Anthony Ottombrino

356 Tysens Ln 
Staten Island NY 10306-2843
Inspector: Anthony Ottombrino

Dun Rite Home Inspection LLC

Client(s):  R. Rodriguez
Property address:  1031 East 226 street Bronx
Inspection date:  Wednesday, April 20, 2022

This report published on Friday, April 22, 2022 7:03:07 PM EDT

Thank you for selecting Dun Rite Home Inspection. We understand that a real estate purchase may be the largest expense of anyone’s life, that is why we strived to give you a comprehensive inspection report, making every reasonable effort to disclose the conditions of the property on the day of the inspection. The inspection report however will not reveal information on concealed items or items that inspector was unable to inspect on the day of inspection. We understand that the information provided to you in this report will assist you in understanding the condition of the property and assist you in making an informed purchase decision.

This inspection complies with the rules and regulations that govern the New York State Standards of Practice (Title 19 NYCRR, Part 197-5), as well as American Society of Home Inspectors’ (ASHI) Standards of Practice and the International Association of Certified Home Inspectors’ (InterNACHI) Standards of Practice.

The Home Inspection Report contains a review of the components in the following basic categories; General Information, Grounds, Exterior and Foundation, Basements/Crawl Space, Roofing, Attic and Roof Structure, Garage / Carport, Electrical, Plumbing / Fuel System, Water Heater, Heating/Ventilation/ Air-Conditioning (HVAC), Fireplaces, Kitchens, Bathrooms, Interior and Wood Destroying Organisms. Additional categories may or may not be included. This report is intended to provide you with an explanation of material defects observed on the date and time of the inspection. It does not guarantee that there may be latent defects that cannot be observed at the time and date of this inspection report due to obstructions, weather, covering, etc.

This Home Inspection Report is the exclusive property of Dun Rite Home Inspection and the client(s) listed in the report title, use of this report by any unauthorized person(s) is prohibited.

The inspection was conducted in the safest manner possible, adhering to safe practices, social distancing and preventing the spread of the covid-19 virus. At the time of inspection, the inspector was 100% vaccinated and did not have any of the symptoms associated with the Covid-19 virus. In addition the inspector has not engaged in travels outside the United States of America in the preceding three (3) months.

Dun Rite Home Inspection
Anthony Ottombrino
(917) 751-6405

New York State Home Inspection License # 16000134656 N.Y.S. DEC Categories/Subcategories of Certification 7c (Termite # T2904245)

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Basement
Roof
Garage or Carport
Electric
Plumbing / Fuel Systems
Heating, Ventilation and Air Condition (HVAC)
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings

View summary

General Information
Table of contents
Time started: 3:30 pm
Time finished: 5:30pm
Present during inspection: Client, Property owner, Realtor
Client present for discussion at end of inspection: Yes
Inspector: Anthony Ottombrino
Weather conditions during inspection: Dry (no rain), Sunny
Temperature during inspection: Cool
Ground condition: Dry
Recent weather: Rain
Overnight temperature: Cold
Inspection fee: $625.00
Payment method: Cash
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: 72 years
Source for main building age: Property owner
Front of building faces: South
Main entrance faces: South
Occupied: Yes
1) Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
https://www.reporthost.com/?EPA
https://www.reporthost.com/?CPSC
https://www.reporthost.com/?CDC
2) Many areas and items at this property were obscured by furniture and/or stored items. This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.
Photo
Photo 2-1 
Photo
Photo 2-2 
Photo
Photo 2-3 
Photo
Photo 2-4 
Photo
Photo 2-5 
Photo
Photo 2-6 
Photo
Photo 2-7 
Photo
Photo 2-8 
Photo
Photo 2-9 
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Condition of fences and gates: Appeared serviceable
Fence and gate material: Wrought iron
Condition of retaining walls: Appeared serviceable
Retaining wall material: Concrete
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Concrete
Condition of stairs, handrails and guardrails: Appeared serviceable
Exterior stair material: Concrete
3) Masonry steps have settled significantly, or significant cracks or deterioration were found. Recommend that a qualified contractor repair or replace steps as necessary.
Photo
Photo 3-1 
4) Cracks, holes, settlement, heaving and/or deterioration were found in the driveway. Recommend that qualified contractor repair as necessary.
Photo
Photo 4-1 
5) The driveway sloped down towards the garage or house. This may result in water accumulating in the garage, around building foundations or underneath buildings, and is a conducive condition for wood-destroying organisms. Monitor these areas in the future, especially during and after periods of rain. If significant amounts of water are found to accumulate, then recommend that a qualified contractor evaluate and repair as necessary. For example, by installing drain(s) or removing and installing new pavement.
Photo
Photo 5-1 
6) The condition of the drain(s) at the base(s) of stairs is unknown. It's beyond the scope of a home inspection to determine if these drains flow adequately during prolonged periods of heavy rain. Recommend consulting with the property owners about this if possible, and monitoring drains in the future. If water is found to accumulate, then recommend that a qualified contractor evaluate and repair as necessary. For example, by cleaning, repairing or installing drains.
Photo
Photo 6-1 
Photo
Photo 6-2 
Exterior and Foundation
Table of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Brick
Wall covering: Vinyl
Condition of foundation and footings: Not determined
Apparent foundation type: Finished basement
Foundation/stem wall material: Poured in place concrete
7) Caulk was deteriorated and/or substandard in some areas. For example, around doors and/or at wall penetrations. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit:
https://www.reporthost.com/?CAULK
Photo
Photo 7-1 
Photo
Photo 7-2 
Photo
Photo 7-3 
Photo
Photo 7-4 
Photo
Photo 7-5 
8) Some above-grade foundation walls were obscured by COVERED WITH VINYL SIDING. The inspector was unable to evaluate these areas. They are excluded from this inspection.
Photo
Photo 8-1 
9) The parging (decorative coating) on one or more foundation walls was damaged or deteriorated. This is not a structural concern, but the client may want this repaired for appearance's sake.
Photo
Photo 9-1 
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood, Metal, Fiberglass or vinyl
Condition of floor substructure above: Not determined (inaccessible or obscured)
Pier or support post material: Not determined (inaccessible or obscured)
Beam material: Not determined (inaccessible or obscured)
Floor structure above: Not determined (inaccessible or obscured)
Condition of insulation underneath floor above: Not determined (inaccessible or obscured)
Insulation material underneath floor above: Not determined (inaccessible or obscured)
10) Guardrails at one or more locations with drop-offs higher than 30 inches had gaps that were too large. This poses a safety hazard for children (e.g. falling, getting stuck in railing). Guardrails should not have gaps or voids that allow passage of a sphere equal to or greater than 4 inches in diameter, or 6 inches in diameter at triangular spaces between stair edges and guardrails. At a minimum, the client should be aware of this hazard. Recommend that a qualified contractor repair or replace guardrails per standard building practices.
Photo
Photo 10-1 
11) One or more handrails had no returns installed, where ends of handrails turn and connect to adjacent walls so objects or clothing will not catch on the open ends. This is a safety hazard. Recommend that a qualified person install returns per standard building practices.
Photo
Photo 11-1 
12) Fungal rot was found at one or more exterior door jambs. Recommend that a qualified person repair as necessary. All rotten wood should be replaced.
Photo
Photo 12-1 
Photo
Photo 12-2 
13) Weatherstripping around one or more exterior doors was damaged and/or deteriorated. Water may enter the building, or energy efficiency may be reduced. Recommend that a qualified person repair or replace weatherstripping as necessary.
Photo
Photo 13-1 replace weather striping
Photo
Photo 13-2 
Photo
Photo 13-3 screen door missing safety chain.
14) Many areas were not evaluated due to lack of access from stored items. These areas are excluded from the inspection.
Photo
Photo 14-1 
Photo
Photo 14-2 
Photo
Photo 14-3 
15) One or more exterior doors had minor damage and/or deterioration. Although serviceable, the client may wish to repair or replace such doors for appearances' sake.
Photo
Photo 15-1 missing dead bolt lock
Photo
Photo 15-2 brocken locking mechanism.
Photo
Photo 15-3 
Photo
Photo 15-4 
Photo
Photo 15-5 base of door is rooted
Photo
Photo 15-6 replace weather striping
Photo
Photo 15-7 screen door missing safety chain.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Age of roof surface(s): Home owner claims the roof is 10 years old.
Roof inspection method: Traversed
Condition of roof surface material: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Roof surface material: Rolled composition
Roof type: Flat or low slope
Apparent number of layers of roof surface material: Not determined (inaccessible or obscured)
Condition of gutters, downspouts and extensions: Appeared serviceable, Limited evaluation due to little or no rainfall during and prior to the inspection
Gutter and downspout material: Metal
Gutter and downspout installation: Full
16) Substandard repairs were found at one or more locations on the roof surface. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor evaluate and repair per standard building practices.
Photo
Photo 16-1 
Photo
Photo 16-2 
Photo
Photo 16-3 
Photo
Photo 16-4 
Photo
Photo 16-5 
Photo
Photo 16-6 
Photo
Photo 16-7 
17) Blisters were found in the flat or low-slope roof surface. Blisters can be caused by improper heating of asphalt, bad adhesion between plys, dry laps, and/or improper torching depending on what materials and methods of installation were used. Moisture and air trapped between layers can vaporize due to heat from the sun and result in blisters. It may not be necessary to repair all blisters, but in some cases, such as when blisters are large or near seams, repair may be needed. Recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 17-1 
18) Sealant was used at one or more roof penetrations (e.g. pipes, vents, chimneys) rather than flashing. Sealant is not required for most roof penetrations when installations of such items are done professionally and per standard building practices. The presence of sealant suggests that work was performed by someone who was not a qualified contractor. The sealant will be a maintenance issue in the future since it must be renewed periodically. Recommend that a qualified contractor repair where necessary and per standard building practices. For example, by removing sealant and installing flashing.
Photo
Photo 18-1 
19) One or more flashings at parapet walls were substandard. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.
Photo
Photo 19-1 
Photo
Photo 19-2 
Garage or Carport
Table of contents
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Condition of garage floor: Unable to evaluate due to stored items
Condition of garage interior: Appeared serviceable
Garage ventilation: None
20) Many floor areas were obscured by stored items and couldn't be fully evaluated.
Photo
Photo 20-1 
Photo
Photo 20-2 
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 100
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded copper
Main disconnect rating (amps): 100
System ground: Cold water supply pipes
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Basement
Location of main disconnect: Breaker at top of main service panel
Branch circuit wiring type: armor clad (AC), metal clad (MC) or flexible metal conduit (FMC)
Ground fault circuit interrupter (GFCI) protection present: No
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: No, recommend install
Carbon monoxide alarms installed: No, recommend install
21) One or more clamps that secure the electric service's grounding electrode conductor(s) to a were . Grounding may be substandard as a result and may be a safety hazard for shock. Recommend that a qualified electrician repair as necessary. For example, by tightening clamps.
Photo
Photo 21-1 
22) One or more electric receptacles at the kitchen had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
For more information, visit:
https://www.reporthost.com/?GFCI
23) Electrical Panel(s) # had inadequate working space. This is a safety hazard when opening or working in panels. Electric panels should have the following clearances:
  • An open area 30 inches wide by 3 feet deep in front of the panel
  • 6 feet 6 inches of headroom in front of the panel
  • The wall below the panel is clear to the floor
  • The center of the grip of the operating handle of the switch or circuit breaker not more than 6 feet 7 inches above the floor or working platform
Recommend that a qualified contractor repair or make modifications per standard building practices. If panels must be opened for repairs, then a qualified electrician should perform repairs.
24) No electric receptacle was found in one or more bathrooms. This is an inconvenience and a potential safety hazard since extension cords from other locations may be used. Recommend that a qualified electrician install ground fault circuit interrupter (GFCI) protected receptacle(s) in bathrooms as necessary and per standard building practices.
Photo
Photo 24-1 
Photo
Photo 24-2 
Photo
Photo 24-3 
25) One or more electric receptacles had reverse-polarity wiring, where the hot and neutral wires were reversed. This is a shock hazard. Recommend that a qualified electrician repair as necessary. For more information, visit:
https://www.reporthost.com/?RPR
Photo
Photo 25-1 
26) Smoke alarms were missing from one or more bedrooms. Smoke alarms should be installed as necessary so a functioning alarm exists in each hallway leading to bedrooms, in each bedroom and on each level. For more information, visit:
https://www.reporthost.com/?SMKALRM
27) One or more cover plates for switches, receptacles or junction boxes were missing or broken. These plates are intended to contain fire and prevent electric shock from occurring due to exposed wires. Recommend that a qualified person install cover plates where necessary.
Photo
Photo 27-1 
Photo
Photo 27-2 
28) No permanently installed carbon monoxide alarms were found. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed for new construction and/or for homes being sold. Recommend installing approved CO alarms outside of each separate sleeping area in the immediate vicinity of the bedrooms on each level and in accordance with the manufacturer's recommendations. For more information, visit:
https://www.reporthost.com/?COALRM
29) One or more globes or covers for light fixtures were missing or damaged. Recommend replacing as necessary to avoid exposed bulbs. With closet lighting or where flammable stored objects are near light fixtures, missing or broken covers can be a fire hazard.
Photo
Photo 29-1 
Photo
Photo 29-2 
Photo
Photo 29-3 
30) The legend for circuit breakers or fuses in panel(s) #A was missing, incomplete, illegible or confusing. This is a potential shock or fire hazard in the event of an emergency when power needs to be turned off. Recommend correcting the legend so it's accurate, complete and legible. Evaluation by a qualified electrician may be necessary.
Photo
Photo 30-1 
31) The electric service to this property appeared to be rated at substantially less than 200 amps and may be inadequate. Depending on the client's needs, recommend consulting with a qualified electrician about upgrading to a 200 amp service. Note that the electric service's rating is based on the lowest rating for the meter base, the service conductors, the main service panel and the main disconnect switch. One or more of these components may need replacing to upgrade.
Plumbing / Fuel Systems
Table of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Location of main water meter: Basement
Location of main water shut-off: Basement
Service pipe material: Copper
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Copper
Condition of waste lines: Appeared serviceable
Waste pipe material: Cast iron
Location(s) of plumbing clean-outs: Basement
Vent pipe condition: Appeared serviceable
Vent pipe material: Galvanized steel
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: Above ground, oil tank, in basement
Location of main fuel shut-off valve: At oil tank
Location of main fuel shut-off valve: At gas meter
32) One or more hose bibs were missing backflow prevention devices. These devices reduce the likelihood of gray water entering the potable water supply. Recommend installing backflow prevention devices on all hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit:
https://www.reporthost.com/?BKFLOW
Photo
Photo 32-1 
33) Copper water supply pipes were installed. Copper pipes installed prior to the late 1980s may be joined with solder that contains lead, which is a known health hazard especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained approximately 50% lead. The client should be aware of this, especially if children will be using this water supply system. Note that the inspector does not test for toxic materials such as lead. The client should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions include:
  • Flush water taps or faucets. Do not drink water that has been sitting in the plumbing lines for more than 6 hours
  • Install appropriate filters at points of use
  • Use only cold water for cooking and drinking, as hot water dissolves lead more quickly than cold water
  • Use bottled or distilled water
  • Treat well water to make it less corrosive
  • Have a qualified plumber replace supply pipes and/or plumbing components as necessary
For more information visit:
https://www.reporthost.com/?LEADDW
https://www.reporthost.com/?LEAD
34) One or more hose bibs appeared to be inoperable. No water flowed from the bib(s) when turned on. This may be due to a shut-off valve being turned off. Note that the inspector does not operate shut-off valves. Recommend consulting with the property owner about inoperable hose bibs, and if necessary have a qualified plumber make repairs.
Photo
Photo 34-1 
35) One or more waste pipes or fittings were loose. Recommend that a qualified plumber evaluate and repair as necessary and per standard building practices.

the waste line clean out cap was not installed properly allowing possible water and sewer gasses to enter the home recommend a licensed plumber evaluate and repair .
Photo
Photo 35-1 
36) One or more hose bibs were not the "frost-free" design, and are more likely to freeze during cold weather than frost-free hose bibs. Recommend that a qualified plumber upgrade these with frost-free hose bibs to prevent freezing, pipes bursting, flooding and possible water damage.
37) Recommend buying oil storage tank replacement insurance available from many full-service oil providers. This can cover up to 100% of the replacement costs of a tank and usually costs less than a few dollars per month.

Also recommend buying pollution liability insurance for oil spills, if available. Some states provide this for free (Washington state), and it may be available from other sources. For more information, visit:
https://www.reporthost.com/?OILSPILL
https://www.reporthost.com/?OILTANKINS
Heating, Ventilation and Air Condition (HVAC)
Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Boiler
General heating distribution type(s): Pipes and radiators
Last service date of primary heat source: no service log found
Condition of hydronic or steam heat system: Appeared serviceable
Type of hydronic or steam heat: Hydronic (hot water), Radiators
Hydronic or steam heat fuel type: Oil
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable
Type of combustion air supply: No dedicated source visible, uses room air
38) The water level gauge indicated that the water level in the steam boiler was too high (flooded). Normally, a steam boiler should be approximately half full of water. A flooded boiler typically requires water be drained from the system. Recommend that a qualified heating contractor evaluate and repair as necessary.
Photo
Photo 38-1 
39) The estimated useful life for most steel boilers is 20 years. This boiler appeared to be beyond this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.

home owner claims the heating system is of 50 years old recommend further evaluation by a licensed plumber.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Permanently installed kitchen appliances present during inspection: Range, Refrigerator
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of dishwasher: N/A (none installed)
Condition of ranges, cooktops and/or ovens: Appeared serviceable, WHIRLPOOL MOD# MGR8800F21 SER# RX4011014 Manufactured about 1990
Range, cooktop, oven type: Natural gas
Type of ventilation: Down draft exhaust
Condition of refrigerator: Appeared serviceable
40) The countertops, areas below sink(s) and/or range or cooktop surface were obscured by stored items or dishes and couldn't be fully evaluated.
Photo
Photo 40-1 
Photo
Photo 40-2 
41) The estimated useful life for most kitchen appliances is 10-15 years. One or more appliances (oven) appeared to be near, at or beyond their service life. Even if operable, recommend budgeting for replacements in the near future.
42)  observed a repair on the celing above the stove the home owner informed the above plumbing had burst and they had made repairs.
Photo
Photo 42-1 
Bathrooms, Laundry and Sinks
Table of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: 3/4 bath, basement
Location #B: Half bath, first floor
Location #C: Full bath, second floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of shower(s) and related plumbing: Appeared serviceable
43) One or more cabinets, drawers and/or cabinet doors at location(s) #C were damaged. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 43-1 
44) One or more bathtub faucet handles at location(s) #C were leaking. Recommend that a qualified person repair or replace handles as necessary.
Photo
Photo 44-1 
45) One or more handles controlling water flow to the shower at location(s) #A were loose. Recommend that a qualified person repair or replace handles as necessary.
Photo
Photo 45-1 
46) The exhaust fan at location(s) A was . Moisture may accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified person clean, repair or replace fans as necessary.
47) Gaps, no caulk, or substandard caulking were found between the bathtub and the walls at location(s) #C. Water may penetrate these areas and cause damage. Recommend that a qualified person re-caulk or install caulking as necessary.
Photo
Photo 47-1 
48) The bathtub drain stopper mechanism at location(s) #C was difficult to operate. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 48-1 
49) Recommend cleaning and sealing the grout in flooring at location(s) #A, B and C now and in the future as necessary to prevent staining and to improve waterproofing.
50) The exhaust fan or fan cover at location(s) #A needed cleaning. Dirty or clogged fans can result in moisture accumulation and subsequent mold, bacteria or fungal growth. Recommend cleaning fan covers or fans now and as necessary in the future.
Photo
Photo 50-1 
51) The sink at location(s) #C was worn, blemished or deteriorated.
Photo
Photo 51-1 
Interior, Doors and Windows
Table of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Exterior door material: Wood, Fiberglass or vinyl
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Type(s) of windows: Vinyl, Double-hung
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Flooring type or covering: Carpet, Tile
Condition of stairs, handrails and guardrails: Appeared serviceable
52) One or more exterior doors were difficult to open or close. Recommend that a qualified person repair as necessary.
Photo
Photo 52-1 brocken locking mechanism.
53) Deadbolts on one or more exterior doors were difficult to operate. Recommend that a qualified person repair as necessary.
Photo
Photo 53-1 brocken locking mechanism.
54) One or more windows that were designed to open and close were difficult to open and close. Recommend that a qualified person repair windows as necessary so they open and close easily.
Photo
Photo 54-1 
55) Metal thresholds at one or more exterior doors sagged or flexed when stepped on. Recommend that a qualified person repair as necessary to minimize sagging or movement, to ensure that the threshold is securely attached, and apply caulk or weather stripping materials to make a weatherproof seal.
Photo
Photo 55-1 
56) One or more interior doors wouldn't latch or were difficult to latch. Recommend that a qualified person repair as necessary. For example, by adjusting latch plates or locksets.
Photo
Photo 56-1 
57) One or more hinged exterior doors had no deadbolt lock installed and relied solely on the entry lockset for security. Recommend installing locksets on exterior doors where missing for added security.
Photo
Photo 57-1 
58)  Bathroom C window is broken consult a licensed contractor to repair or replace window.
Photo
Photo 58-1 
Wood Destroying Organism Findings
Table of contents
Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: No
Visible evidence of past wood-destroying insects: No
Visible evidence of damage by wood-destroying insects: No
Visible evidence of conditions conducive to wood-destroying organisms: No


Photo
Photo X-1 
Photo
Photo X-2 
Photo
Photo X-3 
Photo
Photo X-4 
Photo
Photo X-5 
Photo
Photo X-6 
Photo
Photo X-7 
Photo
Photo X-8 
Photo
Photo X-9 
Photo
Photo X-10 
Photo
Photo X-11 
Photo
Photo X-12 
Photo
Photo X-13 
Photo
Photo X-14 
Photo
Photo X-15 
Photo
Photo X-16 
Photo
Photo X-17 
Photo
Photo X-18 
Photo
Photo X-19 
Photo
Photo X-20 
Photo
Photo X-21 
Photo
Photo X-22 
Photo
Photo X-23 
Photo
Photo X-24 
Photo
Photo X-25 
Photo
Photo X-26 
Photo
Photo X-27 
Photo
Photo X-28 
Photo
Photo X-29 
Photo
Photo X-30 
Photo
Photo X-31 
Photo
Photo X-32 
Photo
Photo X-33 
Photo
Photo X-34 
Photo
Photo X-35 
Photo
Photo X-36 
Photo
Photo X-37 
Photo
Photo X-38 
Photo
Photo X-39 
Photo
Photo X-40 
Photo
Photo X-41 
Photo
Photo X-42 
Photo
Photo X-43 
Photo
Photo X-44 
Photo
Photo X-45 
Photo
Photo X-46 
Photo
Photo X-47 
Photo
Photo X-48 
Photo
Photo X-49 
Photo
Photo X-50 
Photo
Photo X-51 
Photo
Photo X-52 
Photo
Photo X-53 
Photo
Photo X-54 
Photo
Photo X-55 
Photo
Photo X-56 
Photo
Photo X-57 
Photo
Photo X-58 
Photo
Photo X-59 
Photo
Photo X-60 
Photo
Photo X-61 
Photo
Photo X-62 
Photo
Photo X-63 
Photo
Photo X-64 
Photo
Photo X-65 
Photo
Photo X-66 
Photo
Photo X-67 
Photo
Photo X-68 
Photo
Photo X-69 
Photo
Photo X-70 
Photo
Photo X-71 
Photo
Photo X-72 
Photo
Photo X-73 
Photo
Photo X-74 
Photo
Photo X-75 
Photo
Photo X-76 
Photo
Photo X-77 
Photo
Photo X-78 
Photo
Photo X-79 
Photo
Photo X-80 
Photo
Photo X-81 
Photo
Photo X-82 
Photo
Photo X-83 
Photo
Photo X-84 
Photo
Photo X-85 
Photo
Photo X-86 
Photo
Photo X-87 
Photo
Photo X-88 
Photo
Photo X-89 
Photo
Photo X-90 
Photo
Photo X-91 
Photo
Photo X-92 
Photo
Photo X-93 
Photo
Photo X-94 
Photo
Photo X-95 
Photo
Photo X-96 
Photo
Photo X-97 
Photo
Photo X-98 
Photo
Photo X-99 
Photo
Photo X-100 
Photo
Photo X-101 
Photo
Photo X-102 
Photo
Photo X-103 
Photo
Photo X-104 

Your default report footer here...