
Photo
Photo 24-1 Dishwasher installed in 2022 - checked good at time of inspection
Photo
Photo 24-2 Refrigerator - 2022
Photo
Photo 24-3 Refrigerator - 2022
Photo
Photo 24-4 Refrigerator tag
Photo
Photo 24-5 Kitchen sink and under sink view before items were moved.
Photo
Photo 24-6 Fully functional when operated at time of inspection
Photo
Photo 24-7 Dishwasher installed in 2022
Photo
Photo 24-8 Kitchen sink and under sink before items were moved.
25)  
Photo
Photo 25-1 Kitchen sink and under sink view before items were moved.
Photo
Photo 25-2 Fully functional when operated at time of inspection
Photo
Photo 25-3 Dishwasher installed in 2022
26)  
Photo
Photo 26-1 Under kitchen sink. No leaks, no moisture detected at time of inspection.
Bathrooms, Sinks and LaundryTable of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
27)  
Photo
Photo 27-1 Master bathroom sink
Photo
Photo 27-2 checking for moisture and leaks. None at time of inspection.
Photo
Photo 27-3 Master bathroom sink. Faucet and handles checked good.
Photo
Photo 27-4 Fully functional and pressure checked good at time of inspection
Photo
Photo 27-5 
Photo
Photo 27-6 Master Shower
Photo
Photo 27-7 Master shower
Photo
Photo 27-8 Master bathroom shower
Photo
Photo 27-9 Main bathroom - fully functional, checked good at time of inspection. No moisture detected around toilet nor bathtub at time of inspection.
Photo
Photo 27-10 Main bathroom sink - fully functional, checked good at time of inspection.
Photo
Photo 27-11 Main bathroom shower - fully functional, checked good at time of inspection.
Photo
Photo 27-12 Second bathroom shower - fully functional, checked good at time of inspection.
Photo
Photo 27-13 Second bathroom shower - fully functional, checked good at time of inspection.
Photo
Photo 27-14 Main bathroom shower - fully functional, checked good at time of inspection.
Photo
Photo 27-15 Master bathroom sink - fully functional, checked good at time of inspection.
Photo
Photo 27-16 Master bathroom shower - fully functional, checked good at time of inspection.
Photo
Photo 27-17 Master bathroom shower - fully functional, checked good at time of inspection.
Photo
Photo 27-18 Master bathroom shower - fully functional, checked good at time of inspection.
Photo
Photo 27-19 Main bathroom sink
28)  
Photo
Photo 28-1 Washer & Dryer units - 2022
29)  No issues
Photo
Photo 29-1 No leaks. No moisture. Checked good at time of the inspection.
30)  
Photo
Photo 30-1 
Photo
Photo 30-2 
Photo
Photo 30-3 
Photo
Photo 30-4 
31)  No leaks and no moisture detected at time of inspection.
All piping new. New stoppers in both bathrooms. All piping is copper piping throughout the house. This was done approximately 15 year ago, when the home was remodeled.
Photo
Photo 31-1 Old stain. No leaks and no moisture was detected at time of inspection.
Photo
Photo 31-2 Main bathroom under sink. Checked good, no leaks nor moisture was detected at time of inspection.
Photo
Photo 31-3 
32)  No leaks and no moisture detected at time of inspection.
Photo
Photo 32-1 Master bathroom under sink. No leaks and no moisture detected. Fully dry at time of inspection.
Photo
Photo 32-2 
Photo
Photo 32-3 
Photo
Photo 32-4 Checked good; no issues
Photo
Photo 32-5 
Photo
Photo 32-6 
Interior, Windows(Int/Ext) & AtticTable of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
33)  
Photo
Photo 33-1 All lighting in hallway checked good
Photo
Photo 33-2 Back view of home
Photo
Photo 33-3 Right side view of house


Photo
Photo X-1 Attic view
Photo
Photo X-2 Attic
Photo
Photo X-3 Can add a little more insulation is bald areas.
Photo
Photo X-4 
Photo
Photo X-5 
Photo
Photo X-6 
Photo
Photo X-7 Entrance to attic. Insulation is thick - checked good.
Photo
Photo X-8