This report published on Tuesday, April 12, 2022 10:50:18 PM EDT
Thank you for selecting Dun Rite Home Inspection. We understand that a real estate purchase may be the largest expense of anyone’s life, that is why we strived to give you a comprehensive inspection report, making every reasonable effort to disclose the conditions of the property on the day of the inspection. The inspection report however will not reveal information on concealed items or items that inspector was unable to inspect on the day of inspection. We understand that the information provided to you in this report will assist you in understanding the condition of the property and assist you in making an informed purchase decision.
This inspection complies with the rules and regulations that govern the New York State Standards of Practice (Title 19 NYCRR, Part 197-5), as well as American Society of Home Inspectors’ (ASHI) Standards of Practice and the International Association of Certified Home Inspectors’ (InterNACHI) Standards of Practice.
The Home Inspection Report contains a review of the components in the following basic categories; General Information, Grounds, Exterior and Foundation, Basements/Crawl Space, Roofing, Attic and Roof Structure, Garage / Carport, Electrical, Plumbing / Fuel System, Water Heater, Heating/Ventilation/ Air-Conditioning (HVAC), Fireplaces, Kitchens, Bathrooms, Interior and Wood Destroying Organisms. Additional categories may or may not be included. This report is intended to provide you with an explanation of material defects observed on the date and time of the inspection. It does not guarantee that there may be latent defects that cannot be observed at the time and date of this inspection report due to obstructions, weather, covering, etc.
This Home Inspection Report is the exclusive property of Dun Rite Home Inspection and the client(s) listed in the report title, use of this report by any unauthorized person(s) is prohibited.
The inspection was conducted in the safest manner possible, adhering to safe practices, social distancing and preventing the spread of the covid-19 virus. At the time of inspection, the inspector was 100% vaccinated and did not have any of the symptoms associated with the Covid-19 virus. In addition the inspector has not engaged in travels outside the United States of America in the preceding three (3) months.
Dun Rite Home Inspection Anthony Ottombrino (917) 751-6405
New York State Home Inspection License # 16000127627 N.Y.S. DEC Categories/Subcategories of Certification 7c (Termite # T2904245)
How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
Safety
Poses a safety hazard
Repair/Replace
Recommend repairing or replacing
Repair/Maintain
Recommend repair and/or maintenance
Minor Defect
Correction likely involves only a minor expense
Maintain
Recommend ongoing maintenance
Evaluate
Recommend evaluation by a specialist
Monitor
Recommend monitoring in the future
Comment
For your information
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp
Client present for discussion at end of inspection: Yes
Inspector: Anthony Ottombrino
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Cool
Ground condition: Damp
Recent weather: Rain
Overnight temperature: Cold
Inspection fee: $575.00
Payment method: Zelle payment
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: 58 years
Source for main building age: Property owner
Front of building faces: North
Main entrance faces: North
Occupied: Yes
1) Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit: https://www.reporthost.com/?EPA https://www.reporthost.com/?CPSC https://www.reporthost.com/?CDC
2) Some areas and items at this property were obscured by . This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Moderate slope
Condition of driveway: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Driveway material: Asphalt
Condition of deck, patio and/or porch covers: Appeared serviceable, Required repairs, replacement and/or evaluation (see comments below)
Deck, patio, porch cover material and type: Open
Condition of decks, porches and/or balconies: Appeared serviceable, Required repairs, replacement and/or evaluation (see comments below), repair rotted support post at deck
Deck, porch and/or balcony material: Wood
Condition of stairs, handrails and guardrails: Appeared serviceable, Required repairs, replacement and/or evaluation (see comments below), deck railing at the backyard was lose recomend repair qualified contractor
Exterior stair material: Wood
3) Flashing appeared to be missing from above one or more deck or porch ledger boards, or could not be verified. Missing flashing at this location can cause moisture to accumulate between the ledger boards and the building. Fungal rot may occur in this area and cause the ledger board fasteners to fail. The deck may separate from the building in this event. This is a potential safety hazard. Recommend that a qualified contractor install flashing above ledger boards per standard building practices. For more information, visit: https://www.reporthost.com/?LB https://www.reporthost.com/?SD
4) Handrails at one or more flights of stairs were loose and/or wobbly. This is a safety hazard. Recommend that a qualified person repair as necessary.
5) Fungal rot was found in support posts at one or more structures covering decks, patios and/or porches. Recommend that a qualified person repair as necessary. All rotten wood should be replaced.
6) Wooden support posts for the deck or porch were resting directly on concrete piers or footings below. Water may wick up into the support post ends and result in elevated levels of moisture in the wooden support post ends. This is a conducive condition for wood-destroying organisms. Support posts should rest in metal brackets above concrete piers or footings, or should be separated from the concrete below by impervious membranes such as composition shingle scraps. Even if posts are made of treated wood the cut ends may not have been field-treated, leaving little or no preservative at the post center. Recommend that a qualified contractor repair per standard building practices. For example, by installing composition shingle scraps between the posts and the concrete below.
7) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in the driveway, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.
8) The asphalt driveway surface was worn and is prone to developing cracks from water penetration. Recommend that a qualified person reseal the driveway. For more information, visit: https://www.reporthost.com/?RAD
9) Soil was in contact with one or more wooden deck, porch or balcony support posts. This is a conducive condition for wood destroying organisms. Even if posts are made of treated wood, the cut ends below soil may not have been field treated. Recommend grading soil or repairing as necessary to prevent wood-soil contact.
10) Some nails securing decking boards were loose and were not flush with the surfaces of boards. Boards are more likely to loosen and warp. This may pose a safety hazard to those with bare feet. Recommend that a qualified person repair as necessary. For example, by replacing nails or installing screws. Note that existing nails that are simply pounded back in will be likely to loosen again.
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground, from a ladder
Condition of wall exterior covering: Appeared serviceable, Required repairs, replacement and/or evaluation (see comments below)
Apparent wall structure: Wood frame
Wall covering: Wood, Brick veneer
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Unfinished basement
Foundation/stem wall material: Concrete block
11) Trees were in contact with or were close to the building at one or more locations. Damage to the building may occur, especially during high winds, or may have already occurred (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.
12) One or more large trees were very close to the foundation. Tree roots can cause significant structural damage to foundations, or may have already caused damage (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to foundations.
13) Many sections of siding and/or trim were peeling. Recommend that a qualified person repair, replace or install siding or trim as necessary.
overall house is in need of painting to prevent further deterioration.
14) Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
15) One or more holes or gaps were found in siding or trim. Vermin, insects or water may enter the structure. Recommend that a qualified person repair as necessary.
16) One or more minor cracks (1/8 inch or less) were found in the foundation. These didn't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitor them in the future. Numerous products exist to seal such cracks including hydraulic cement, non-shrinking grout, resilient caulks and epoxy sealants.
17) a section of exterior wall was has a significant bulge, unable to determine cause recommend a licensed contractor to evaluate and repair as necessary.
18) The paint or stain finish over much of the entire structure was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture. Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint or restain the entire building exterior per standard building practices. Any repairs needed to the siding or trim should be made prior to this.
19) Caulk was missing and/or deteriorated in some areas. For example, around windows, around doors and/or at wall penetrations. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit: https://www.reporthost.com/?CAULK
20) One or more sections of brick or stone veneer at exterior walls had no visible . Masonry veneers should be constructed as follows to prevent water penetration and accumulation in the wall structure:
Weep holes should be installed (typically every 24 inches max) at the bottom of the masonry to allow any accumulated water to drain out of the wall cavity.
Base flashing should be installed below the masonry veneer to prevent water from accumulating at the base of the wall cavity.
It is common that either or both of these components are not installed in masonry veneers, more so in older homes. However, without them water is likely to accumulate in wall cavities and cause mold, fungal rot and/or structural damage. The likelihood of this occurring depends on the installation configuration, such as how deep the roof overhangs are, how tall the exterior walls are, what the exposure is to prevailing weather, what the proximity to sprinkler systems is, etc. In most cases it's not practical to install these components retroactively, since all or significant sections of the masonry veneer would need to be dismantled. Note that the inspector is unable to determine if any damage has already occurred since these areas are inaccessible. The client should at least be aware of this potential for water intrusion, and monitor these walls inside and out for any signs of accumulated moisture in the future. If damage occurs, recommend that a qualified contractor repair as necessary. For more information, visit: https://www.reporthost.com/?MVCD
21) Some exterior wall sections were obscured by vegetation and couldn't be fully evaluated. They are excluded from this inspection.
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.
Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Steel
Beam material: Built-up wood
Floor structure above: Solid wood joists
Condition of insulation underneath floor above: Not applicable, none installed
22) Handrails at one or more flights of stairs were not graspable and posed a fall hazard. Handrails should be 1 1/4 - 2 inches in diameter if round, or 2 5/8 inches or less in width if flat. Recommend that a qualified person install graspable handrails or modify existing handrails per standard building practices.
23) Handrails at one or more flights of stairs were not continuous or did not extend the full length of the stairs. This is a potential fall hazard. Handrails should be continuous for the entire length of the stairs. Recommend that a qualified contractor replace or repair handrails per standard building practices.
24) Guardrails at one or more locations with drop-offs higher than 30 inches had gaps that were too large. This poses a safety hazard for children (e.g. falling, getting stuck in railing). Guardrails should not have gaps or voids that allow passage of a sphere equal to or greater than 4 inches in diameter, or 6 inches in diameter at triangular spaces between stair edges and guardrails. At a minimum, the client should be aware of this hazard. Recommend that a qualified contractor repair or replace guardrails per standard building practices.
25) One or more handrails had no returns installed, where ends of handrails turn and connect to adjacent walls so objects or clothing will not catch on the open ends. This is a safety hazard. Recommend that a qualified person install returns per standard building practices.
26) Handrails at one or more flights of stairs were loose and/or wobbly. This is a safety hazard. Recommend that a qualified person repair as necessary.
27) The only entrance/exit to the basement appeared to be the basement stairs. While this is common in older homes, modern standards require a secondary escape for use in the event of fire or an emergency. Such entrances/exits should allow entry by emergency personnel and their equipment. It is beyond the scope of this inspection to verify compliance with the current codes, and codes are generally not retroactive. Consult with a window/door contractor and/or the local municipal building officials regarding egress guidelines.
28) Glass in one or more windows was cracked, broken and/or missing. Recommend that a qualified contractor replace glass where necessary.
29) One or more windows that were designed to open and close were difficult to open and close. Recommend that a qualified person repair windows as necessary so they open and close easily.
recommend replacing all basement windows.
30) No under-floor insulation was installed in the unheated basement. Recommend that a qualified person install insulation for better energy efficiency and per standard building practices. Typically this is R-19 rated fiberglass batt with the attached facing installed against the warm (floor) side.
31) Minor cracks were found in the concrete slab floor. These are common and appeared to be only a cosmetic issue.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Age of roof surface(s): According to the home owner the roof is approximately 2 years old
Roof inspection method: Viewed from eaves on ladder
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of gutters, downspouts and extensions: Appeared serviceable
Gutter and downspout material: Metal
Gutter and downspout installation: Full
32) Extensions such as splash blocks or drain pipes for one or more downspouts were missing. Water can accumulate around the building foundation or inside crawl spaces or basements as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure.
33) Significant amounts of debris such as leaves, needles, seeds, etc. have accumulated on the roof surface. Water may not flow easily off the roof, and can enter gaps in the roof surface. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend cleaning debris from the roof surface now and as necessary in the future.
34) Vegetation such as trees, shrubs, and/or vines overhung the roof surface or were in contact with the roof edge. Organic debris such as leaves or needles are likely to accumulate in gutters and on the roof surface. Gutters can overflow and cause water to come in contact with the building exterior or water can accumulate around the foundation. This is a conducive condition for wood-destroying organisms. Vegetation in contact with the roof can damage the roof surface and/or the roof drainage system. Recommend pruning vegetation so as to not be in contact with the roof and to not overhang the roof surface. If vegetation is too tall then it should be pruned at least 10 feet above the roof surface.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch(es)
Location of attic access point #A: Hall closet
Attic access points that were opened and viewed, traversed or partially traversed: A
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass roll or batt
Approximate attic insulation R value (may vary in areas): Not determined (inaccessible or obscured)
Vapor retarder: Not determined (inaccessible or obscured)
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Gable end vents
35) The attic access hatch, door or stairs was located or configured so that it posed a safety hazard for falling when attempting to enter the attic. Recommend that a qualified contractor relocate or reconfigure the access per standard building practices to eliminate this hazard.
36) One or more indoor attic access hatch covers or doors were missing, damaged and/or substandard. When located indoors, conditioned air can enter the attic. Energy efficiency can be reduced, moisture can form in the attic, attic air laden with insulation fibers can enter living spaces, and/or pets can enter the attic . This is also a fire hazard as attic access hatch covers and doors are meant to stop or slow the spread of fire into the attic. A qualified person should replace, install or repair hatches or doors as necessary and per standard building practices. Each access point should be insulated and sealed with weatherstripping. For more information, visit: https://www.reporthost.com/?ATTACC
37) One or more gable end vents were damaged or significantly deteriorated. This can result in bird, vermin and/or water intrusion. Recommend that a qualified person repair or replace gable end vents as necessary.
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of door between garage and house: Required repair, replacement and/or evaluation (see comments below), recommend replacing door between house and garage with an updated fire door.
Type of door between garage and house: Wood
Condition of exterior entry doors: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Exterior door material: Wood
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Condition of automatic opener(s): Appeared serviceable
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
Condition of garage floor: Appeared serviceable, recommend a licensed contractor to further evaluate the floor for settling.
Condition of garage interior: Appeared serviceable
Garage ventilation: None visible
38) The door between the garage and the house did not appear to be fire resistant, or the inspector was unable to verify that it was via a label. This is a potential safety hazard. House to garage doors, to prevent fire and fumes from spreading from the garage into interior living space, should be constructed of fire-resistant materials. Doors, generally considered to be suitable for the purpose, are solid core wood, steel, honeycomb steel or a door that has been factory labeled as fire rated. Recommend that a qualified contractor replace or repair the door and, at that time, make any other corrections that might be required to provide suitable fire resistance between the garage and the dwelling per standard building practices. For more information, visit: https://www.reporthost.com/?AGFR
39) The door between the house and the garage wouldn't latch when closed. This is meant to be a fire-resistant door for safety reasons, and should latch when closed. Recommend that a qualified person repair as necessary.
40) Weatherstripping around or at the base of the door between the garage and the house was substandard. House to garage doors should prevent fire and fumes from spreading from the garage to the house. Weatherstripping should form a seal around this door. This is a potential safety hazard. Recommend that a qualified person replace or install weatherstripping as necessary.
41) One or more exterior doors were difficult to latch. Recommend that a qualified person repair as necessary.
42) Weatherstripping around one or more exterior doors was deteriorated. Water may enter the building, or energy efficiency may be reduced. Recommend that a qualified person repair or replace weatherstripping as necessary.
43) Some floor areas were obscured by vehicles and couldn't be fully evaluated.
44) One or more exterior doors had minor damage and/or deterioration. Although serviceable, the client may wish to repair or replace such doors for appearances' sake.
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 100
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Not determined (components inaccessible or obscured)
Main disconnect rating (amps): 100
System ground: Cold water supply pipes
Condition of main service panel: Not determined (inaccessible or obscured, or panel not opened), unable to open panel due to rusted screws
Location of main service panel #A: Basement
Location of main disconnect: Breaker at top of main service panel
Smoke alarms installed: No, recommend install
Carbon monoxide alarms installed: Yes, but not tested
45) One or more clamps that secure the electric service's grounding electrode conductor(s) to a water pipe were corroded. Grounding may be substandard as a result and may be a safety hazard for shock. Recommend that a qualified electrician repair as necessary. For example, by tightening clamps.
46) One or more electric receptacles at the kitchen, bathroom(s), master bath and/or laundry area had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
Outdoors (since 1973)
Bathrooms (since 1975)
Garages (since 1978)
Kitchens (since 1987)
Crawl spaces and unfinished basements (since 1990)
47) The service drop wires had no drip loop where they attached to the service mast, or the drip loop was substandard. This can result in water entering electric panels, and is a potential shock hazard. Recommend that a qualified electrician repair per standard building practices.
48) Panel(s) #A were Pushmatic brand panels. These panels are found in older electrical systems. Their circuit breakers are known to become very stiff and difficult to operate or reset over time. Breakers may remain on after attempts to trip or turn them off have been made. They also have an indicator flag that falsely indicates the on/off/tripped state. The breakers rely on thermal tripping only, whereas modern breakers have both thermal and magnetic trip mechanisms. These conditions pose shock and fire hazards. Replacement circuit breakers and spare parts are usually difficult to find, and are expensive. Recommend that a qualified electrician replace Pushmatic brand panels with modern panels that offer more flexibility for new, safer protective technologies like ground fault circuit interrupters (GFCls) and arc fault circuit interrupters (AFCls).
49) One or more receptacles were broken or damaged. This is a potential shock or fire hazard. Recommend that a qualified electrician replace such receptacles as necessary.
50) No electric receptacle was found in one or more bathrooms. This is an inconvenience and a potential safety hazard since extension cords from other locations may be used. Recommend that a qualified electrician install ground fault circuit interrupter (GFCI) protected receptacle(s) in bathrooms as necessary and per standard building practices.
51) Light fixtures with fully or partially exposed incandescent bulbs were installed in one or more closets. This is a fire hazard. Flammable stored items can come into contact with hot bulbs, or hot fragments from broken bulbs can fall on combustible materials. Closet lighting should use fluorescent light fixtures or fully enclosed incandescent fixtures. Installing a compact fluorescent lamp in a lamp holder is not an acceptable practice. If globes or covers are missing, they should be replaced. Otherwise recommend that a qualified electrician replace closet lights per standard building practices.
52) No permanently installed smoke alarms were found. This is a potential safety hazard. A qualified electrician should install smoke alarms per standard building practices (e.g. in hallways leading to bedrooms, in each bedroom, on each floor and in attached garages). For more information, visit: https://www.reporthost.com/?SMKALRM
53) Smoke alarms were missing from one or more bedrooms. Smoke alarms should be installed as necessary so a functioning alarm exists in each hallway leading to bedrooms, in each bedroom and on each level. For more information, visit: https://www.reporthost.com/?SMKALRM
54) One or more wall-mounted exterior light fixtures had no caulk installed above the back plate. Water can enter the space behind the back plate and contact wiring. This is a potential shock hazard. Recommend that a qualified person apply caulk above and around the back plate per standard building practices. A gap should be left at the bottom of the plate so that condensation can drain out.
55) The inspector was unable to open and evaluate panel(s) #A because . The condition of these panel(s) is unknown and they are excluded from this inspection. Repairs may be needed. Recommend that a qualified person correct conditions, or that a qualified contractor make repairs if necessary so panels can be opened, and that a qualified person fully evaluate panel(s).
unable to open panel due to rusted screws
56) One or more receptacles have been painted, and slots were clogged with paint. Recommend that a qualified electrician replace such receptacles as necessary.
57) One or more globes or covers for light fixtures were missing or damaged. Recommend replacing as necessary to avoid exposed bulbs. With closet lighting or where flammable stored objects are near light fixtures, missing or broken covers can be a fire hazard.
58) The legend for circuit breakers or fuses in panel(s) #A was missing, incomplete, illegible or confusing. This is a potential shock or fire hazard in the event of an emergency when power needs to be turned off. Recommend correcting the legend so it's accurate, complete and legible. Evaluation by a qualified electrician may be necessary.
59) The electric service to this property appeared to be rated at substantially less than 200 amps and may be inadequate. Depending on the client's needs, recommend consulting with a qualified electrician about upgrading to a 200 amp service. Note that the electric service's rating is based on the lowest rating for the meter base, the service conductors, the main service panel and the main disconnect switch. One or more of these components may need replacing to upgrade.
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Location of main water meter: basement
Location of main water shut-off: Basement
Service pipe material: Copper
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Copper
Condition of waste lines: Appeared serviceable
Waste pipe material: Cast iron
Location(s) of plumbing clean-outs: Basement
Vent pipe condition: Appeared serviceable
Vent pipe material: Not determined (inaccessible or obscured)
Sump pump installed: Yes
Condition of sump pump: Appeared serviceable
Location of main fuel shut-off valve: At gas meter
60) Copper water supply pipes were installed. Copper pipes installed prior to the late 1980s may be joined with solder that contains lead, which is a known health hazard especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained approximately 50% lead. The client should be aware of this, especially if children will be using this water supply system. Note that the inspector does not test for toxic materials such as lead. The client should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions include:
Flush water taps or faucets. Do not drink water that has been sitting in the plumbing lines for more than 6 hours
Install appropriate filters at points of use
Use only cold water for cooking and drinking, as hot water dissolves lead more quickly than cold water
Use bottled or distilled water
Treat well water to make it less corrosive
Have a qualified plumber replace supply pipes and/or plumbing components as necessary
61) One or more hose bibs appeared to be inoperable. No water flowed from the bib(s) when turned on. This may be due to a shut-off valve being turned off. Note that the inspector does not operate shut-off valves. Recommend consulting with the property owner about inoperable hose bibs, and if necessary have a qualified plumber make repairs.
62) One or more hose bibs were not the "frost-free" design, and are more likely to freeze during cold weather than frost-free hose bibs. Recommend that a qualified plumber upgrade these with frost-free hose bibs to prevent freezing, pipes bursting, flooding and possible water damage.
63) The sump pump discharge pipe was routed so that it drained close to the foundation. Prolonged, high levels of moisture in soil can cause foundation settlement and failure. If drainage is near a crawl space or basement, water can accumulate in these spaces. Recommend that a qualified contractor repair as necessary so the discharge pipe terminates well away from the foundation and to soil that is sloping down and away from the foundation.
64) Steel piping for the gas service located outside was significantly corroded. Gas leaks can result. Recommend evaluation by a qualified contractor to determine if piping needs replacing. If not, then a qualified person should prep and paint lines as necessary with a rust-preventative paint. Very corroded pipes should be replaced by a qualified contractor.
65) A sump pump was installed in the basement. These are specialty systems and only a limited evaluation was performed as part of this inspection. The inspector does not determine the adequacy of sump pumps and their associated drainage systems. The presence of a sump pump may indicate that water routinely accumulates below or inside the structure. Recommend asking the property owner how often the sump pump operates and for how long at different times of the year. The client should be aware that the service life of most sump pumps is 5-7 years, and that the pump may need replacing soon depending on its age and how often it operates.
66) No battery backup system was found for the sump pump. If the power goes out during heavy rains, the sump pump won't be able to eliminate accumulated water. Consider installing a battery backup system for the sump pump.
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Near, at or beyond service life
Type: Tank
Energy source: Natural gas
Estimated age: 14 years
Capacity (in gallons): 40
Temperature-pressure relief valve installed: Yes
Manufacturer: Bradford White
Model number: MI4OT6FBN
Serial number: EK11199952
Location of water heater: Basement
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 114
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable
67) The estimated useful life for most water heaters is 8-12 years. This water heater appeared to be beyond this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Furnace
General heating distribution type(s): Pipes and convectors
Condition of hydronic or steam heat system: Appeared serviceable
Type of hydronic or steam heat: Circulating pump
Hydronic or steam heat fuel type: Natural gas
Boiler model #: TAWI128SNST1PSU
Boiler serial number: TOPMNT000414842
Condition of burners: Appeared serviceable
Type of combustion air supply: No dedicated source visible, uses room air
68) No drain line was installed for the boiler's temperature-pressure relief valve. This is a potential safety hazard due to the risk of scalding if someone is standing next to the boiler when the valve opens. Recommend that a qualified heating contractor or plumber install a drain line per standard building practices.
69) The furnace burner flame was not blue in color. Various conditions can cause incorrect flames (not blue, noisy, floating) including incorrect drafting, dirty burner orifices and improper gas pressure. Recommend that a qualified heating contractor evaluate and repair as necessary.
70) The estimated useful life for most steel boilers is 20 years. This boiler appeared to be near this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Appeared serviceable
Wood-burning fireplace type: Masonry
Fan or blower installed in wood-burning fireplace or stove: No
Condition of chimneys and flues: Appeared serviceable
Wood-burning chimney type: Masonry
71) One or more solid fuel-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all solid fuel-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at: https://www.reporthost.com/?CSIA
72) The brick chimney was moderately deteriorated. For example, loose or missing mortar, cracked, broken, loose or spalled bricks. Loose bricks can pose a safety hazard, and deteriorated masonry can allow water to infiltrate the chimney structure and cause further damage. Recommend that a qualified contractor repair as necessary.
73) One or more masonry chimney crowns were cracked. Crowns are meant to keep water off of the chimney structure and prevent damage from freeze-thaw cycles. Chimney crowns are commonly constructed by mounding concrete or mortar on the top chimney surface, however this is substandard. A properly constructed chimney crown should:
Be constructed using either precast concrete slabs, cast-in-place steel reinforced concrete, solid stone, or metal
Be sloped down from the flue a minimum of 3 inches of fall per foot of run
Extend a minimum of 2 1/2 inches beyond the face of the chimney on all sides
Not directly contact the flue liner (if installed), with the gap filled with flexible caulk
Have flashing installed between the bottom of the crown and the top of the brick chimney
Recommend that a qualified contractor repair or replace crowns as necessary, and per standard building practices.
74) Mortar at the brick chimney was deteriorated (e.g. loose, missing, cracked). As a result, water is likely to infiltrate the chimney structure and cause further damage. Recommend that a qualified contractor repair as necessary. For example, by repointing the mortar.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of cabinets: Required repair, replacement and/or evaluation (see comments below)
Condition of sinks and related plumbing: Appeared serviceable
Condition of dishwasher: Not determined
Condition of ranges, cooktops and/or ovens: Not determined
Range, cooktop, oven type: Natural gas
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Not determined
Condition of built-in microwave oven: Not determined
Condition of hot water dispenser: N/A (none installed)
Condition of trash compactor: N/A (none installed)
75) One or more cabinets, drawers and/or cabinet doors were loose. Recommend that a qualified person repair or replace as necessary.
76) The estimated useful life for most kitchen appliances is 10-15 years. One or more appliances (range, cooktop, microwave and/or range hood) appeared to be near, at or beyond their service life. Even if operable, recommend budgeting for replacements in the near future.
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Half bath, Laundry room/area, first floor
Location #B: Full bath, second floor
Location #C: Master bath
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of shower(s) and related plumbing: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of ventilation systems: Not determined (power off, etc.)
Bathroom and laundry ventilation type: Windows
Gas supply for laundry equipment present: Not determined
240 volt receptacle for laundry equipment present: Not determined
77) The clothes dryer was equipped with a vinyl or mylar, accordion-type, flexible exhaust duct. The U.S. Consumer Product Safety Commission considers these types of ducts to be unsafe, and a fire hazard. They can trap lint and are susceptible to kinks or crushing, which can greatly reduce the air flow and cause overheating. Recommend that such ducts be replaced with a rigid or corrugated semi-rigid metal duct, and by a qualified contractor if necessary. For more information, visit: https://www.reporthost.com/?DRYER
78) The shower door at location(s) #B was difficult to open or close. Recommend that a qualified person repair as necessary.
79) The shower head at location(s) # was LOOSE. Recommend that a qualified person repair as necessary.
80) The bathroom with a shower or bathtub at location(s) #B and C didn't have an exhaust fan installed. Moisture can accumulate and result in mold, bacteria or fungal growth. Even if the bathroom has a window that opens, it may not provide adequate ventilation, especially during cold weather when windows are closed or when wind blows air into the bathroom. Recommend that a qualified contractor install exhaust fans per standard building practices where missing in bathrooms with showers or bathtubs.
81) The laundry room didn't have an exhaust fan installed. Moisture can accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified contractor install an exhaust fan per standard building practices.
82) Water was leaking at the sink faucet base or handles at location(s) #B. Recommend that a qualified plumber repair as necessary.
83) The bathtub drain stopper mechanism at location(s) #B was inoperable. Recommend that a qualified person repair or replace as necessary.
84) The clothes dryer exhaust duct was DIRTY in one or more places. Clothes dryers produce large amounts of moisture which should not enter structure interiors. Moisture can accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified person make permanent repairs as necessary. For more information, visit: https://www.reporthost.com/?DRYER
85) Recommend cleaning and sealing the grout in flooring at location(s) #A, B and C now and in the future as necessary to prevent staining and to improve waterproofing.
86) The sink at location(s) #B was worn, blemished or deteriorated.
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood
Condition of interior doors: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of windows and skylights: Required repair, replacement and/or evaluation (see comments below)
Type(s) of windows: Multi-pane, Double-hung
Condition of walls and ceilings: Appeared serviceable, Required repairs, replacement and/or evaluation (see comments below)
Wall type or covering: Drywall, Plaster
Ceiling type or covering: Drywall, Drywall or plaster
Condition of flooring: Appeared serviceable
Condition of concrete slab floor(s): Appeared serviceable
Flooring type or covering: Carpet, Wood or wood products
87) One or more exterior doors were difficult to latch. Recommend that a qualified person repair as necessary.
88) One or more interior doors were missing. Recommend that a qualified person replace or repair doors as necessary.
89) One or more windows that were designed to open and close were difficult to open and close. Recommend that a qualified person repair windows as necessary so they open and close easily.
90) One or more interior doors were sticking in the door jamb and were difficult to operate. Recommend that a qualified person repair as necessary. For example, by trimming doors.
91) Minor cracks, nail pops and/or blemishes were found in walls and/or ceilings in one or more areas. Cracks and nail pops are common, are often caused by lumber shrinkage or minor settlement, and can be more or less noticeable depending on changes in humidity. They did not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons. For recurring cracks, consider using an elastic crack covering product: https://www.reporthost.com/?ECC
92) The glazing compound or caulk that holds glass panes in one or more windows was deteriorated and/or substandard. Air and/or water can leak through windows, and wood window frames are prone to rot. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person replace glazing compound as necessary. For more information, visit: https://www.reporthost.com/?PUTTY
Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: No
Visible evidence of past wood-destroying insects: No
Visible evidence of damage by wood-destroying insects: No